| 2021-04-21 12:47:13 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 3RD REVIEW: FBC SIXTH EDITION (2017) & CITY OF W.P.B. |
| | CHAPTER 1 AMENDMENTS |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | 345 BANYAN BLVD. |
| | PERMIT #20101431 |
| | 170 MPH, EXPOSURE "D" |
| | FLOOD ZONE "X" |
| | HIGH-RISE BLDG. PER FBC 403 (15 STORIES, 177'-8" TO TOP |
| | OF OCCUPIED FLOOR, 188'-0" TO HIGHEST ROOF OF OCCUPIED |
| | SPACE) |
| | CONSTRUCTION TYPE: IA (REDUCED TO IB FOR FIRE |
| | RESISTANCE RATING OF BUILDING MATERIALS PER FBC |
| | 403.2.1.1) |
| | OCCUPANCY TYPE: (MIXED USE) R-2, S-2, S-1, M, B, A-3 |
| | BLDG. AND GARAGE ARE FULLY SPRINKLERED |
| | GARAGE IS ENCLOSED |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PARTIALLY RESOLVED. [PLEASE KEEP ALL OF THE |
| | THRESHOLD DOCUMENTS TOGETHER AND IN THE ORDER OF THE |
| | THRESHOLD INSPECTION BOOKLET. THE RESUMES, LICENSES AND |
| | CERTIFICATES CAN BE PUT IN THE BOOKLET BEHIND THE FORM |
| | FOR THAT SPECIFIC ENTITY. THE SIGNED AND NOTARIZED |
| | THRESHOLD FORMS FROM THE OWNER, CONTRACTOR AND DELEGATE |
| | INSPECTOR HAVE NOT BEEN SUBMITTED. THE THRESHOLD |
| | ENGINEER/SPECIAL INSPECTOR FORM IS NOT COMPLETELY |
| | FILLED OUT. THE ENGINEER IS REQUIRED TO DIGITALLY SIGN |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. YOU ALSO HAVE THE |
| | OPTION TO SUBMIT THE ORIGINAL SIGNED AND SEALED PAPER |
| | DOCUMENTS TO THE BUILDING DEPARTMENT AFTER THE |
| | ELECTRONIC VERSION OF THEM ONES HAVE BEEN APPROVED.] |
| | THIS PROJECT IS A THRESHOLD BUILDING PER FL S. S. |
| | 553.71(7) "THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DEFINED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF |
| | GREATER THAN 500 PERSONS. |
| | |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | 2) TO BE RESOLVED BY MS. SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR AT 822-1515 OR E-MAIL: |
| | [email protected] |
| | |
| | 3) RESOLVED. |
| | |
| | 4) RESOLVED. |
| | |
| | 5) RESOLVED. |
| | |
| | 6) RESOLVED. |
| | |
| | 7) RESOLVED. |
| | |
| | 8) PARTIALLY RESOLVED. [REVISE THE CODE DATA TABLE FOR |
| | FIRE SEPARATION DISTANCE ON SHEET ALS.0.1. ADD THE EAST |
| | WALL TO THE TABLE WITH THE FIRE SEPARATION DISTANCE TO |
| | REFLECT THE 23'-7" FROM THE EAST WALL TO THE ASSUMED |
| | PROPERTY LINE BETWEEN THE TWO BUILDINGS ON THE SAME |
| | LOT. THE EXEMPTION IN TABLE 602 (G) IS FOR NON-LOAD |
| | BEARING WALLS. THE FIRE RESISTANCE RATING OF EXTERIOR |
| | WALLS IS STILL REQUIRED TO COMPLY WITH FBC TABLE 601.] |
| | |
| | 9) RESOLVED. |
| | |
| | 10) RESOLVED. |
| | |
| | 11) RESOLVED. |
| | |
| | 12) RESOLVED. |
| | |
| | 13) RESOLVED. |
| | |
| | 14) RESOLVED. [THE BUILDING OFFICIAL AND FIRE MARSHAL |
| | HAVE ACCEPTED THIS CONDITION.] |
| | |
| | 15) RESOLVED. |
| | |
| | 16) RESOLVED. |
| | |
| | 17) RESOLVED. |
| | |
| | 18) RESOLVED. |
| | |
| | 19) RESOLVED. |
| | |
| | 20) RESOLVED. |
| | |
| | 21) RESOLVED. |
| | |
| | 22) RESOLVED. |
| | |
| | 23) RESOLVED. |
| | |
| | 24) RESOLVED. |
| | |
| | 25) RESOLVED. |
| | |
| | 26) RESOLVED. |
| | |
| | 27) RESOLVED. |
| | |
| | 28) RESOLVED. |
| | |
| | 29) RESOLVED. |
| | |
| | 30) RESOLVED. |
| | |
| | 31) RESOLVED. |
| | |
| | 32) RESOLVED. |
| | |
| | 33) RESOLVED. |
| | |
| | 34) RESOLVED. |
| | |
| | 35) RESOLVED. THE VALUATION HAS BEEN ADJUSTED. |
| | |
| | 36) RESOLVED. THE VALUATION IS FOR THE BUILDING AND |
| | MEPS. ITEMS THAT REQUIRE SEPARATE PERMITS AND REVIEWS |
| | WILL HAVE FEES BASED ON THEIR VALUATIONS FOR THE SCOPE |
| | OF WORK. ITEMS SUCH AS FIRE ALARM, FIRE SPRINKLER, LOW |
| | VOLTAGE, LANDSCAPING, IRRIGATION AND ALL ITEMS OTHER |
| | THAN BUILDING, MECHANICAL, ELECTRIC AND PLUMBING |
| | REQUIRE SEPARATE PERMITS. |
| | |
| | 37) RESOLVED. |
| | |
| | 38) RESOLVED. |
| | |
| | 39) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | NEW COMMENTS: |
| | |
| | 40) RESOLVED. |
| | |
| | 41) RESOLVED. |
| | |
| | 42) NEW COMMENT. THE FLORIDA ENERGY CODE PERFORMANCE |
| | BASED COMPLIANCE CERTIFICATE IS REQUIRED TO BE SIGNED |
| | AND SEALED BY THE PREPARER. ELECTRONICALLY SUBMITTED |
| | DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT'S OR |
| | ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE |
| | OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF |
| | DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN |
| | APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER |
| | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE |
| | ARCHITECT'S OR ENGINEER'S ORIGINAL HANDWRITTEN |
| | SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. |
| | NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE |
| | ACCEPTABLE. FS 481 & 61G1, FS 471 & 61G15 |
| | |
| | |
| | ****PROVISOS**** |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | A SEPARATE ROOF SUB-PERMIT IS REQUIRED. PRIOR TO |
| | INSTALLATION, SUBMIT DEFERRED ROOF PRODUCT APPROVALS |
| | REVIEWED BY DESIGNER OF RECORD AND ENGINEERING. |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | |
| | DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE |
| | FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS |
| | SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR |
| | PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS, |
| | STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS |
| | REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW |
| | AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION. |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH |
| | PRESSURES SHOWN ON SHEET S0.0.5) |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5 |
| | PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, |
| | INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS |
| | COMPLY WITH MINIMUM DESIGN PRESSURES. |
| | |
| | SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | PARKING LOT |
| | SWIMMING POOLS |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR |
| | TO C.O. |
| | |
| | SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED |
| | TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS |
| | TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE |
| | POUR. |
| | |
| | A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED |
| | TO BE PROVIDED PRIOR TO INSTALLATION. |
| | |
| | CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |