| 2021-03-04 15:13:29 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD | | | ANCHORING DETAILS. PRE-FABRICATED GENERATOR PADS | | | REQUIRE PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING. | | | FBC AMENDMENTS 107.2.1 | | | 2) SUBMIT A SITE PLAN THAT SHOWS THE LOCATION OF THE | | | GENERATOR. FBC AMEND.107 | | | 3) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM | | | OPENINGS TO A STRUCTURE INCLUDING GARAGES. FBC-R303.5.1 | | | INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR | | | INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET | | | (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, | | | SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, | | | ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | |
|