Date Text
2020-11-10 07:43:411ST REVIEW FBC-2017 RES.
 PERMIT- 20110217
 11/10/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3.0 PLUMBING RISER: SHOW THE DISHWASHER DRAIN
 CONNECTION AND REQUIRED MINIMUM 1-1/2 IN. SINK TRAP-
 SECTION P2717.1 FBC P.
  
 2) A3.0: PROVIDE A WATER RISER DRAWING SHOWING THE NEW
 PIPING CONNECTIONS TO THE EXTERIOR WATER HEATER-
 SECTION 107.3.5.3 WPB.
  
 3) A3.0: CORRECT PLUMBING NOTE #21 TO INDICATE R-3 HOT
 WATER PIPE INSULATION AND UPDATE THE 2014 CODE
 REFERENCE- SECTION R403.5.3 FBC EC. INDICATE WHERE THE
 PIPE INSULATION WILL BE INSTALLED.
  
 4) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  