2020-11-24 12:14:41WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101496
 ADD: 360 S. ROSEMARY AVE. SUITE: 1100
 CONT: TBD/ TO BE DETERMINED
 TEL: 786-320-6070
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 24TH/2020
 ACTION: DENIED
  
 1) SHEET A4-0-5 THE RECEPTION DESK DETAIL # 2 SHOWS THE
 WORKING HEIGHT OF THE RECEPTION DESK FROM FINISH FLOOR
 TO THE TOP OF THE COUNTER HEIGHT TO BE 36 INCHES IN
 HEIGHT. 2017 FBC-ACCESSIBILITY CODE 902.3 HEIGHT. THE
 TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 ADVISORY 226.1. IN FACILITIES COVERED BY THE ADA, THIS
 REQUIREMENT DOES NOT APPLY TO WORK SURFACES USED ONLY
 BY EMPLOYEES, THERE WILL BE CLIENTS USING THIS SAME
 WORK SURFACE.
  
 2) SHEET A-3-0-3 DETAIL 5 ELEV. BAR @ ADA SHOWS ANOTHER
 SECTION 7/ A4.0.4. THIS SECTION/ DETAIL SHOW A FLIP UP
 COUNTER TOP WITH LEG SUPPORT TO FINISH AT A HEIGHT OF 2
 FEET 10 INCHES. THE DROPPED OR FLIP UP COUNTER DOES NOT
 COUNT AS AN ACCESSIBLE COUNTER TOP. THE HANDICAPPED
 PERSON IS TO BE ABLE TO WHEEL UP TO THE ACCESSIBLE
 COUNTERTOP WITHOUT ANY HELP FROM OTHERS OR WHERE THEY
 HAVE TO TAKE ANY ACTION TO MAKE ANY ELEMENT ACCESSIBLE.
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3.
  
 2)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER