Plan Review Notes
Plan Review Notes For Permit 20110300
Permit Number 20110300
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-10 10:56:28WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110300
 ADD: 701 S. ROSEMARY AVE. #159 / STARBUCKS BUILD OUT
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-583-9990
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 10TH/2020
 ACTION: DENIED
  
 1) STRUCTURAL CALCULATIONS 20 PAGES BY STEPHEN SACCO P.
 E. THE SUBMITTED DOCUMENT DOES NOT HAVE THE COVERSHEET
 WITH NUMBER OF PAGES COVERED UNDER THIS SEAL, NOR A
 INDEX SHEET WITH SEAL NOR EACH PAGE SIGNED AND SEALED.
 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH
 LISTED PAGES OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 2) LIFE SAFETY SHEET:
 2A) UNDER THE OCCUPANCY COUNT THE PLAN STATES BEVERAGE
 PREP (KITCHEN) 342 SQ. FT./100 SQ. FT./OCC = 3
 OCCUPANTS. PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2.
 FOR COMMERCIAL KITCHENS THE OCCUPANT LOAD FACTOR IS 200
 GROSS NOT 100. PLEASE UPDATE PLANS AND OCCUPANT LOAD
 FOR THE KITCHEN.
 2B) UNDER THE OCCUPANCY COUNT THE PLAN STATES THE
 WORKROOM (STORAGE) 445 SQ. FT./ 300= 1 OCCUPANT. PLEASE
 BE ADVISED THAT YOU ALWAYS ROUND UP TO WHOLE OCCUPANTS.
 2017 FBC-B TABLE 1004.1.2 AND 2015 IBC-B COMMENTARY.
 THE 445 SQ. FT./ 300= 2 OCCUPANTS.
 2C) FOR BOTH THE ASSEMBLY STANDING AND SEATED BOTH
 NUMBERS ALSO NEED TO BE INCREASED BY ONE SINCE THE
 REMAINDER WAS ALSO DROPPED OFF. 2017 FBC-B TABLE
 1004.1.2 AND 2015 IBC-B COMMENTARY.
 3) SHEET G-002.1 ALSO SHOWS THE SAME PROBLEMS WITH THE
 OCCUPANT LOAD COUNT AS ON THE LIFE SAFETY PLAN, PLEASE
 UPDATE CHART. 2017 FBC-B TABLE 1004.1.2 AND 2015 IBC-B
 COMMENTARY.
 4) SHEET G-003 ACCESSIBILITY GUIDELINES.
 4A) DETAIL # 13 DRINKING FOUNTAINS. DOES NOT STATE WHAT
 THE SPOUT OUTLET HEIGHTS ARE, SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE SECTION SPOUT OUTLETS/
 DRINKING FOUNTAINS. 2017 ACCESS. CODE. SPOUT OUTLETS
 SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
 4B) DETAIL # 13 DRINKING FOUNTAINS: SHOWS A SIDE
 APPROACH PROVIDE COMPLIANCE WITH: 602.2 CLEAR FLOOR
 SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305,
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTION, SIDE APPROACH IS FOR CHILDREN.
 4C) DETAIL # 10 LAVATORIES AND MIRRORS PLEASE SHOW
 COMPLIANCE WITH 2017 FBC-ACCESS. CODE SECTION 606.5
 EXPOSED PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES
 UNDER LAVATORIES AND SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT.
 4D) DETAIL # 16: SIDE AND BACK GRAB BAR HEIGHTS TO
 COMPLY WITH: 2017 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
 4E) DETAIL # 16 TOILET PAPER DISPENSERS. FBC-ACCESS.
 CODE 604.7. THE TOILET PAPER DISPENSER SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
 5) SHEET 401.1 ENLARGED RESTROOM ELEVATIONS. DETAILS 3
 & 7 BOTH SHOW THE BACKWALL BEHIND THE WATER CLOSET
 TILED TO A HEIGHT OF 3 FEET 4 INCHES. PLEASE SHOW
 COMPLIANCE WITH THE 17 FBC-B 1210.2.2. WALLS &
 PARTITIONS. WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS
 THAN 4 FEET ABOVE THE FLOOR (TILE), EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
 6A) SHEET APX-201 & A-601 NEW STOREFRONT DOOR AND
 WINDOW SYSTEM. THE SYSTEM TO BE YKK YHS 50 FI SYSTEM
 WITH
 1- 5/16TH INCH IMPACT/ INSULATED GLASS. PLEASE SUBMIT
 THE PRODUCT APPROVALS FOR THESE SYSTEMS.
 COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
  
 6B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 6C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6D) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) SHEET S2.1 FOUNDATION NOTE # 6 INDICATES ALL
 EXTERIOR WALL SHEATHING NOT SPECIFIED AS (SHEAR WALL
 SHEATHING) IS TO BE ? INCH OSB SHEATHING. PLEASE REFER
 BACK TO SHEET G-001 TO THE MINIMUM BUILDING TYPE AS
 TYPE: II-B SPRINKLERED. PLEASE REVIEW SECTION
 603.1.1FIRE RETARDANT TREATED WOOD SHALL BE PERMITTED
 IN: 1.2 NONBEARING EXTERIOR WALLS WHERE FIRE
 RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED. SHEET
 S3.2 STATES ABOVE THE NEW STOREFRONT GLAZING SYSTEM ?
 INCH SHEATHING. PLEASE SPECIFY THE TYPE OF SHEATHING TO
 BE INSTALLED IN ACCORDANCE WITH 603.1.1FIRE RETARDANT
 TREATED WOOD.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  