| 2020-11-10 13:43:43 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC B 107.1. THE CONSTRUCTION DOCUMENTS SHALL BE |
| | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE |
| | REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15 |
| | FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA |
| | STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. |
| | 2. FBC B 1609. PROVIDE A COMPLETE SET OF SIGNED AND |
| | SEALED DESIGN PRESSURE CALCULATIONS FOR HIGH |
| | RISE/COMMERCIAL BUILDINGS BY A FLORIDA REGISTERED |
| | DESIGN PROFESSIONAL. DESIGN PRESSURE CALCULATIONS MUST |
| | BE SPECIFIC FOR EACH OPENING. |
| | 3. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| | PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| | HEADING ?WALL PRESSURE?; PROVIDE THE ACTUAL [PSF] FROM |
| | THE REVISED DESIGN PRESSURE CALCULATIONS. PLEASE |
| | CORRECT COLUMN HEADING ?ANCHOR SPACING?; USE CORRECT |
| | DESIGN PRESSURE CALCULATIONS TO DETERMINE CORRECT |
| | SPACING. |
| | |