| 2020-11-09 09:56:38 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20110186 |
| | ADD: 701 S. OLIVE AVE. # 1204 |
| | CONT: MARTINGALE BUILDERS INC. |
| | TEL: 561-371-0568 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV. 09/2020 |
| | ACTION: DENIED |
| | 1) PLEASE NOTE 3 OF THE 5 PAGES ARE COPY OF APPROVED |
| | PLANS WITH CITY STAMPS ON THEM WITH THE TITLE BLOCK CUT |
| | OFF. SHEET E3.24 HAS THE FULL TITLEBLOCK AND ENGINEERS |
| | NAME JIMENEZ MCDOWELL ON THE SHEET. PLEASE NOTE THERE |
| | ARE COPYRIGHT LAWS BEING VIOLATED. 61G15-23.002 |
| | ENGINEER SEAL SIGNATURE AND DATE SHALL BE AFFIXED. |
| | (1) A PROFESSIONAL ENGINEER SHALL SIGN BY HAND THE |
| | LICENSEE?S HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT |
| | ACCEPTABLE) AND AFFIX THE LICENSEE?S SEAL: |
| | (A) TO ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, |
| | REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE |
| | LICENSEE AND BEING FILED FOR PUBLIC RECORD. |
| | CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY |
| | CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED |
| | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/ |
| | MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE |
| | CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT |
| | TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE |
| | SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | 2) PAGES DO NOT HAVE NUMBERS TO IDENTIFY THEM, THE |
| | PROPOSED FLOOR PLAN SHOWS BOTH A NEW WALL AND DROPPED |
| | CEILINGS. |
| | |
| | 2A) THE PROPOSED WALL DOES NOT PROVIDE A LENGTH, DOES |
| | IT EXTEND TO THE CEILING ABOVE, WHAT TYPE OF STUDS AND |
| | SPACING OF VERTICAL FRAMING MEMBERS, TYPE OF DRYWALL, |
| | THICKNESS AND IS THERE BACKING FOR THE CABINETS. |
| | ADMINISTRATION 107.2.1. W.P.B. ADMINISTRATIVE CODE/2017 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2B) THE PROPOSED FLOOR PLAN ALSO NOTES AN AREA WHERE |
| | THE CEILINGS ARE TO BE DROPPED. THE PLAN IS SILENT AS |
| | TO WHAT HEIGHT THE CEILINGS ARE TOO DROPPED. PLEASE |
| | NOTE HABITABLE SPACES AND CORRIDORS SHALL HAVE CEILING |
| | HEIGHTS OF NOT THAN 7 FEET 6 INCHES, BATHROOMS, TOILET |
| | ROOMS, KITCHENS, STORAGE ROOMS AND LAUNDRY ROOMS SHALL |
| | NOT HAVE CEILING HEIGHT OF NOT LESS THAN 7 FEET. SEE |
| | 2017 FBC-B SECTION 1208.2 MINIMUM CEILING HEIGHTS. |
| | |
| | 2C) THE PLANS ARE SILENT AS TO THE FRAMING MEMBERS FOR |
| | THE DROPPED CEILINGS, SIZE, MATERIAL, ASSUMED METAL |
| | STUDS, GAUGE OF METAL, SPACING OF METAL, ALLOWABLE |
| | SPAN, IF MID SPAN SUPPORT IS REQUIRED, STIFF-BACKS, |
| | ANCHORS TO WALLS, ANCHORS METAL TO METAL, TYPE OF |
| | FINISH MATERIAL AND THICKNESS. ADMINISTRATION 107.2.1. |
| | W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. |
| | |
| | 3) THE PERMIT APPLICATION MENTIONS FLOOR REPAIR, PLEASE |
| | EXPOUND ON THAT COMMENT. A REPAIR IS TO REPLACE WITH |
| | LIKE MATERIAL. OR IS THE WHOLE FLOOR IN A SINGLE ROOM |
| | BE REPLACED. IF THE FLOOR IS TO BE REPLACED THEN SHOW |
| | COMPLIANCE WITH: FOR TILE, STONE, MARBLE, VINYL AND |
| | WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING |
| | COMPLIANCE WITH: |
| | TYPE I AND II BUILDINGS |
| | |
| | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| | CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| | CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| | THE 2017 FBC-B. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |