2020-11-24 15:25:36CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) E-501 AND E-601: PANEL B IS SHOWN AS 400 AMPS, MLO
 ON RISER DIAGRAM BUT PANEL SCHEDULE SPECIFIES A 225
 AMPS PANEL. PLEASE CORRECT DISCREPANCIES.
 2) E-501 AND E-601: PANEL A ON RISER DIAGRAM SHOWS A
 400 AMPS MCB. WHAT IS THIS BREAKER FOR? PANEL SCHEDULE
 A HAS A 225 AMPS MCB AND IS RATED FOR 225 AMPS AND
 FEEDER TO PANEL B IS SHOWN AS A LUG LOAD ON PANEL A
 SCHEDULE. FEEDER FROM PANEL A TO PANEL B SHOULD BE
 RATED FOR 225 AMPS MINIMUM AND #3/0 IS ONLY 200 AMPS.
 NEC 240.21(B)
 3) E-501 AND E-601: FEEDER FROM 75 KVA TRANSFORMER TO
 PANEL A IS SHOWN AS #3/0 WITH AMPACITY OF 200 AMPS AND
 IT REQUIRES CONDUCTORS RATED AT LEAST 225 AMPS. NEC
 240.21(C)
 4) E-501 (RISER DIAGRAM): GROUNDING ELECTRODE CONDUCTOR
 FOR 75 KVA TRANSFORMER IS TOO SMALL. PLEASE SIZE AS PER
 NEC TABLE 250.66 AND BASED ON CORRECTED FEEDER SIZE
 FROM TRANSFORMER TO PANEL A MENTIONED ON ITEM 3. NEC
 250.30(5).
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  