| Notes |
| Date |
Text |
| 2020-11-30 15:53:31 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | | | | 1) THE SOUND TESTS THAT WERE SUBMITTED ARE FOR AN 8" | | | CONCRETE SLAB WITH A SUSPENDED DRYWALL CEILING WHICH | | | DOES NOT MATCH THE FIELD CONDITIONS. | | | | | | 2) NO TESTS WERE SUBMITTED FOR THE FLAME SPREAD AND | | | SMOKE DEVELOPED. | | | | | | FBC 603.1 FLAME SPREAD - ASTM E 84-09 | | | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | | | | | | | | | | | | | |
|