Plan Review Notes
Plan Review Notes For Permit 20110119
Permit Number 20110119
Review Stop E
Sequence Number 2
Notes
Date Text
2021-02-11 16:14:49CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 1) ELECTRICAL DRAWING SUBMITTED FOR GAS WATER HEATER
 NOT CLEAR:
 ? BOX LABELED ?EXISTING OUTDOOR LIGHTING?: IS THIS A
 SUBPANEL, JUNCTION BOX? PLEASE CLARIFY FBC 107
 ? BOX IS LABELED EXISTING OUTDOOR LIGHTING, BUT DIAGRAM
 MENTIONS THAT YOU ARE ADDING 2#12 CU CONDUCTORS TO FEED
 THE BOX. IS THERE AN EXISTING CIRCUIT TO THE BOX BEING
 REPLACED? FBC 107
 ? CIRCUIT FROM EXISTING CUTTLER HAMMER PANEL TO
 ?EXISTING OUTDOOR LIGHTING? BOX SHOWS 2#12 CONDUCTORS
 WITH NO EQUIPMENT GROUNDING. PLEASE SPECIFY EQUIPMENT
 GROUNDING. NEC 250
 ? WHAT IS THE SIZE OF CONDUCTORS CONNECTING TO THE
 ?EXISTING OUTDOOR LIGHTING?? WHAT IS THE EXISTING LOAD
 ON THIS CIRCUIT? WHAT WILL BE THE TOTAL LOAD ON THIS
 CIRCUIT IF IT IS ALSO FEEDING THE GAS WATER HEATER?
  
 2) ELECTRICAL DRAWING FOR GAS WATER HEATER MUST HAVE
 THE NAME AND SIGNATURE OF CONTRACTOR QUALIFIER
 PREPARING THE DRAWINGS FBC 107
 3) NEW A-3 MEP DRAWINGS SUBMITTED ARE DISTORTED AND
 DIFFICULT TO READ.
 4) ELECTRICAL SUB-PERMIT REQUIRED
 5) PLEASE SEE ALSO SIGNATURE COMMENTS FOR DRAWINGS FBC
 107
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved