| 2020-11-16 10:18:29 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | FBC B 107.2.1, | | | 1) PLEASE PROVIDE THE MISSING PRODUCT APPROVAL SHEETS | | | AND WINDLOAD PRESSURE CALCULATION SHEETS THAT INDICATE | | | THE ANCHOR FASTENING PATTERNS AND ADHHESIVE | | | PRODUCT/APPLICATION DIRECTIONS FOR MEETING UPLIFT | | | REQUIREMENTS. | | | | | | 2) PLEASE PROVIDE THE MOISTURE SURVEY FOR THE | | | LIGHTWEIGHT CONCREET. | | | |
|