Plan Review Notes
Plan Review Notes For Permit 20110320
Permit Number 20110320
Review Stop M
Sequence Number 2
Notes
Date Text
2021-03-10 12:07:311ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20110320
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN THIS BUSINESS YOU HAVE OFFICES, 2 CONFERENCE
 ROOMS AND 2 LOUNGE AREAS. PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS FOR EACH OF THESE AREAS. EACH DIFFERENT
 USE OF SPACE IN THIS BUSINESS MUST HAVE A SEPARATE
 OUTDOOR AIR CALCULATION. THE LOUNGE AREAS MUST MATCH UP
 WITH EITHER ?CAFETERIA, FAST FOOD? OR DINING ROOMS.
 USING THE ASHRAE 62.1-2013 THE AREA OUTDOOR RATE FOR
 CAFETERIA/FAST FOOD IS .18 AND THE PEOPLE OUTDOOR RATE
 IS 7.5 THE LOUNGE OUTDOOR AIR WOULD BE 495 CFM. THIS
 SHOULD BE USED FOR THE LOUNGE AREA.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  