| 2020-11-19 07:50:32 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20110141 |
| | 11/18/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REVISE THE RISER DRAWING TO SHOW THE BRANCH LINE |
| | INTO THE RESIDENCE SUPPLYING THE WATER HEATER INSTALLED |
| | UNDER PERMIT 16040206, AND ALL OTHER INTERIOR |
| | APPLIANCES- SECTIONS G2412.3 & G2412.4 FBC RES. PER THE |
| | PERMIT RECORDS, THE WATER HEATER IS A 50 GALLON, 40,000 |
| | BTUH UNIT. |
| | |
| | 2) REVISE THE TOTAL LOAD AND THE INDIVIDUAL LOADS OF |
| | THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| | RES. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | FIREPIT MARKED UP OR HIGHLIGHTED TO SHOW THE BTUH LOAD, |
| | INPUT PRESSURE, AND UL OR ANSI STANDARD LISTING NUMBER- |
| | SECTION 107.2.1 WPB. |
| | |
| | 4) ADJUST THE $1800.00 PERMIT VALUE TO INCLUDE THE COST |
| | OF THE FIREPIT- SECTION 109.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |