| 2020-11-19 13:28:10 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | THE FOLLOWING TEST REPORTS ARE REQUIRED: |
| | |
| | FBC 603.1 FLAME SPREAD - ASTM E 84-09 |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1) THE TEST REPORT FOR STRUCTURE-BORNE SOUND, ASTM E |
| | 492-09, IS A BLANK PAGE. FBC1207.3 |
| | |
| | 2) THE REQUIRED FLAME SPREAD TEST REPORT FOR THE SOUND |
| | INSULATION, ASTM E 84-09, WAS NOT SUBMITTED. FBC 603.1 |
| | |
| | 3) THE TEST REPORTS WILL HAVE TO CLEARLY IDENTIFY THE |
| | PRODUCT THAT IS BEING TESTED IN ORDER TO VERIFY THAT IT |
| | IS THE PRODUCT THAT WILL BE INSTALLED. FBC 107.2.1 |
| | |
| | |