| Date |
Text |
| 2020-11-05 17:15:59 | 11/05/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3 |
| | BUILDING PERMIT VALUATIONS. |
| | |
| | 2. PLEASE PROVIDE THE LOCATION OF THE BACKFLOW FOR THE |
| | CITY OF WPB UTILITIES DEPARTMENT TO APPROVE ITS |
| | LOCATION AND INSPECTOR ON FINDING IT ON THE PROPERTY. |
| | ALSO PLEASE CALL OR EMAIL THE UTILITIES FOR PRIOR |
| | APPROVAL IF THE BACKFLOW WILL BE REQUIRED TO BE IN THE |
| | BUILDING (561-822-2244 OR [email protected].) AND PROVIDE |
| | DOCUMENTATION OF THIS APPROVAL. |
| | |
| | 3. PLEASE PROVIDE THE TYPE OF BACKFLOW, IF A DIFFERENT |
| | TYPE OF DEVICE OTHER THAN RPZ IT WILL NEED TO GET PRIOR |
| | APPROVAL. THE DEGREE OF HAZARD MAY REQUIRE AN RPZ AND A |
| | DRAIN MAY BE REQUIRED IF INSIDE A BUILDING SO PLEASE |
| | SEND DETAIL WITH RE-SUBMITTALS. |
| | |
| | 4. PLEASE PROVIDE THE MANUFACTURER?S SPECIFICATIONS FOR |
| | THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF |
| | THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE |
| | WORK SECTION ON THE PERMIT APPLICATION. |
| | |
| | 5. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE |
| | WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD. |
| | |
| | 6. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND |
| | FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING |
| | OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL |
| | HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR |
| | LESS PER THE 2017 FBC SEC. P 605.2.1 LEAD CONTENT OF |
| | DRINKING WATER PIPE AND FITTINGS. |
| | |
| | 7. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS |
| | ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY |
| | OF SOUTHERN CALIFORNIA (USC). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |