| Date |
Text |
| 2021-01-05 12:10:43 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20110300 |
| | ADD: 701 S. ROSEMARY AVE. #159 / STARBUCKS BUILD OUT |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 954-583-9990 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. JAN. 05//2021 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) COMPLIED.LIFE SAFETY SHEET: |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6A) 2ND REQUEST. TESTING REPORTS AND THEIR TECHNICAL |
| | SHEETS ARE TO BE EITHER A MIAMI-DADE NOA OR FLORIDA |
| | APPROVAL. |
| | SHEET APX-201 & A-601 NEW STOREFRONT DOOR AND WINDOW |
| | SYSTEM. THE SYSTEM TO BE YKK YHS 50 FI SYSTEM WITH |
| | 1- 5/16TH INCH IMPACT/ INSULATED GLASS. PLEASE SUBMIT |
| | THE PRODUCT APPROVALS FOR THESE SYSTEMS. |
| | COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | |
| | 6B)2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 6C) 2ND REQUEST. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 6D) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6E) NEW COMMENT. YKKAP SERIES YHS50 FI INSIDE GLAZED |
| | ALUMINUM STOREFRONT SYSTEM IS NOT THE COMPLETE FLORIDA |
| | APPROVAL 14218. THE TOTAL REPORT INCLUDING THE |
| | TECHNICAL SHEETS ARE REQUIRED. THE RESPONCE SHEET |
| | STATES THE DESIGNER OF RECORD WILL REVIEW SHOP |
| | DRAWINGS. PLEASE NOTE WE REVIEW THE PRODUCT APPROVALS |
| | TO SEE IF THE SIZE OF THE GLAZING AND MULLIONS WILL |
| | MEET THE REQUIRED PRESSURES. THIS IS WHY WE GIVE THE |
| | DESIGNER OF RECORD A CHOICE, EITHER WE REVIEW ALL OF |
| | THE COMPONENT & CLADDING BEFORE PERMIT ISSUANCE OR THE |
| | DESIGNER OF RECORD CAN ASK FOR A DEFERRED SUBMITTAL |
| | UNTIL AFTER PERMIT ISSUANCE. IT APPEARS WITH THE ATEMPT |
| | AT SUBMITTING PRODUCT APPROVALS WE WILL BE REVIEWING |
| | THEM NOW. IF THE CONTRACTOR CHANGES PRODUCT APPROVALS |
| | AFTER PERMIT ISSUANCE, EACH PRODUCT APPROVAL CHANGED IS |
| | CONSIDERED A SEPARATE REVISION AND REVIEWS WITH |
| | ASSOCIATED FEES. |
| | |
| | 6F) THE SUBMITTED TREMCO YKK35H GASKET SYSTEM SHOULD BE |
| | PART OF THE PRODUCT APPROVAL FOR THE DOOR SYSTEM, |
| | EITHER A MIAMI-DADE NOA OR FLORIDA APPROVAL. |
| | |
| | 6G) YKKAP SERIES 50H ALUMINUM OUTSWING DOOR FL 16554, |
| | AGAIN THIS IS ONLY A PORTION OF THE FLORIDA |
| | APPROVAL.THE RESPONCE SHEET STATES THE DESIGNER OF |
| | RECORD WILL REVIEW SHOP DRAWINGS. PLEASE NOTE WE REVIEW |
| | THE PRODUCT APPROVALS TO SEE IF THE SIZE OF THE GLAZING |
| | AND MULLIONS WILL MEET THE REQUIRED PRESSURES. THIS IS |
| | WHY WE GIVE THE DESIGNER OF RECORD A CHOICE, EITHER WE |
| | REVIEW ALL OF THE COMPONENT & CLADDING BEFORE PERMIT |
| | ISSUANCE OR THE DESIGNER OF RECORD CAN ASK FOR A |
| | DEFERRED SUBMITTAL UNTIL AFTER PERMIT ISSUANCE. IT |
| | APPEARS WITH THE ATEMPT AT SUBMITTING PRODUCT APPROVALS |
| | WE WILL BE REVIEWING THEM NOW. IF THE CONTRACTOR |
| | CHANGES PRODUCT APPROVALS AFTER PERMIT ISSUANCE, EACH |
| | PRODUCT APPROVAL CHANGED IS CONSIDERED A SEPARATE |
| | REVISION AND REVIEWS WITH ASSOCIATED FEES. |
| | |
| | |
| | 7) 2ND REQUEST. THE RESPONCE TO THIS COMMENT STATES |
| | THAT 1/2 INCH OSB SHEATHING IS ALLOWED AS INDICATED IN |
| | 603.1 IF IT IS FIRE RETARDANT TREATED WOOD. I TOTALLY |
| | AGREE, THE PLANS DO NOT INDICATE THAT THE OSB SHEATHING |
| | IS FIRE RETARDENT TREATED. 2017 FBC-B SECTION |
| | 603.1.1.2. PLEASE PROVIDE THE PRODUCT REPORT OFR |
| | COMPLIANCE WITH THE ICC FIRE CODE COMPLIANCE REPORT FOR |
| | THE BRAND OF FIRE RETARDENT TREATED OSB BOARD TO BE |
| | INSTALLED. |
| | |
| | 1 REVIEW COMMENT. SHEET S2.1 FOUNDATION NOTE # 6 & |
| | SHEET S3.2 INDICATES ALL EXTERIOR WALL SHEATHING NOT |
| | SPECIFIED AS (SHEAR WALL SHEATHING) IS TO BE ? INCH OSB |
| | SHEATHING. PLEASE REFER BACK TO SHEET G-001 TO THE |
| | MINIMUM BUILDING TYPE AS TYPE: II-B SPRINKLERED. PLEASE |
| | REVIEW SECTION 603.1.1FIRE RETARDANT TREATED WOOD SHALL |
| | BE PERMITTED IN: 1.2 NONBEARING EXTERIOR WALLS WHERE |
| | FIRE RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED. |
| | SHEET S3.2 STATES ABOVE THE NEW STOREFRONT GLAZING |
| | SYSTEM ? INCH SHEATHING. PLEASE SPECIFY THE TYPE OF |
| | SHEATHING TO BE INSTALLED IN ACCORDANCE WITH |
| | 603.1.1FIRE RETARDANT TREATED WOOD. |
| | |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |