| Plan Review Notes For Permit 20101457 |
| Permit Number |
20101457 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-12 15:03:48 | SFR REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) OFFICE AREA IS CONSIDERED LIVING SPACE WHICH IS | | | HABITABLE SPACE - PLEASE SHOW THE CEILING HEIGHT TO | | | COMPLY WITH FBC R305.1 MINIMUM HEIGHT. | | | HABITABLE SPACE, HALLWAYS AND PORTIONS OF BASEMENTS | | | CONTAINING THESE SPACES SHALL HAVE A CEILING HEIGHT OF | | | NOT LESS THAN 7 FEET (2134 MM). EXCEPTIONS:1.FOR ROOMS | | | WITH SLOPED CEILINGS, THE REQUIRED FLOOR AREA OF THE | | | ROOM SHALL HAVE A CEILING HEIGHT OF NOT LESS THAN 5 | | | FEET (1524 MM) AND NOT LESS THAN 50 PERCENT OF THE | | | REQUIRED FLOOR AREA SHALL HAVE A CEILING HEIGHT OF NOT | | | LESS THAN 7 FEET (2134 MM). | | | 2) DRAWING A3 SHOWS SECTION CUTS A/A1 AND B/A1 - | | | DRAWING A1 DOES NOT SHOW THESE SECTIONS. (CEILING | | | HEIGHT WOULD BE BEST SHOWN ON THOSE CUT SECTIONS. | | | 3) SMOKE ALARM PLACEMENTS NEAR BATHROOM DOOR - FBC | | | R314.3 LOCATION (4).SMOKE ALARMS SHALL BE INSTALLED NOT | | | LESS THAN 3 FEET (914 MM) HORIZONTALLY FROM THE DOOR OR | | | OPENING OF A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER | | | UNLESS THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM | | | REQUIRED BY SECTION R314.3. | | | | | | |
|