| Plan Review Notes For Permit 20110227 |
| Permit Number |
20110227 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-06-21 15:42:47 | PLEASE RESPOND TO THE MECHANICAL 1ST CYCLE REVIEW | | | COMMENTS BELOW: | | | | | | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-20110227 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE GENERATOR SPECIFICATIONS ALONG | | | WITH THE FUEL SOURCE OF THIS GENERATOR. PLEASE PROVIDE | | | DETAIL DRAWINGS OF THE TANK AND LOCATION, FUEL PIPING | | | FOR THIS SYSTEM. PLEASE ALSO PROVIDE DETAIL DRAWINGS OF | | | THE EXHAUST FOR THE GENERATOR ALONG WITH THE | | | TERMINATION LOCATION, THIS SHOULD MEET FBC M 501.3.1. | | | IS THE NEW STRUCTURE AT THE GENERATOR OPEN OR CLOSED? | | | IF CLOSED PLEASE SHOW THE VENTILATION REQUIRED. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|