Plan Review Notes
Plan Review Notes For Permit 20101431
Permit Number 20101431
Review Stop B
Sequence Number 3
Notes
Date Text
2021-04-21 12:47:13PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017) & CITY OF W.P.B.
 CHAPTER 1 AMENDMENTS
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 345 BANYAN BLVD.
 PERMIT #20101431
 170 MPH, EXPOSURE "D"
 FLOOD ZONE "X"
 HIGH-RISE BLDG. PER FBC 403 (15 STORIES, 177'-8" TO TOP
 OF OCCUPIED FLOOR, 188'-0" TO HIGHEST ROOF OF OCCUPIED
 SPACE)
 CONSTRUCTION TYPE: IA (REDUCED TO IB FOR FIRE
 RESISTANCE RATING OF BUILDING MATERIALS PER FBC
 403.2.1.1)
 OCCUPANCY TYPE: (MIXED USE) R-2, S-2, S-1, M, B, A-3
 BLDG. AND GARAGE ARE FULLY SPRINKLERED
 GARAGE IS ENCLOSED
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PARTIALLY RESOLVED. [PLEASE KEEP ALL OF THE
 THRESHOLD DOCUMENTS TOGETHER AND IN THE ORDER OF THE
 THRESHOLD INSPECTION BOOKLET. THE RESUMES, LICENSES AND
 CERTIFICATES CAN BE PUT IN THE BOOKLET BEHIND THE FORM
 FOR THAT SPECIFIC ENTITY. THE SIGNED AND NOTARIZED
 THRESHOLD FORMS FROM THE OWNER, CONTRACTOR AND DELEGATE
 INSPECTOR HAVE NOT BEEN SUBMITTED. THE THRESHOLD
 ENGINEER/SPECIAL INSPECTOR FORM IS NOT COMPLETELY
 FILLED OUT. THE ENGINEER IS REQUIRED TO DIGITALLY SIGN
 ELECTRONICALLY SUBMITTED DOCUMENTS. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE ORIGINAL SIGNED AND SEALED PAPER
 DOCUMENTS TO THE BUILDING DEPARTMENT AFTER THE
 ELECTRONIC VERSION OF THEM ONES HAVE BEEN APPROVED.]
 THIS PROJECT IS A THRESHOLD BUILDING PER FL S. S.
 553.71(7) "THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DEFINED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF
 GREATER THAN 500 PERSONS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 2) TO BE RESOLVED BY MS. SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR AT 822-1515 OR E-MAIL:
 [email protected]
  
 3) RESOLVED.
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) RESOLVED.
  
 7) RESOLVED.
  
 8) PARTIALLY RESOLVED. [REVISE THE CODE DATA TABLE FOR
 FIRE SEPARATION DISTANCE ON SHEET ALS.0.1. ADD THE EAST
 WALL TO THE TABLE WITH THE FIRE SEPARATION DISTANCE TO
 REFLECT THE 23'-7" FROM THE EAST WALL TO THE ASSUMED
 PROPERTY LINE BETWEEN THE TWO BUILDINGS ON THE SAME
 LOT. THE EXEMPTION IN TABLE 602 (G) IS FOR NON-LOAD
 BEARING WALLS. THE FIRE RESISTANCE RATING OF EXTERIOR
 WALLS IS STILL REQUIRED TO COMPLY WITH FBC TABLE 601.]
  
 9) RESOLVED.
  
 10) RESOLVED.
  
 11) RESOLVED.
  
 12) RESOLVED.
  
 13) RESOLVED.
  
 14) RESOLVED. [THE BUILDING OFFICIAL AND FIRE MARSHAL
 HAVE ACCEPTED THIS CONDITION.]
  
 15) RESOLVED.
  
 16) RESOLVED.
  
 17) RESOLVED.
  
 18) RESOLVED.
  
 19) RESOLVED.
  
 20) RESOLVED.
  
 21) RESOLVED.
  
 22) RESOLVED.
  
 23) RESOLVED.
  
 24) RESOLVED.
  
 25) RESOLVED.
  
 26) RESOLVED.
  
 27) RESOLVED.
  
 28) RESOLVED.
  
 29) RESOLVED.
  
 30) RESOLVED.
  
 31) RESOLVED.
  
 32) RESOLVED.
  
 33) RESOLVED.
  
 34) RESOLVED.
  
 35) RESOLVED. THE VALUATION HAS BEEN ADJUSTED.
  
 36) RESOLVED. THE VALUATION IS FOR THE BUILDING AND
 MEPS. ITEMS THAT REQUIRE SEPARATE PERMITS AND REVIEWS
 WILL HAVE FEES BASED ON THEIR VALUATIONS FOR THE SCOPE
 OF WORK. ITEMS SUCH AS FIRE ALARM, FIRE SPRINKLER, LOW
 VOLTAGE, LANDSCAPING, IRRIGATION AND ALL ITEMS OTHER
 THAN BUILDING, MECHANICAL, ELECTRIC AND PLUMBING
 REQUIRE SEPARATE PERMITS.
  
 37) RESOLVED.
  
 38) RESOLVED.
  
 39) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 NEW COMMENTS:
  
 40) RESOLVED.
  
 41) RESOLVED.
  
 42) NEW COMMENT. THE FLORIDA ENERGY CODE PERFORMANCE
 BASED COMPLIANCE CERTIFICATE IS REQUIRED TO BE SIGNED
 AND SEALED BY THE PREPARER. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT'S OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT'S OR ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS.
 NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1, FS 471 & 61G15
  
  
 ****PROVISOS****
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A SEPARATE ROOF SUB-PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT DEFERRED ROOF PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD AND ENGINEERING.
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE
 FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS
 SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR
 PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS,
 STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS
 REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW
 AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION.
  
 COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR
 TO C.O.
  
 SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED
 TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS
 TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE
 POUR.
  
 A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED
 TO BE PROVIDED PRIOR TO INSTALLATION.
  
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  