| Date |
Text |
| 2021-02-10 11:14:51 | 02/10/21 1ST REVIEW PLUMBING REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE RESIDENCE'S PHYSICAL ADDRESS MUST BE ON PLANS IN |
| | FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED THE |
| | ISOMETRIC, ALL PIPE SIZES, AND THE CORRESPONDING EHD |
| | NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED |
| | FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC. |
| | G2421.1. |
| | |
| | 5. PLEASE PROVIDE THE TANK-LESS WATER HEATER'S LOCATION |
| | AND THE DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE WATER HEATER'S |
| | LOCATION SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 6. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT. THE OVERALL VALUE IS LOW. SUPPOSE, IN THE |
| | BUILDING OFFICIAL'S OPINION, THE BUILDING'S CLAIMED |
| | VALUATION, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION. IN THAT CASE, THE |
| | PERMIT SHALL BE DENIED UNLESS THE APPLICANT CAN SHOW |
| | DETAILED QUANTITY ESTIMATES AND BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE BUILDING |
| | OFFICIAL'S APPROVAL. FOR PERMITTING PURPOSES, THE |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD, AND PROFIT, EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS POSTED BY |
| | INTERNATIONAL CODE CONGRESS. THE BUILDING OFFICIAL'S |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING PERMIT |
| | VALUATIONS. |
| | |
| | 7. PLEASE PROVIDE THE TYPE OF GAS (LP OR NATURAL) PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER THE 2020 FBC FG SEC. 402.2 OR 2020 FBC |
| | RES. SEC. G2413.2. |
| | |
| | 9. PLEASE LIST EACH APPLIANCE'S BTU LOAD AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. THE BTU LOAD OF THE EXISTING |
| | GAS SYSTEM MUST BE ADDED TO THE TOTAL BTU LOAD ON THE |
| | SYSTEM TO ENSURE THE EXISTING SYSTEM IS SIZED |
| | CORRECTLY. IF UNDERSIZED, THE EXISTING SYSTEM MUST BE |
| | REDONE TO ENSURE A SAFE OPERATING SYSTEM PER THE 2020 |
| | FBC RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2, |
| | G2413.3. |
| | |
| | 10. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND SYSTEM PER THE 2020 FBC RES. |
| | SEC. G2413.4.1. |
| | |
| | 11. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR GAS RANGE EQUIPMENT TO |
| | VERIFY COMPLIANCE, AND GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED PER THE 2020 FBC RES. SEC. G2408.1. |
| | |
| | 12. PLEASE SUBMIT A COPY OF THE SIZING TABLE USED IN |
| | THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH |
| | SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES |
| | OR ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM |
| | PER THE 2020 FBC RES. SEC. G2413.3. |
| | |
| | 13. PLEASE SHOW AND LABEL UNION IN FRONT OF REGULATOR |
| | 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2. |
| | |
| | 14. PLEASE SHOW AND LABEL THE SHUTOFF VALVES ON GAS |
| | ISOMERIC. PLEASE NOTE THAT THE STOVE'S VALVE SHALL BE |
| | ACCESSIBLE WITHOUT MOVING THE UNIT PER THE 2020 FBC |
| | RES. SEC. G2401.1.3. |
| | |
| | 15. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT |
| | INSTALLED, EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD |
| | GRILLS PER THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |