Date Text
2020-11-09 15:36:171ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20110078
 11/9/20200
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISE THE GAS RISER DRAWING TO SHOW THE COMPLETE
 PIPING SYSTEM INCLUDING THE PIPING FOR THE GENERATOR,
 AND THE EXISTING PIPING INSTALLED UNDER PREVIOUS GAS
 PERMITS- 05101117 & 08040179 SECTIONS G2412.3 & G2412.4
 FBC RES. PLEASE NOTE THE PLANS FOR PERMIT 05101117 SHOW
 A 340,000 BTUH SYSTEM AT 12 IN. W.C.
  
 A) SHOW THE TOTAL LOAD AND THE INDIVIDUAL LOADS OF THE
 SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES.
  
 B) SHOW THE TOTAL LENGTH DEVELOPED LENGTH OF THE PIPING
 FROM THE METER TO THE MOST REMOTE OUTLET, AND THE
 INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND
 G2413.4.2 FBC RES.
  
 C) SHOW THE LOCATIONS OF NEW AND EXISTING REGULATORS.
 INDICATE THE MAKES AND MODELS OF THE REGULATORS AND
 THEIR INLET AND OUTLET PRESSURES- SECTION G2421.1 &
 G2421.2. SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING
 THE SELECTED MODELS, THE MAX INLET AND OUTLET SIZES AND
 PRESSURES, SPRING DATA, AND ORIFICE SIZES. PLEASE NOTE
 THAT THE SPECS FOR THE GENERATOR SUBMITTED UNDER PERMIT
 20090247 SHOW A FULL LOAD CAPACITY OF 301,000 BTUH AND
 AN INPUT PRESSURE OF 7- 11 IN. W.C.
  
 D) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE THE REGULATOR- SECTION
 G2421.2(7) FBC RES.
  
 E) PROVIDE THE PIPE SIZING TABLES FOR THE 1 IN.
 GALVANIZED RISER AND THE 1 IN. PE- SEE TABLES
 G2413.4(1)- G2413.4(8) FBC RES.
  
 2) SURVEY: PLACE A NOTE TO INDICATE THE GENERATOR WILL
 BE INSTALLED WITH A MINIMUM 10 FT. CLEARANCE TO
 MECHANICAL AND GRAVITY AIR INTAKES (WINDOWS AND DOORS)
 INTO THE BUILDING- SECTION-R303.5.1 FBC RES.
  
 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS SIGNATURE ON IT- SECTION 107.2.1 WPB,
 AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  