| 2020-12-17 09:46:04 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20101496 |
| | 12/17/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P0.0.0 & P1.1.1: PROVIDE NOTES FOR REQUIRED |
| | SLAB XRAY PROCEDURE OF THE EXISTING SLAB FOR DRAIN |
| | INSTALLATIONS- SECTION 107.2.1 WPB. |
| | |
| | 2) P0.0.0: PLEASE ADD THE BACKFLOW PREVENTERS, HUB |
| | DRAIN, AND MIXING VALVE TO THE FIXTURE SCHEDULE- |
| | SECTION 107.2.1 WPB. DEFERRED SUBMITTALS: |
| | MANUFACTURER'S SPECIFICATIONS FOR ALL PLUMBING |
| | FIXTURES, EQUIPMENT INCLUDING THE DISHWASHER, ICE |
| | MAKERS, COFFEE MACHINES, AND WATER DISPENSER MAY BE |
| | SUBMITTED FOR REVIEW OR BE DEFERRED AND BE ONSITE AT |
| | TIME OF INSPECTION- SECTION 107.3.4.1 WPB. |
| | |
| | 3) P1.1.2 & P2.0.0: THE FILTRATION SYSTEMS SHALL BE |
| | PROTECTED AGAINST CONTAMINATION- SECTION 608.3 FBC P. |
| | BUSINESS LOUNGE- PROVIDE BACKFLOW PREVENTERS FOR THE |
| | SUPPLY LINES TO THE ICE MAKER AND COFFEE MACHINE. |
| | RECEPTION- PROVIDE A BACKFLOW PREVENTER FER THE SUPPLY |
| | LINE TO THE COFFEE MACHINE. |
| | |
| | 4) P1.1.2 & P2.0.0: BUSINESS LOUNGE- PROVIDE A BACKFLOW |
| | PREVENTER FOR THE SUPPLY LINE TO THE REF ICE MAKER |
| | LINE- SECTION 608.3. |
| | |
| | 5) P1.1.2 & P2.0.0: PROVIDE WATER HAMMER ARRESTORS FOR |
| | SUPPLY LINES TO THE DISHWASHER, COFFEE MACHINES AND ICE |
| | MAKER- SECTION 604.9 FBC P. |
| | |
| | 6) P1.1.2: NOTE #1 IS CALLING OUT A MIXING VALVE FOR |
| | THE KITCHEN SINK WHICH IS NOT REQUIRED. PLEASE CORRECT |
| | THE NOTE OR PROVIDE THE VALVE- SECTION 107.2.1 WPB. |
| | |
| | 7) FBC-17 ACCESSIBILITY: |
| | |
| | A) BUSINESS LOUNGE AND RECEPTION: SHOW CLEAR FLOOR |
| | APPROACH DIAGRAMS AND DIMENSIONS AT THE KITCHEN SINK, |
| | WATER DISPENSER, ICE MAKER, AND COFFEE MACHINES- |
| | SECTION 305. |
| | |
| | B) BUSINESS LOUNGE AND RECEPTION: SHOW COMPLIANCE WITH |
| | SECTIONS 904.5.1 & 308 (REACH RANGES) FOR THE KITCHEN |
| | SINK, WATER DISPENSER, ICE MAKER, AND COFFEE MACHINES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |