2021-04-14 13:31:51WE HAVE LOOKED AT THE VENT TERMINATION AGAIN AND WHILE
 IT MEETS FBC M 501.3.2 REQUIREMENTS FOR GENERAL EXHAUST
 VENT TERMINATION WITH THE SCREEN, LOUVER OR GRILLE A
 DRYER VENT TERMINATION HAS SPECIFIC REQUIREMENTS FOR
 THE VENT TERMINATION.
 FBC M 501.3.2EXHAUST OPENING PROTECTION.
 EXHAUST OPENINGS THAT TERMINATE OUTDOORS SHALL BE
 PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS OR
 GRILLES. OPENINGS IN SCREENS, LOUVERS AND GRILLES SHALL
 BE SIZED NOT LESS THAN 1/4 INCH (6.4 MM) AND NOT LARGER
 THAN 1/2 INCH (12.7 MM). OPENINGS SHALL BE PROTECTED
 AGAINST LOCAL WEATHER CONDITIONS. LOUVERS THAT PROTECT
 EXHAUST OPENINGS IN STRUCTURES LOCATED IN
 HURRICANE-PRONE REGIONS, AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING, SHALL COMPLY WITH AMCA
 STANDARD 550. OUTDOOR OPENINGS LOCATED IN EXTERIOR
 WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR WALL
 OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 THE PRODUCT DOES MEET THIS SECTION OF THE CODE FOR
 TYPICAL EXHAUST VENT TERMINATION. THE CODE IS SAYING
 ALL EXHAUST TERMINATION OPENINGS MUST HAVE EITHER A
 SCREEN, LOUVER OR GRILLE.
 DRYER VENT TERMINATIONS HAVE THEIR OWN SET OF RULES
 SPECIFICALLY COVERED IN. FBC M 504.4 EXHAUST
 INSTALLATION.
 DRYER EXHAUST DUCTS FOR CLOTHES DRYERS SHALL TERMINATE
 ON THE OUTSIDE OF THE BUILDING AND SHALL BE EQUIPPED
 WITH A BACKDRAFT DAMPER. SCREENS SHALL NOT BE INSTALLED
 AT THE DUCT TERMINATION. DUCTS SHALL NOT BE CONNECTED
 OR INSTALLED WITH SHEET METAL SCREWS OR OTHER FASTENERS
 THAT WILL OBSTRUCT THE EXHAUST FLOW. CLOTHES DRYER
 EXHAUST DUCTS SHALL NOT BE CONNECTED TO A VENT
 CONNECTOR, VENT OR CHIMNEY. CLOTHES DRYER EXHAUST DUCTS
 SHALL NOT EXTEND INTO OR THROUGH DUCTS OR PLENUMS.
  
 BASED ON THIS CODE SECTION THE INTENT OF THE CODE IS TO
 NOT HAVE ANY RESTRICTIONS BEYOND THE BACKDRAFT DAMPER
 FOR ANY DRYER EXHAUST TERMINATION, THERE SHALL BE NO
 SCREEN, LOUVER OR GRILLE BEYOND THE BACKDRAFT DAMPER OF
 THE DRYER EXHAUST TERMINATION.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  