Plan Review Notes
Plan Review Notes For Permit 20110244
Permit Number 20110244
Review Stop P
Sequence Number 1
Notes
Date Text
2020-11-05 17:15:5911/05/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3
 BUILDING PERMIT VALUATIONS.
  
 2. PLEASE PROVIDE THE LOCATION OF THE BACKFLOW FOR THE
 CITY OF WPB UTILITIES DEPARTMENT TO APPROVE ITS
 LOCATION AND INSPECTOR ON FINDING IT ON THE PROPERTY.
 ALSO PLEASE CALL OR EMAIL THE UTILITIES FOR PRIOR
 APPROVAL IF THE BACKFLOW WILL BE REQUIRED TO BE IN THE
 BUILDING (561-822-2244 OR [email protected].) AND PROVIDE
 DOCUMENTATION OF THIS APPROVAL.
  
 3. PLEASE PROVIDE THE TYPE OF BACKFLOW, IF A DIFFERENT
 TYPE OF DEVICE OTHER THAN RPZ IT WILL NEED TO GET PRIOR
 APPROVAL. THE DEGREE OF HAZARD MAY REQUIRE AN RPZ AND A
 DRAIN MAY BE REQUIRED IF INSIDE A BUILDING SO PLEASE
 SEND DETAIL WITH RE-SUBMITTALS.
  
 4. PLEASE PROVIDE THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE
 WORK SECTION ON THE PERMIT APPLICATION.
  
 5. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE
 WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD.
  
 6. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND
 FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING
 OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL
 HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR
 LESS PER THE 2017 FBC SEC. P 605.2.1 LEAD CONTENT OF
 DRINKING WATER PIPE AND FITTINGS.
  
 7. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved