Plan Review Notes
Plan Review Notes For Permit 20110110
Permit Number 20110110
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-19 15:54:33CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) PLEASE PROVIDE ELECTRICAL DRAWINGS FOR MAIN HOUSE.
 INCLUDE RISER DIAGRAM, PANEL SCHEDULES, POWER AND
 LIGHTING LAYOUT, SYSTEM GROUNDING, SERVICE EQUIPMENT
 AND LOCATION, SMOKE ALARMS, LOAD CALCULATIONS,
 AVAILABLE FAULT CURRENT, NOTES AND SYMBOLS. FBC 107
 2) PLEASE PROVIDE PANEL SCHEDULE FOR GUEST HOUSE. FBC
 107
 3) PLEASE SHOW LOCATION OF DISCONNECTING MEANS FOR
 GUEST HOUSE PANEL.
 4) GUEST HOUSE MUST HAVE GFCI, WP RECEPTACLES ON BACK
 AND FRONT.
 5) FOR MAIN HOUSE PLEASE PROVIDE ARC-FAULT AND GFI
 PROTECTION AS PER FBC RE E3902.
 6) FOR MAIN HOUSE PLEASE PROVIDE TAMPER RESISTANT
 RECEPTACLE AS PER FBC RE E4002.14
 7) PLEASE SHOW WIRING METHOD UTILIZED TO FEED GUEST
 HOUSE. UNDERGROUND INSTALLATION MUST COMPLY WITH NEC
 TABLE 300.5
 8) FOR GUEST HOUSE (DETACHED STRUCTURE) PLEASE SHOW
 COMPLIANCE WITH NEC 250.32
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  