| Plan Review Notes For Permit 20101488 |
| Permit Number |
20101488 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-20 16:16:41 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | MIXING SERVICE AND FEEDER IN SAME RACEWAY(GUTTER) | | | | | | 230.7 OTHER CONDUCTORS IN RACEWAY OR CABLE CONDUCTORS | | | OTHER THAN SERVICE CONDUCTORS SHALL NOT BE INSTALLED IN | | | THE SAME SERVICE RACEWAY OR SERVICE CABLE. |
|