| 2020-11-24 12:14:41 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20101496 |
| | ADD: 360 S. ROSEMARY AVE. SUITE: 1100 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 786-320-6070 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. NOV. 24TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A4-0-5 THE RECEPTION DESK DETAIL # 2 SHOWS THE |
| | WORKING HEIGHT OF THE RECEPTION DESK FROM FINISH FLOOR |
| | TO THE TOP OF THE COUNTER HEIGHT TO BE 36 INCHES IN |
| | HEIGHT. 2017 FBC-ACCESSIBILITY CODE 902.3 HEIGHT. THE |
| | TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | ADVISORY 226.1. IN FACILITIES COVERED BY THE ADA, THIS |
| | REQUIREMENT DOES NOT APPLY TO WORK SURFACES USED ONLY |
| | BY EMPLOYEES, THERE WILL BE CLIENTS USING THIS SAME |
| | WORK SURFACE. |
| | |
| | 2) SHEET A-3-0-3 DETAIL 5 ELEV. BAR @ ADA SHOWS ANOTHER |
| | SECTION 7/ A4.0.4. THIS SECTION/ DETAIL SHOW A FLIP UP |
| | COUNTER TOP WITH LEG SUPPORT TO FINISH AT A HEIGHT OF 2 |
| | FEET 10 INCHES. THE DROPPED OR FLIP UP COUNTER DOES NOT |
| | COUNT AS AN ACCESSIBLE COUNTER TOP. THE HANDICAPPED |
| | PERSON IS TO BE ABLE TO WHEEL UP TO THE ACCESSIBLE |
| | COUNTERTOP WITHOUT ANY HELP FROM OTHERS OR WHERE THEY |
| | HAVE TO TAKE ANY ACTION TO MAKE ANY ELEMENT ACCESSIBLE. |
| | 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY |
| | WITH 902.2 AND 902.3. |
| | |
| | 2)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 2)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |