| 2021-04-28 10:59:05 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. SEE NEW COMMENTS BELOW |
| | |
| | 1) THIS PERMIT FALLS UNDER THE FBC 2017 7TH EDITION AND |
| | NEC 2017. ELECTRICAL DRAWINGS ARE REFERING TO THE NEC |
| | 2011. |
| | PLEASE UPDATE NOTES TO REFERENCE THE RIGHT CODES. FBC |
| | 107 |
| | |
| | 2) ELECTRICAL DRAWING SHOWS AN EMERGENCY GENERATOR AND |
| | GENERATOR SWITCH THAT ARE NOT SHOWN ON RISER DIAGRAM. |
| | PLEASE NOTE THAT THE EMERGENCY GENERATOR REQUIRES A |
| | SEPARATE SUBMISSION AND SEPARATE ELECTRICAL PERMIT. |
| | PLEASE ADD NOTE STATING THIS FACT. FBC 107 |
| | |
| | 3) PANELS A AND B ARE NOT LOCATED IN DETACHED |
| | STRUCTURES. GROUNDING SHALL BE DONE WITH GROUNDING |
| | EQUIPMENT CONDUCTORS NOT SEPARATE GROUNDING ELECTRODE |
| | SYSTEMS. |
| | PLEASE SPECIFY THE SIZE OF THE GROUNDING EQUIPMENT |
| | CONDUCTORS FOR THOSE FEEDERS. NEC 250 |
| | |
| | 4) DOES THE MDP HAVE A MAIN CIRCUIT BREAKER AND |
| | BREAKERS FOR FEEDERS TO PANELS A AND B? IF YES, PLEASE |
| | PROVIDE BREAKER SIZES. |
| | IF NOT PLEASE CLARIFY HOW FEEDERS TO PANELS A AND B ARE |
| | PROTECTED? NEC 240 |
| | |
| | 5) GROUNDING NOTES ARE UNREADABLE. PLEASE SUBMIT NEW |
| | DRAWING WITH READABLE NOTES. FBC 107 |
| | |
| | 6) WHAT IS THE ACTUAL RATING OF THE ELECTRICAL SERVICE? |
| | THE SERVICE CONDUCTORS SPECIFIED ON RISER DIAGRAM ARE |
| | FOR A 225 AMPS SERVICE AND MIGHT BE TOO SMALL DEPENDING |
| | ON THE RATINGS OF THE MDP. |
| | |
| | 7) SMOKE DETECTORS ARE REQUIRED AS PER FBC RE 2020, 7TH |
| | EDITION. PLEASE SHOW LOCATION OF ALL SMOKE DETECTORS. |
| | |
| | 8) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | ELECTRICAL SERVICE INCLUDING INFORMATION FROM THE POWER |
| | COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| | CURRENT IS. NEC 110.9, 110.10; FBC RE E3606.3 |
| | |
| | 9) GFI/WP RECEPTACLES ARE REQUIRED AT FRONT AND BACK OF |
| | HOUSE. NEC 210.8 |
| | |
| | 10) SEPARATE GFI RECEPTACLE IS REQUIRED IN WASHER/DRYER |
| | ROOM. NEC 210.8 |
| | |
| | 11) A MINIMUM OF ONE COMMUNICATIONS OUTLET SHALL BE |
| | PROVIDED AS PER NEC 800.156. PLEASE SHOW LOCATION AND |
| | ADD TO SYMBOLS. |
| | |
| | 12) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF |
| | THE LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL |
| | HAVE |
| | AN EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL |
| | UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65 |
| | LUMENS-PER-WATT?. |
| | A NOTE WILL SUFFICE. FBC EC R404.1 |
| | |
| | |
| | SINCERELY, |
| | |
| | ENRIQUE QUINONEZ PE |
| | ELECTRICAL PLANS EXAMINER |