| Plan Review Notes For Permit 20110155 |
| Permit Number |
20110155 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-07-01 10:08:07 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT COMPLIED. [THE GENERATOR PAD DRAWING THAT WAS | | | SUBMITTED IS NOT SIGNED AND SEALED BY THE ENGINEER AND | | | IS ILLEGIBLE. FS 471 AND FBC AMEND. 107.2.1] SUBMIT | | | GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD ANCHORING | | | DETAILS. PRE-FABRICATED GENERATOR PADS REQUIRE PRODUCT | | | APPROVALS OR SITE SPECIFIC ENGINEERING. FBC AMENDMENTS | | | 107.2.1 | | | | | | 2) NOT COMPLIED. SUBMIT A SITE PLAN THAT SHOWS THE | | | LOCATION OF THE GENERATOR. FBC AMEND.107 | | | | | | 3) NOT COMPLIED. THE GENERATOR EXHAUST IS REQUIRED TO | | | BE 10 FEET FROM OPENINGS TO A STRUCTURE INCLUDING | | | GARAGES. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND | | | GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED | | | NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR | | | NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING | | | VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | |
|