| 2020-12-05 08:51:37 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20110321 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE CHECK THE CFM?S OF THE AHU?S, THE AHU?S ARE |
| | PROVIDING 2000CFM?S OF AIR FLOW TO EACH AREA. THE |
| | MECHANICAL LEGEND INDICATES THAT THE AHU?S MAX AIR FLOW |
| | IS 1890 @ .5 INCH. FBC EC C403.2.1 |
| | |
| | 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC EC 403.2.1 |
| | |
| | 3) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION BASED ON |
| | THE USE OF EACH SPACE. IT APPEARS THAT THERE ARE |
| | OFFICES AND SHOWROOMS IN THIS BUILDING. EACH WOULD BE |
| | FIGURED DIFFERENTLY BASED ON TABLE 403.3.1.1 FBC M. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |