Plan Review Notes
Plan Review Notes For Permit 20110110
Permit Number 20110110
Review Stop P
Sequence Number 1
Notes
Date Text
2020-11-16 16:53:5111/16/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING.
  
 3. A GAS RANGE IS SHOWN ON PLANS AND NOT NOTED, A
 SEPARATE GAS PERMIT WILL BE REQUIRED WITH A NARRATIVE
 OF THE SCOPE OF WORK OR PROVIDE AT THIS TIME FOR REVIEW
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THE WASHING MACHINE IS STACKABLE IN THE GUEST HOUSE
 PLEASE SHOW THE LOCATION OF THE VALVE ACCESS, THE
 WASHING MACHINE SHUT OFF VALVES SHALL BE ACCESSIBLE
 WITHOUT MOVING OF THE UNITS AND WITHIN REACH PER THE
 2017 FBC SEC. R 2903.9.3.
  
 5. THE GUEST HOUSE SHOWS A GAS WATER HEATER BUT THE
 MAIN HOUSE DOES NOT SHOW ANY WATER HEATER PLEASE
 CLARIFY IF THERE ARE TWO OR JUST ON THE UNIT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. THIS IS MULTI-FAMILY DWELLINGS AND WATER USERS WILL
 BE REQUIRED TO INSTALL A BACKFLOW PREVENTION ASSEMBLY
 AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY
 REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD
 POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS CONNECTION CONTROL MANUAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  