| 2021-02-11 16:14:49 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | |
| | 1) ELECTRICAL DRAWING SUBMITTED FOR GAS WATER HEATER |
| | NOT CLEAR: |
| | ? BOX LABELED ?EXISTING OUTDOOR LIGHTING?: IS THIS A |
| | SUBPANEL, JUNCTION BOX? PLEASE CLARIFY FBC 107 |
| | ? BOX IS LABELED EXISTING OUTDOOR LIGHTING, BUT DIAGRAM |
| | MENTIONS THAT YOU ARE ADDING 2#12 CU CONDUCTORS TO FEED |
| | THE BOX. IS THERE AN EXISTING CIRCUIT TO THE BOX BEING |
| | REPLACED? FBC 107 |
| | ? CIRCUIT FROM EXISTING CUTTLER HAMMER PANEL TO |
| | ?EXISTING OUTDOOR LIGHTING? BOX SHOWS 2#12 CONDUCTORS |
| | WITH NO EQUIPMENT GROUNDING. PLEASE SPECIFY EQUIPMENT |
| | GROUNDING. NEC 250 |
| | ? WHAT IS THE SIZE OF CONDUCTORS CONNECTING TO THE |
| | ?EXISTING OUTDOOR LIGHTING?? WHAT IS THE EXISTING LOAD |
| | ON THIS CIRCUIT? WHAT WILL BE THE TOTAL LOAD ON THIS |
| | CIRCUIT IF IT IS ALSO FEEDING THE GAS WATER HEATER? |
| | |
| | 2) ELECTRICAL DRAWING FOR GAS WATER HEATER MUST HAVE |
| | THE NAME AND SIGNATURE OF CONTRACTOR QUALIFIER |
| | PREPARING THE DRAWINGS FBC 107 |
| | 3) NEW A-3 MEP DRAWINGS SUBMITTED ARE DISTORTED AND |
| | DIFFICULT TO READ. |
| | 4) ELECTRICAL SUB-PERMIT REQUIRED |
| | 5) PLEASE SEE ALSO SIGNATURE COMMENTS FOR DRAWINGS FBC |
| | 107 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | ENRIQUE QUINONEZ P.E. |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |