| 2020-11-24 15:25:36 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. |
| | |
| | 1) E-501 AND E-601: PANEL B IS SHOWN AS 400 AMPS, MLO |
| | ON RISER DIAGRAM BUT PANEL SCHEDULE SPECIFIES A 225 |
| | AMPS PANEL. PLEASE CORRECT DISCREPANCIES. |
| | 2) E-501 AND E-601: PANEL A ON RISER DIAGRAM SHOWS A |
| | 400 AMPS MCB. WHAT IS THIS BREAKER FOR? PANEL SCHEDULE |
| | A HAS A 225 AMPS MCB AND IS RATED FOR 225 AMPS AND |
| | FEEDER TO PANEL B IS SHOWN AS A LUG LOAD ON PANEL A |
| | SCHEDULE. FEEDER FROM PANEL A TO PANEL B SHOULD BE |
| | RATED FOR 225 AMPS MINIMUM AND #3/0 IS ONLY 200 AMPS. |
| | NEC 240.21(B) |
| | 3) E-501 AND E-601: FEEDER FROM 75 KVA TRANSFORMER TO |
| | PANEL A IS SHOWN AS #3/0 WITH AMPACITY OF 200 AMPS AND |
| | IT REQUIRES CONDUCTORS RATED AT LEAST 225 AMPS. NEC |
| | 240.21(C) |
| | 4) E-501 (RISER DIAGRAM): GROUNDING ELECTRODE CONDUCTOR |
| | FOR 75 KVA TRANSFORMER IS TOO SMALL. PLEASE SIZE AS PER |
| | NEC TABLE 250.66 AND BASED ON CORRECTED FEEDER SIZE |
| | FROM TRANSFORMER TO PANEL A MENTIONED ON ITEM 3. NEC |
| | 250.30(5). |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | SINCERELY, |
| | |
| | ENRIQUE QUINONEZ |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |