| 2020-12-16 12:56:34 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110271 |
| | 12/15/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | 1) SHEETS C13, L05-L08: PLEASE NOTE SEPARATE PERMITS |
| | AND PLANS ARE REQUIRED FOR THE POTABLE WATER SERVICE |
| | BACKFLOW PREVENTER, GREASE INTERCEPTOR, AND THE |
| | IRRIGATION SYSTEM. COMPLETE SETS OF PLANS AND |
| | SPECIFICATIONS ARE REQUIRED FOR REVIEW AND PERMIT |
| | ISSUANCE- SECTION 107.2.1 WPB. |
| | |
| | 2) SHEET CS: PLEASE INCLUDE THE REQUIRED SERVICE SINK |
| | IN THE PLUMBING FIXTURE DATA- TABLE 403.3 FBC P. |
| | |
| | 3) EQ-1, P1 & P4: THE MOP SINK AND FLOOR DRAIN BY THE |
| | WATER HEATER, THE FLOOR SINKS AND HUB DRAINS RECEIVING |
| | CONDENSATE DRAINAGE FROM REFRIGERATORS AND ICE MAKERS |
| | IN THE COFFEE AND TRASH AREAS, AND THE F5 HAND SINKS |
| | SHALL NOT CONNECT INTO THE GREASE WASTE LINE IN |
| | COMPLIANCE WITH SECTION 1003.3.1 FBC P. PLEASE NOTE |
| | THAT GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| | DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES AND |
| | EQUIPMENT THAT ALLOW FATS, OILS, OR GREASE TO BE |
| | DISCHARGED. BASED ON THE PLAN THE RESTRICTED FIXTURES |
| | DO NOT APPEAR TO BE SIGNIFICANT GREASE CONTRIBUTORS. |
| | PLEASE REVIEW THE INTERNATIONAL PLUMBING CODE- 2015 |
| | COMMENTARY ON GREASE INTERCEPTORS FOR FURTHER |
| | CLARIFICATION. |
| | |
| | 4) P2 & P4: PROVIDE A FULL OPEN TYPE SHUTOFF VALVE FOR |
| | THE 2 IN. CW WATER SERVICE/DISTRIBUTION LINE AT THE |
| | ENTRANCE OF THE BUILDING- SECTION 606.1(2) FBC P. |
| | |
| | 5) P2 & P4: IN ACCORDANCE WITH SECTION 608.3 INDICATE |
| | HOW THE CSR AND FREESTYLE FILTERING SYSTEMS WILL BE |
| | PROTECTED AGAINST CONTAMINATION. WILL BACKFLOW |
| | PREVENTERS BE INSTALLED ON THE WATER SUPPLY AND FILTER |
| | LINES? |
| | |
| | 6) P2 & P4: PROVIDE SYMBOLS TO SHOW THE LOCATIONS OF |
| | BACKFLOW PREVENTERS FOR SUPPLY LINES TO THE VARIOUS |
| | BEVERAGE DISPENSERS, ICE MAKERS, COFFEE AND CAPPUCCINO |
| | MACHINES, AND OTHER FIXTURES OR EQUIPMENT PERFORMING A |
| | SPECIAL INCLUDING THE SANITIZING EQUIPMENT AT THE MOP |
| | SINK- SECTION 608.3 FBC P. PLEASE NOTE THAT DETAIL |
| | 2/P2.0 DOES NOT SHOW BACKFLOW PREVENTERS FOR THE CSRX |
| | LINES TO THE ICE MACHINES. |
| | |
| | 7) P2, P4 & P5: PLEASE DEFINE OR EXPLAIN THE |
| | ABBREVIATIONS CSR AND CSRX TO CLARIFY THE FUNCTIONS OF |
| | THE PLUMBING LINES- SECTION 107.2.1 WPB. |
| | |
| | 8) P2 & P4: PROVIDE WATER HAMMER ARRESTOR SYMBOLS FOR |
| | SUPPLY LINES TO THE DRINKING FOUNTAINS, ICE MAKERS, |
| | BEVERAGE DISPENSERS, COFFEE MACHINES, AND OTHER |
| | FIXTURES OR EQUIPMENT WITH QUICK CLOSING VALVES- |
| | SECTION 604.9 FBC P. |
| | |
| | 9) P4: PROVIDE SYMBOLS TO SHOW THE REQUIRED TRAP |
| | PRIMERS AT FLOOR DRAINS- SECTION 1002.4.1 FBC P. PLEASE |
| | ADD THE DEVICES TO THE FIXTURE SPECIFICATIONS SCHEDULE |
| | ON P5 AND PROVIDE A DETAIL- SECTION 107.2.1 WPB. |
| | |
| | 10) P2 & P4: PROVIDE A SHUT OFF VALVE FOR THE WATER |
| | FEED UP TO THE WCH ON THE ROOF- SECTION 606.1(4) FBC P. |
| | |
| | 11) P5: PROVIDE THE EFFICIENCY RATING OF THE WATER |
| | HEATER AND ADD THE DATA TO THE ENERGY COMPLIANCE REPORT |
| | SUBMITTAL- TABLE C404.2 FBC EC. |
| | |
| | 12) P1 & P5: PLEASE INCLUDE THE WATER SOFTENER AND |
| | BRINE TANK IN THE PLUMBING FIXTURE SPEC SCHEDULE- |
| | SECTION 107.2.1 WPB. |
| | |
| | 13) P3 ROOF DRAIN PLAN- FBC P. |
| | |
| | A) PROVIDE ROOF DRAIN, ROOF SCUPPER, AND OVERFLOW |
| | SCUPPER INSTALLATION DETAILS- SECTIONS 1105.1, 1106.5, |
| | & 1108.1. |
| | |
| | B) PROVIDE A DETAIL SHOWING HOW THE MAIN BUILDING |
| | DOWNSPOUTS WILL CONNECT TO THE STORM DRAINS- 1101.6. |
| | |
| | C) SHOW THE SLOPED ROOF B AND E HORIZONTAL GUTTER RUNS |
| | AND SIZES- 1106.6. |
| | |
| | D) SHOW HOW THE ROOF B DOWNSPOUTS WILL TERMINATE AT THE |
| | ROOF SURFACES AT A1 AND A2, AND IF SOME FORM OF |
| | PROTECTION WILL BE PROVIDED TO MITIGATE EROSION OR |
| | DEGRADATION FROM THE CONCENTRATED FLOW OF WATER FROM |
| | DOWNSPOUTS- 1101.2, 1101.6, & 1101.7. |
| | |
| | E) PROVIDE A SIZING SCHEDULE FOR THE SECONDARY ROOF |
| | DRAINS- 1108.3. |
| | |
| | F) SHOW HOW THE DRAINAGE FROM ROOF E DOWNSPOUT WILL |
| | EITHER CONNECT TO THE STORM DRAIN SYSTEM OR TO AN |
| | APPROVED PLACE OF DISPOSAL- 1101.2. |
| | |
| | 14) C02 SYSTEM- SECTION 107.2.1 WPB AND SECTION 1203.1 |
| | FBC P. |
| | |
| | A) PROVIDE A C02 BOX INSTALLATION DETAIL. CLARIFY IF |
| | THE BOX CONTAINS THE C02 TANKS OR IF THE BOX IS A |
| | TRANSFER STATION FOR THE TANKS. SHOW HOW THE BOX AND |
| | TANKS WILL BE SECURED AND SUPPORTED. |
| | |
| | B) PLEASE SHOW THE C02 LINE RUNS THROUGH THE BUILDING |
| | AND HOW THE LINES WILL BE CHASED AND PROTECTED AGAINST |
| | DAMAGE OR LEAKAGE. |
| | |
| | C) PROVIDE A PRODUCT SUBMITTAL PACKAGE FOR THE SYSTEM. |
| | |
| | 15) AC1-0 & EQ2-0: PLEASE SHOW COMPLIANCE WITH SECTIONS |
| | 904.5.1 AND 308 (REACH RANGES) FBC ACC FOR ALL |
| | SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR |
| | TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES, |
| | |
| | 16) PLEASE PROVIDE A PRODUCT SUBMITTAL PACKAGE THAT |
| | INCLUDES BUT NOT IS NOT LIMITED TO THE WATER HEATER AND |
| | EXPANSION TANK, THE CSR AND FREESTYLE FILTERING SYSTEMS |
| | AND PIPING, THE WATER SOFTENER AND BRINE TANK, AND THE |
| | 3-COMPARTMENT SINK. PLEASE NOTE THAT MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION MANUALS FOR ALL |
| | PLUMBING FIXTURES, EQUIPMENT, AND DEVICES MAY BE |
| | DEFERRED SUBMITTALS OR BE ONSITE AT TIME OF INSPECTION- |
| | SECTIONS 107.2.1 AND 107.3.4.1 WPB. |
| | |
| | 17) ADVISORIES FOR SEPARATE PERMIT SUBMITTALS. |
| | |
| | A) BACKFLOW PREVENTER: PLEASE NOTE THAT A FL. LICENSED |
| | PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| | WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| | FURTHER INFORMATION. |
| | |
| | B) GREASE INTERCEPTOR: SUBMITTED PLANS SHALL INCLUDE |
| | GREASE WATER CALCULATIONS IN ACCORDANCE WITH SECTION |
| | 1003.3.4 FOR HYDROMECHANICAL INTERCEPTORS OR 1003.3.6 |
| | FOR GRAVITY TYPE INTERCEPTORS. MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION MANUALS SHALL ALSO BE |
| | SUBMITTED FOR REVIEW. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |