| 2020-11-24 08:54:25 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 20110252 |
| | REVIEWED: NOVEMBER 24, 2020 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | |
| | 1207.2 FBC[B] FLOORING SUBMITTAL. |
| | - FLOOR PLAN LAYOUT TO SHOW TYPE OF FLOORING FOR EACH |
| | AREA. |
| | |
| | 1207.2 FBC[B] FLOORING SUBMITTAL. |
| | - TYPE OF CEILING ASSEMBLE INCLUDING THICKNESS OF |
| | CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT |
| | BELOW. |
| | |
| | 1207.2 FBC[B] PLEASE ADVISE, VIA EMAIL, WHAT FLOORING |
| | AND UNDERLAYMENT ARE PROPOSED? IF THE UNDERLAYMENT |
| | PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST |
| | REPORTS ON FILE, THE FOLLOWING REPORTS WILL BE |
| | REQUIRED: |
| | 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND |
| | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E90. |
| | 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR |
| | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR |
| | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E492. |
| | 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR |
| | COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2 |
| | THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND |
| | COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL, |
| | LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING |
| | MATERIALS THAT ARE NOT COMPRISED OF FIBERS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |