| 2021-03-05 08:29:12 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) STORAGE ROOM NEXT TO THE GARAGE SHOWS FLOOD VENTS - |
| | THE EXTERIOR GRADE APPEARS HIGH - PLEASE SHOW THE |
| | EXTERIOR GRADE TO COMPLY WITH FBC |
| | R322.2.2.1INSTALLATION OF OPENINGS. |
| | THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS |
| | INSTALLED SUCH THAT: THE BOTTOM OF EACH OPENING SHALL |
| | BE NOT MORE THAN 1 FOOT (305 MM) ABOVE THE HIGHER OF |
| | THE FINAL INTERIOR GRADE OR FLOOR AND THE FINISHED |
| | EXTERIOR GRADE IMMEDIATELY UNDER EACH OPENING. |
| | 2) THE STORAGE ROOM WALLS AND FLOORING BELOW BASE FLOOD |
| | ELEVATION NEED TO COMPLY WITH FBC R322.1.8 |
| | FLOOD-RESISTANT MATERIALS. |
| | BUILDING MATERIALS AND INSTALLATION METHODS USED FOR |
| | FLOORING AND INTERIOR AND EXTERIOR WALLS AND WALL |
| | COVERINGS BELOW THE ELEVATION REQUIRED IN SECTION |
| | R322.2 OR R322.3 SHALL BE FLOOD DAMAGE-RESISTANT |
| | MATERIALS THAT CONFORM TO THE PROVISIONS OF FEMA TB-2. |
| | 3) DRAWING C-1 HAS NOT BEEN REVISED - DRAWING "C1" |
| | SHOWS THE FFE AT 7.63 NAVD - PLEASE REVISE AS THE FLOOR |
| | PLANS WERE REVISED TO SHOW 8.13 NAVD |
| | 4) DRAWING C-1 - PLEASE SHOW ELEVATIONS USING NAVD - |
| | LEGEND ON DRAWING C-1 SHOWS ELEVATIONS USING NGVD BUT |
| | THE FLOOR ELEVATION IS SHOWN USING NAVD. |
| | ELEVATION CERTIFICATE = |
| | A8 PLEASE SHOW THE SQUARE FOOTAGE FOR THE STORAGE ROOM |
| | (ENCLOSED FLOOR). |
| | C2(A) PLEASE SHOW THE TOP OF ENCLOSURE FLOOR ELEVATION. |
| | C2(B) PLEASE SHOW THE TOP OF THE NEXT HIGHEST FLOOR |
| | (THE FIRST FLOOR OF THE HOUSE) |
| | C2(F) THE LOWEST ADJACENT GRADE IS ABOVE THE STORAGE |
| | ROOM AND GARAGE FLOOD VENTS? |
| | |
| | 5) ROOFING SYSTEM TO BE DEFERRED. |
| | |
| | |
| | |