Plan Review Notes
Plan Review Notes For Permit 20110300
Permit Number 20110300
Review Stop B
Sequence Number 2
Notes
Date Text
2021-01-05 12:10:43WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110300
 ADD: 701 S. ROSEMARY AVE. #159 / STARBUCKS BUILD OUT
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-583-9990
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JAN. 05//2021
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) COMPLIED.LIFE SAFETY SHEET:
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6A) 2ND REQUEST. TESTING REPORTS AND THEIR TECHNICAL
 SHEETS ARE TO BE EITHER A MIAMI-DADE NOA OR FLORIDA
 APPROVAL.
 SHEET APX-201 & A-601 NEW STOREFRONT DOOR AND WINDOW
 SYSTEM. THE SYSTEM TO BE YKK YHS 50 FI SYSTEM WITH
 1- 5/16TH INCH IMPACT/ INSULATED GLASS. PLEASE SUBMIT
 THE PRODUCT APPROVALS FOR THESE SYSTEMS.
 COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
  
 6B)2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 6C) 2ND REQUEST. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6D) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6E) NEW COMMENT. YKKAP SERIES YHS50 FI INSIDE GLAZED
 ALUMINUM STOREFRONT SYSTEM IS NOT THE COMPLETE FLORIDA
 APPROVAL 14218. THE TOTAL REPORT INCLUDING THE
 TECHNICAL SHEETS ARE REQUIRED. THE RESPONCE SHEET
 STATES THE DESIGNER OF RECORD WILL REVIEW SHOP
 DRAWINGS. PLEASE NOTE WE REVIEW THE PRODUCT APPROVALS
 TO SEE IF THE SIZE OF THE GLAZING AND MULLIONS WILL
 MEET THE REQUIRED PRESSURES. THIS IS WHY WE GIVE THE
 DESIGNER OF RECORD A CHOICE, EITHER WE REVIEW ALL OF
 THE COMPONENT & CLADDING BEFORE PERMIT ISSUANCE OR THE
 DESIGNER OF RECORD CAN ASK FOR A DEFERRED SUBMITTAL
 UNTIL AFTER PERMIT ISSUANCE. IT APPEARS WITH THE ATEMPT
 AT SUBMITTING PRODUCT APPROVALS WE WILL BE REVIEWING
 THEM NOW. IF THE CONTRACTOR CHANGES PRODUCT APPROVALS
 AFTER PERMIT ISSUANCE, EACH PRODUCT APPROVAL CHANGED IS
 CONSIDERED A SEPARATE REVISION AND REVIEWS WITH
 ASSOCIATED FEES.
  
 6F) THE SUBMITTED TREMCO YKK35H GASKET SYSTEM SHOULD BE
 PART OF THE PRODUCT APPROVAL FOR THE DOOR SYSTEM,
 EITHER A MIAMI-DADE NOA OR FLORIDA APPROVAL.
  
 6G) YKKAP SERIES 50H ALUMINUM OUTSWING DOOR FL 16554,
 AGAIN THIS IS ONLY A PORTION OF THE FLORIDA
 APPROVAL.THE RESPONCE SHEET STATES THE DESIGNER OF
 RECORD WILL REVIEW SHOP DRAWINGS. PLEASE NOTE WE REVIEW
 THE PRODUCT APPROVALS TO SEE IF THE SIZE OF THE GLAZING
 AND MULLIONS WILL MEET THE REQUIRED PRESSURES. THIS IS
 WHY WE GIVE THE DESIGNER OF RECORD A CHOICE, EITHER WE
 REVIEW ALL OF THE COMPONENT & CLADDING BEFORE PERMIT
 ISSUANCE OR THE DESIGNER OF RECORD CAN ASK FOR A
 DEFERRED SUBMITTAL UNTIL AFTER PERMIT ISSUANCE. IT
 APPEARS WITH THE ATEMPT AT SUBMITTING PRODUCT APPROVALS
 WE WILL BE REVIEWING THEM NOW. IF THE CONTRACTOR
 CHANGES PRODUCT APPROVALS AFTER PERMIT ISSUANCE, EACH
 PRODUCT APPROVAL CHANGED IS CONSIDERED A SEPARATE
 REVISION AND REVIEWS WITH ASSOCIATED FEES.
  
  
 7) 2ND REQUEST. THE RESPONCE TO THIS COMMENT STATES
 THAT 1/2 INCH OSB SHEATHING IS ALLOWED AS INDICATED IN
 603.1 IF IT IS FIRE RETARDANT TREATED WOOD. I TOTALLY
 AGREE, THE PLANS DO NOT INDICATE THAT THE OSB SHEATHING
 IS FIRE RETARDENT TREATED. 2017 FBC-B SECTION
 603.1.1.2. PLEASE PROVIDE THE PRODUCT REPORT OFR
 COMPLIANCE WITH THE ICC FIRE CODE COMPLIANCE REPORT FOR
 THE BRAND OF FIRE RETARDENT TREATED OSB BOARD TO BE
 INSTALLED.
  
 1 REVIEW COMMENT. SHEET S2.1 FOUNDATION NOTE # 6 &
 SHEET S3.2 INDICATES ALL EXTERIOR WALL SHEATHING NOT
 SPECIFIED AS (SHEAR WALL SHEATHING) IS TO BE ? INCH OSB
 SHEATHING. PLEASE REFER BACK TO SHEET G-001 TO THE
 MINIMUM BUILDING TYPE AS TYPE: II-B SPRINKLERED. PLEASE
 REVIEW SECTION 603.1.1FIRE RETARDANT TREATED WOOD SHALL
 BE PERMITTED IN: 1.2 NONBEARING EXTERIOR WALLS WHERE
 FIRE RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED.
 SHEET S3.2 STATES ABOVE THE NEW STOREFRONT GLAZING
 SYSTEM ? INCH SHEATHING. PLEASE SPECIFY THE TYPE OF
 SHEATHING TO BE INSTALLED IN ACCORDANCE WITH
 603.1.1FIRE RETARDANT TREATED WOOD.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT