Plan Review Notes
Plan Review Notes For Permit 20110119
Permit Number 20110119
Review Stop G
Sequence Number 1
Notes
Date Text
2021-02-10 11:14:5102/10/21 1ST REVIEW PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE RESIDENCE'S PHYSICAL ADDRESS MUST BE ON PLANS IN
 FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED THE
 ISOMETRIC, ALL PIPE SIZES, AND THE CORRESPONDING EHD
 NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF
 APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC.
 G2421.1.
  
 5. PLEASE PROVIDE THE TANK-LESS WATER HEATER'S LOCATION
 AND THE DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE WATER HEATER'S
 LOCATION SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. THE OVERALL VALUE IS LOW. SUPPOSE, IN THE
 BUILDING OFFICIAL'S OPINION, THE BUILDING'S CLAIMED
 VALUATION, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION. IN THAT CASE, THE
 PERMIT SHALL BE DENIED UNLESS THE APPLICANT CAN SHOW
 DETAILED QUANTITY ESTIMATES AND BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE BUILDING
 OFFICIAL'S APPROVAL. FOR PERMITTING PURPOSES, THE
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD, AND PROFIT, EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS POSTED BY
 INTERNATIONAL CODE CONGRESS. THE BUILDING OFFICIAL'S
 FINAL BUILDING PERMIT VALUATION SHALL BE SET PER THE
 WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING PERMIT
 VALUATIONS.
  
 7. PLEASE PROVIDE THE TYPE OF GAS (LP OR NATURAL) PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER THE 2020 FBC FG SEC. 402.2 OR 2020 FBC
 RES. SEC. G2413.2.
  
 9. PLEASE LIST EACH APPLIANCE'S BTU LOAD AND THE TOTAL
 BTU LOAD ON THE SYSTEM. THE BTU LOAD OF THE EXISTING
 GAS SYSTEM MUST BE ADDED TO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS SIZED
 CORRECTLY. IF UNDERSIZED, THE EXISTING SYSTEM MUST BE
 REDONE TO ENSURE A SAFE OPERATING SYSTEM PER THE 2020
 FBC RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
 10. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND SYSTEM PER THE 2020 FBC RES.
 SEC. G2413.4.1.
  
 11. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR GAS RANGE EQUIPMENT TO
 VERIFY COMPLIANCE, AND GAS APPLIANCES SHALL BE LISTED
 AND LABELED PER THE 2020 FBC RES. SEC. G2408.1.
  
 12. PLEASE SUBMIT A COPY OF THE SIZING TABLE USED IN
 THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH
 SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES
 OR ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM
 PER THE 2020 FBC RES. SEC. G2413.3.
  
 13. PLEASE SHOW AND LABEL UNION IN FRONT OF REGULATOR
 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2.
  
 14. PLEASE SHOW AND LABEL THE SHUTOFF VALVES ON GAS
 ISOMERIC. PLEASE NOTE THAT THE STOVE'S VALVE SHALL BE
 ACCESSIBLE WITHOUT MOVING THE UNIT PER THE 2020 FBC
 RES. SEC. G2401.1.3.
  
 15. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT
 INSTALLED, EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD
 GRILLS PER THE 2020 FBC RES. SEC. G2419.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  