| 2020-11-10 11:51:56 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20110337 |
| | 11/10/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REVISE THE GAS RISER DRAWING TO SHOW THE COMPLETE |
| | PIPING SYSTEM INCLUDING THE PIPING FOR THE FUTURE AND |
| | EXISTING APPLIANCES AND EQUIPMENT- SECTIONS G2412.3 & |
| | G2412.4 FBC RES.FG. |
| | |
| | A) SHOW THE TOTAL LOAD AND THE INDIVIDUAL LOADS OF THE |
| | MODIFIED SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 |
| | FBC RES.FG. |
| | |
| | B) SHOW THE TOTAL LENGTH DEVELOPED LENGTH OF THE PIPING |
| | FROM THE METER TO THE MOST REMOTE OUTLET, AND THE |
| | INDIVIDUAL BRANCH LENGTHS, INCLUDING ALL CUT LENGTHS OF |
| | PIPING- SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.FG. |
| | |
| | C) INDICATE THE PIPING TO THE FUTURE GENERATOR AND |
| | BARBECUES WILL BE CAPPED GAS TIGHT- SECTION G2415.15 |
| | FBC RES.FG. |
| | |
| | 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |