| 2020-12-11 15:54:38 | PLAN REVIEW / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | |
| | 1. CLEARANCE TO BUILDING OPENINGS IS 10 FEET PER |
| | R303.5.1. CORRECTED |
| | |
| | R303.5.1 INTAKE OPENINGS. |
| | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS |
| | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM |
| | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, |
| | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS |
| | AND LOADING DOCKS. |
| | |
| | 2. PROVIDE A COPY OF THE PROPOSED GENERATOR |
| | SPECIFICATIONS. (NOT ADDRESSED) |
| | |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |