| 2020-11-30 11:35:33 | PLAN REVIEW / ELECTRIC |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. AIC: - N/A |
| | |
| | 2. SMOKE DETECTORS ARE MISSING ON 1ST FLOOR. |
| | |
| | R314.3 LOCATION. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 1. 1.IN EACH SLEEPING ROOM. |
| | 2. 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE |
| | IMMEDIATE VICINITY OF THE BEDROOMS. |
| | 3. 3.ON EACH ADDITIONAL STORY OF THE DWELLING, |
| | INCLUDING BASEMENTS AND HABITABLE ATTICS AND NOT |
| | INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS. IN |
| | DWELLINGS OR DWELLING UNITS WITH SPLIT LEVELS AND |
| | WITHOUT AN INTERVENING DOOR BETWEEN THE ADJACENT |
| | LEVELS, A SMOKE ALARM INSTALLED ON THE UPPER LEVEL |
| | SHALL SUFFICE FOR THE ADJACENT LOWER LEVEL PROVIDED |
| | THAT THE LOWER LEVEL IS LESS THAN ONE FULL STORY BELOW |
| | THE UPPER LEVEL. |
| | 4. 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 |
| | FEET (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF |
| | A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS |
| | THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED |
| | BY SECTION R314.3 |
| | |
| | 3. PROVIDE CARBON MONOXIDE DETECTORS: |
| | |
| | R314.5 COMBINATION ALARMS. |
| | COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE |
| | PERMITTED TO BE USED IN LIEU OF SMOKE ALARMS. |
| | |
| | R315.1 CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES. |
| | |
| | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| | FEET OF EACH SLEEPING ROOM. |
| | |
| | 4. HIGH EFFICACY LAMPS |
| | |
| | PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". |
| | |
| | A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 |
| | |
| | 5. PROVIDE GFCI OUTLET AT REAR OF STRUCTURE. |
| | |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| | |
| | 6. RE: RISER DIAGRAHM - PANELS A AND B: |
| | |
| | E3607.3.1 EQUIPMENT GROUNDING CONDUCTOR. |
| | AN EQUIPMENT GROUNDING CONDUCTOR AS DESCRIBED IN |
| | SECTION E3908 SHALL BE RUN WITH THE SUPPLY CONDUCTORS |
| | AND CONNECTED TO THE BUILDING OR STRUCTURE |
| | DISCONNECTING MEANS AND TO THE GROUNDING ELECTRODE(S). |
| | THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE USED FOR |
| | GROUNDING OR BONDING OF EQUIPMENT, STRUCTURES OR FRAMES |
| | REQUIRED TO BE GROUNDED OR BONDED. THE EQUIPMENT |
| | GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH |
| | SECTION E3908.12. ANY INSTALLED GROUNDED CONDUCTOR |
| | SHALL NOT BE CONNECTED TO THE EQUIPMENT GROUNDING |
| | CONDUCTOR OR TO THE GROUNDING ELECTRODE(S). [250.32(B) |
| | AND TABLE 250.122] |
| | |
| | 1ST MEANS OF DISCONNECT |
| | E3607.2 LOCATION OF GROUNDING ELECTRODE CONDUCTOR |
| | CONNECTION. |
| | THE GROUNDING ELECTRODE CONDUCTOR SHALL BE CONNECTED TO |
| | THE GROUNDED SERVICE CONDUCTOR AT ANY ACCESSIBLE POINT |
| | FROM THE LOAD END OF THE OVERHEAD SERVICE CONDUCTORS, |
| | SERVICE DROP, UNDERGROUND SERVICE CONDUCTORS, OR |
| | SERVICE LATERAL TO AND INCLUDING THE TERMINAL OR BUS TO |
| | WHICH THE GROUNDED SERVICE CONDUCTOR IS CONNECTED AT |
| | THE SERVICE DISCONNECTING MEANS. A GROUNDING CONNECTION |
| | SHALL NOT BE MADE TO ANY GROUNDED CIRCUIT CONDUCTOR ON |
| | THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS, |
| | EXCEPT AS PROVIDED IN SECTION E3607.3.2. [250.24(A)(1) |
| | AND (A)(5)] NEC 250.24 (A) |
| | |
| | 7. PROVIDE CIRCUT FOR T/W/H IGNITER CIRCUTS. |
| | |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE E3602.2 |
| | |
| | 8. PROVIDE INTERSYSTEM BONDING TERMINAL. |
| | |
| | PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |