Plan Review Notes
Plan Review Notes For Permit 20110300
Permit Number 20110300
Review Stop P
Sequence Number 1
Notes
Date Text
2020-11-19 16:06:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PROVIDE NOTE ON PLANS THAT STATES "DRINKING WATER
 SHALL BE PROVIDED IN A FLAT BOTTOM CUP FREE OF CHARGE"
  
 2A.RE: PLAN SHEET G-003; 2017 FLORIDA BUILDING
 CODE-ACCESSIBILITY IS THE PREVAILING CODE FOR THIS
 PROJECT. THIS PLAN SEEMS TO REFLECT A STANDARD OTHER
 THAN THE 2017 FLORIDA BUILDING CODE-ACCESSIBILITY (I.E.
 DETAIL 16 REFERENCES SECTION 4.16 OF WHAT STANDARD. THE
 PREVAILING CODE WOULD BE FBC ACC SECTIONS 604.2 THROUGH
 604.8 AND 609.1 THROUGH 609.4 .) PER WPB FBC 107.2.1,
 PROVIDE REFERENCE AND DETAILS AS APPLICABLE TO THE 2017
 FLORIDA BUILDING CODE-ACCESSIBILITY. REFLECT THE
 REQUIREMENTS LISTED IN COMMENT 1B OR COMPLY WITH
 COMMENT 2B. ADDITIONALLY, DELETE DETAILS PERTAINING TO
 ITEMS NOT INCLUDED IN THE PROJECT SUCH AS THE URINAL
 AND THE DRINKING FOUNTAIN.
  
 2B.RE: PLAN SHEETS I-401 7 I-401.1; PER WPB FBC
 107.2.1, TO SHOW COMPLIANCE WITH THE 2017 FLORIDA
 BUILDING CODE-ACCESSIBILITY FBC ACC CHAPTERS 3 AND 6
 INDICATE ON THESE PLAN SHEETS THE FOLLOWING:
 A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL PER
 FBC ACC 604.5.1
 D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. SEATS SHALL NOT BE
 SPRUNG TO RETURN TO A LIFTED POSITION PER FBC ACC
 604.4.
 H. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE
 I. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 J. PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 K. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 L. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE (NOT THE BOTTOM EDGE OF THE FIXTURE)
 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER
 FBC ACC 603.3.
 M. SHOW CLEAR FLOOR SPACES LAVATORY. THE CLEAR FLOOR OR
 GROUND SPACE SHALL BE 30 INCHES MINIMUM BY 48 INCHES
 MINIMUM AND COMPLY WITH FBC ACC SECTION 305.
  
 3.RE: P-001; PER WPB FBC 107.2.1. AS THERE DOES NOT
 APPEAR TO BE ANY GAS REQUIRED FOR THIS PROJECT, DELETE
 REFERENCE TO NATURAL GAS PIPING.
  
 4.RE: P-001; PER WPB FBC 107.2.1, PROVIDE THE PROJECT
 MANUAL REFERENCED IN PIPING. PIPING MATERIALS AND
 INSULATION MATERIALS SPECIFICATIONS SHALL BE PROVIDED.
 IF THE INFORMATION REQUESTED IS NOT IN THE PROJECT
 MANUAL, PROVIDE THE INFORMATION.
  
 5.P-501/DETAIL 8: TYPE 3 WATER TREATMENT; DETAIL DOES
 NOT CLEARLY SHOW PIPING. PER WPB FBC 107.2.1, PROVIDE
 SUPPLEMENTAL SCHEMATIC/FLOW CHART/P&ID CLEARLY
 INDICATING THE PIPING ARRANGEMENT. SHOW ALL VALVES,
 BACKFLOW PREVENTERS, TEES AND APPURTENANCES WITHOUT
 BACKGROUND.
  
 6.PER WPB FBC 107.2.1, SHOW ON THE WATER RISER DIAGRAM
 ALL IN LINE BACKFLOW PREVENTERS.
  
 7.PER WPB FBC 107.2.1, PROVIDE A BACKFLOW PREVENTION
 DEVICE SCHEDULE.
  
 8. PER WPB FBC 107.2.1, SPECIFY AND PROVIDE BACKFLOW
 PREVENTION DEVICE COMPLYING WITH FBC PL SECTION 608 FOR
 THE HOSE BIB(S).
  
 9.PER FBC PL 606.1, PROVIDE FULL-OPEN VALVES ON THE TOP
 OF EVERY WATER DOWN-FEED PIPE. SHOW ON WATER RISER
 DIAGRAM.
  
 10. RE: P-501/DETAIL 6; TRAP PRIMER DETAIL. THIS DETAIL
 IS NOTED AND CONFORMS TO FBC PL 1002.4.1.1. PER WPB FBC
 107.2.1, PROVIDE THE FOLLOWING:
 A. REQUIRED TRAP PRIMER CONNECTIONS TO FLOOR DRAINS ON
 SANITARY RISER DIAGRAM.
 B. TRAP PRIMER BRANCH PIPING TO TRAP PRIMER DEVICE(S)
 ON WATER RISER DIAGRAM. SHOW TRAP PRIMER DEVICE AND
 WHERE APPLICABLE, SHOW DISTRIBUTION UNIT. PLEASE NOTE
 THAT THE FLOOR DRAIN AT THE SERVICE ENTRANCE DOES
 REQUIRE TRAP SEAL PROTECTION AND SHALL BE PROTECTED BY
 ONE OF THE METHODS IN FBC PL SECTIONS 1002.4.1.1
 THROUGH 1002.4.1.4.
  
 11.RE: P-601 PLUMBING SCHEDULE. IT APPEARS OBVIOUS THAT
 SPECIFIC FIXTURES /EQUIPMENT IS TO BE FURNISHED BUT TAG
 NUMBERS ATTACHED TO DESCRIPTIONS IS NOT ADEQUATE. MORE
 INFORMATION IS REQUIRED FOR PLUMBING FIXTURES. PER WPB
 FBC 107.2.1, PROVIDE MANUFACTURER'S MODEL
 NUMBERS/SPECIFICATIONS/INSTALLATION MANUALS FOR ALL
 FIXTURES, EQUIPMENT AND APPURTENANCES. INCLUDE WALL
 SUPPORTS FOR LAVATORIES. A PROJECT MANUAL IS REFERENCED
 ON P-001 AND NEEDS TO BE SUBMITTED. IF THE INFORMATION
 REQUESTED IS IN THE PROJECT MANUAL AND IS CLEAR, THEN
 PROVIDE A NOTE ON THE PLUMBING SCHEDULE REFERENCING
 THAT. IF NOT, PROVIDE THE INFORMATION.
  
 12.RE: P-601 PLUMBING SCHEDULE. NOTE ON SCHEDULE ITEMS
 THAT REQUIRE BACKFLOW PREVENTERS AND T THE
 MANUFACTURER'S MODEL NUMBER
  
 13. PER WPB FBC 107.2.1, SUBMIT A SLAB REPAIR DETAIL.
 SHOW THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF
 THE CONCRETE TO BE REPLACED, AND THE PSI OF THE
 CONCRETE. SHOW THE SIZE AND LENGTH OF THE DOWELS, THE
 MINIMUM EMBEDMENT DEPTH INTO THE EXISTING SLAB, THE
 ANCHORING MATERIAL FOR THE DOWELS AND THE SPACING OF
 THE DOWELS ON CENTER. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AND THE REQUIRED VAPOR
 BARRIER OVER WELL-COMPACTED SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 14. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR POTABLE
 WATER CONNECTION TO THE DISHWASHER. INCLUDE VALVES,
 BACKFLOW PREVENTION DEVICE, STRAINER(S), PRV AND ANY
 APPURTENANCES REQUIRED.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20110300 701 S ROSEMARY AVE # 159
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved