| 2021-03-12 13:40:02 | 03/12/21 2ND REVIEW PLUMBING REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | PLEASE NOTE THAT WE CAN DO A ZOOM MEETING FOR THIS |
| | REVIEW TO CLARIFY THE IN-QUESTION COMMENT IF NEEDED. |
| | YOU MAY CONTACT ME VIA PHONE OR EMAIL TO SET THIS |
| | MEETING UP AT YOUR CONVENIENCE. |
| | |
| | 1. THE RESPONSE TO COMMENT NOT FOUND OR NEW DRAWING; |
| | PLEASE PROVIDE PAGE AND OR DETAIL REFERENCE; SHEET 5 OF |
| | 16 REFERS TO 45,800 CUBIC FOOT TANK STORAGE CHAMBERS. |
| | SUBMIT A DETAIL OF THIS STORAGE ARRANGEMENT, IT'S |
| | PURPOSE AND ANY/ ALL ASSOCIATED PIPING, PUMPS AND/OR |
| | ANY OTHER DETAILS ASSOCIATED WITH THIS SYSTEM. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 2. SHEETS, ALS 0.2, ALS 0.3, ALS 0.4, ALS 0.5, THE |
| | REFERENCE NOTES HAVE FAIR HOUSING ACT DESIGN MANUAL |
| | (1998), WHICH IS FINE BUT ALSO NEEDS TO HAVE THE |
| | REFERENCES TO THE ANSI A117.1 1986, AND THIS IS THE ONE |
| | THAT SHOULD BE USED IN COMMON AREAS. THE ANSI 2009 WAS |
| | USED IN SOME COMMENT IN THE LAST REVIEW WHICH DOES NOT |
| | APPLY AND SHOULD BE NOTED THE SAFE HARBORS IN USE. |
| | PLEASE MAKE CHANGES PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | A. ON SHEET ALS 0.1, PLEASE PLACE A NOTE THAT THE BUILT |
| | OUT AREA SHALL BE BUILT TO THE CURRENT FLORIDA BUILDING |
| | CODE ACCESSIBILITY. |
| | |
| | B. A. ON ALL NOTE ON THESE PAGES, A NOTE THAT STATES |
| | FHA DESIGN MANUAL (1998 ED.) IS FINE, BUT THE PART OF |
| | ADA FBC 2017 WILL NEED TO BE REMOVED. ANY CODE |
| | REFERENCE NOTES TO THE ACCESSIBILITY CODE FBC NEED TO |
| | BE REMOVED AS WELL. |
| | |
| | C. ON ALS 0.02, PLEASE PROVIDE THE DISTANCE FROM THE |
| | WALL ON THE TOILET WHERE IT GIVES THE REAR GRAB OF THE |
| | BAR OF 1'- 6" ABSOLUTE AND REMOVES THE 16? FROM THE |
| | COMPARTMENT DRAWING PER THE ANSI 117.1 1886 4.16.2. THE |
| | GRAB BARS FOR THE SUPPORT NEED TO COMPLY WITH THE ANSI |
| | 117 4.24.3, AND THE BACKING ON THE DETAIL MAY NOT BE |
| | ENOUGH FOR THE ALLOWABLE STRESS OF 250 LBS. PLEASE |
| | ADDRESS THE APPLICATION OR INCREASE THE SIZE OF THE |
| | BACKING; PROVIDE DETAIL IF POSSIBLE. THE HEIGHT OF GRAB |
| | BARS FOR THE TOILET IS NOT CONSISTENT, AND THEY NEED TO |
| | MEASURE TO THE CENTER OF THE BAR PER THE ANSI 4.17.6. |
| | THE GRAB BAR IN A VERTICAL POSITION IS NOT IN ANY OF |
| | THE STANDARDS REFERENCES, AND THERE ARE NO EXCEPTIONS. |
| | PLEASE REMOVE ALL DRAWINGS PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | D. ON SHEET ALS.0.4, NO ACTION WAS TAKEN ON THIS |
| | COMMENT. THERE ARE FHA DETAILS WITH ADA, ACCESSIBLY / |
| | ICC ANSI A117.1-2009 NOTES; PLEASE CORRECT THEM. PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | E. PLEASE PROVIDE THE MAXIMUM HEIGHT AND CLEARANCE FOR |
| | URINAL PARTITIONS PER THE 2017 FBC P 405.3.5 URINAL |
| | PARTITIONS. |
| | |
| | 3. HUD RECOGNIZES TEN SAFE HARBORS FOR COMPLIANCE WITH |
| | THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION |
| | REQUIREMENTS. THE ICC/ANSI A117.1 - 2009 IS NOT LISTED |
| | AS A SAFE HARBOR. HUD SAID IN THE INTRODUCTION TO THE |
| | ACCESSIBILITY GUIDELINES, "BUILDERS AND DEVELOPERS MAY |
| | CHOOSE TO DEPART FROM THESE GUIDELINES AND SEEK |
| | ALTERNATE WAYS TO DEMONSTRATE THAT THEY HAVE MET THE |
| | REQUIREMENTS OF THE FAIR HOUSING ACT." THE STANDARD |
| | EMPLOYED MUST MEET ALL OF THE DESIGN AND CONSTRUCTION |
| | REQUIREMENTS SPECIFIED IN THE FAIR HOUSING ACT AND |
| | HUD'S FAIR HOUSING ACT REGULATIONS, AND PROVIDE THE |
| | SAME OR A STRICTER DEGREE OF ACCESSIBILITY THAN THE |
| | RECOGNIZED SAFE HARBORS. FAIR HOUSING ACT DESIGN |
| | MANUAL, PAGE 13. PREAMBLE TO THE GUIDELINES, 56 FR |
| | 9478-79, MARCH 6, 1991. THE PURPOSE OF THE FAIR HOUSING |
| | ACT GUIDELINES IS "TO DESCRIBE THE MINIMUM STANDARDS OF |
| | COMPLIANCE WITH THE SPECIFIC ACCESSIBILITY REQUIREMENTS |
| | OF THE ACT." PREAMBLE TO THE GUIDELINES, 56 FR 9472, |
| | 9476, MARCH 6, 1991. VERIFICATION MUST BE PROVIDED THAT |
| | THE 2009 EDITION OF THE ANSI A117.1 PROVIDES THE SAME |
| | OR A STRICTER DEGREE OF ACCESSIBILITY THE RECOGNIZED |
| | SAFE HARBORS. |
| | |
| | 4. DONE. |
| | |
| | 5. PLEASE ADDRESS COMMENT TWO AND REMOVE ADA FBC 2017 |
| | DETAIL ON TITLE BLOCK PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. PLEASE REFER TO COMMENT TWO FOR CORRECTIONS; SHEET. |
| | ALS 0.2 - DRINKING FOUNTAIN DETAILS - THE DETAIL TITLE |
| | REFERS TO THE ANSI 2009 EDITION BUT NOTE #1 REFERS TO |
| | THE FLORIDA BUILDING CODE. THE COMMON AREAS SHALL |
| | COMPLY WITH THE APPLICABLE STANDARD USED FOR FAIR |
| | HOUSING DESIGN COMPLIANCE. THE FLORIDA BUILDING CODE |
| | DOES NOT APPLY TO THE COMMON AREAS OF THE BUILDING. THE |
| | FLORIDA BUILDING CODE WOULD APPLY TO ANY RETAIL OR |
| | TENANT SPACES THAT DO NOT FALL UNDER FAIR HOUSING |
| | REQUIREMENTS. THE SAME APPLIES TO THE URINAL DETAIL. |
| | REVISE THE NOTES. |
| | |
| | 7. DONE. |
| | |
| | 8. DONE. |
| | |
| | 9. DONE. |
| | |
| | 10. THERE IS NO INFORMATION ON THIS PAGE THAT SEEMS TO |
| | HAVE TWO-THIRD OF THE DETAILS DELETE. IF THIS IS IN |
| | ERROR, PLEASE CLARIFY. PLEASE REFER TO COMMENT TWO AND, |
| | IF NEEDED, PUT BACK INFORMATION THAT WILL BE REQUIRED |
| | FOR THESE PLANS; SHT. ALS 0.3 - ACCESSIBLE WATER |
| | CLOSETS DETAIL - SECTION 1003.11.2.4.4 OF THE NOTED |
| | ANSI STANDARD REQUIRES THE CLEARANCE AT THE WATER |
| | CLOSET TO BE 66 INCHES MINIMUM MEASURED PERPENDICULAR |
| | FROM THE REAR WALL WHEN A LAVATORY IS LOCATED NEXT TO |
| | THE WATER CLOSET FOR TYPE "A" ACCESSIBLE WATER CLOSETS. |
| | THE DEPTH OF THE LAVATORY SHALL BE A MAXIMUM OF 24 |
| | INCHES. |
| | |
| | 11. SOME GRAB BARS ARE 36" TO THE TOP AND OTHERS 36" TO |
| | THE MIDDLE. ARE THESE FHA OR ACC REFERENCES? SEE |
| | COMMENT TWO? PLEASE CLARIFY PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 12. THIS COMMENT IS NOT CLEAR ABOUT WHAT WAS CORRECTED |
| | TO ITS REFERENCE OF THE DETAILS; SHOW THE CLEAR FLOOR |
| | SPACE DIMENSIONS FOR THE WATER CLOSETS ON ALL THE WATER |
| | CLOSET DETAILS ON THE FHA DRAWINGS. COMPLY WITH THE |
| | REQUIREMENTS FROM THE DESIGN STANDARD BEING USED.WPB |
| | AMEND. TO FBC |
| | SEC. 107.2.1. |
| | |
| | 13. ITEM REMOVE. |
| | |
| | 14. DONE. |
| | |
| | 15. DONE. |
| | |
| | 16. DONE. |
| | |
| | 17. COULD NOT LOCATE THE PAGE REFERENCE GIVEN ALS 6.1. |
| | NO SUCH PAGE NUMBER. PLEASE CLARIFY. |
| | |
| | 18. COULD NOT LOCATE THE PAGE REFERENCE GIVEN ALS 6.1. |
| | NO SUCH PAGE NUMBER. PLEASE CLARIFY. |
| | |
| | 19. DONE. |
| | |
| | 20. DONE. |
| | |
| | 21. DONE. |
| | |
| | 22. DONE. |
| | |
| | 23. DONE. |
| | |
| | 24. THE RESPONSE TO THE COMMENT IS NOT CORRECT; PLEASE |
| | REFER TO THE DESIGN MANUAL PAGE 7.43 AND FIGURE 7.44; |
| | THE MAXIMUM DEPTH OF THE LAVATORIES SHALL BE 24 INCHES. |
| | THE PLANS SHOW SOME OF THE LAVATORIES AS 25 1/2 INCHES |
| | DEEP. INDICATE ON THE UNIT FLOOR PLANS THAT THE |
| | LAVATORIES' MAXIMUM DEPTH IS 24 INCHES PER ANSI A117.1. |
| | |
| | 25. DONE. |
| | |
| | 26 SECOND REQUEST; SHEET A9.17.1 - UNIT 17 - SHOWS THE |
| | WATER CLOSET IN THE MASTER BATH LOCATED 2 FEET 5 INCHES |
| | ( 2'- 5" ) FROM THE ADJACENT WALL TO THE WATER CLOSET'S |
| | CENTERLINE. THE WATER CLOSET SHALL BE 18 INCHES FROM |
| | SIDE TO ITS CENTERLINE PER THE FHAGL PAGE 6.5. |
| | |
| | 27. SHEET A9.20.1 - UNIT 20 ? IS MISSING THE TYPE FOR |
| | FHA; IS IT AN A OR A B UNIT?? PLEASE PROVIDE PER WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 28. DONE. |
| | |
| | 29. DONE. |
| | |
| | 30. DONE. |
| | |
| | 31. DONE. |
| | |
| | 32. DONE. |
| | |
| | A. DONE. |
| | |
| | 33. DONE. |
| | |
| | 34. DONE. |
| | |
| | 35. PLEASE HAVE ENGINEER ADDRESS SHEET P 1.0.1. THE |
| | GRID NUMBERS AND LETTERS ARE ON TOP OF EACH OTHER IN |
| | SOME PLACES, AND PLEASE OFFSET OR MOVE AWAY FOR CLARITY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. THIS IS TYPICAL |
| | ON ALL PLUMBING PAGES, SO NOT TO REPEAT EVERY COMMENT; |
| | IT IS NOTED IN THIS ONE ONLY. |
| | |
| | A. DONE. |
| | |
| | 36. PLUMBING RISERS WILL BE MOVED TO THE INSIDE FACE OF |
| | THE COLUMN DURING THE SHOP DRAWING COORDINATION TO |
| | ALLOW THE CONCRETE COLUMN TO PROVIDE PROTECTION. PLEASE |
| | PLACE A NOTE ON THE PLANS ON THIS COMMENT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | IN ANSWER TO THE RESPONSE, PLEASE NOTE THE REFERENCE |
| | PAGES; PLUMBING RISERS WILL BE MOVED TO THE INSIDE FACE |
| | OF THE COLUMN DURING THE SHOP DRAWING COORDINATION TO |
| | ALLOW THE CONCRETE COLUMN TO PROVIDE PROTECTION. |
| | |
| | A. GRIDLINE LETTERS ARE NOT SHOWN. PLEASE MOVE THE |
| | DRAWING OVER PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. DONE. |
| | |
| | C. SECOND REQUEST; THE STORAGE ROOM WITH THE LAUNDRY |
| | TRAY IS NOT LABELED NEXT TO THE ELEVATORS; PLEASE LABEL |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. DONE. |
| | |
| | 37. DONE. |
| | |
| | A. DONE. |
| | |
| | 38. DONE. |
| | |
| | 39. DONE. |
| | |
| | 40 DONE. |
| | |
| | 41. SECOND REQUEST; SHEET P 1.5.B, IN THE POOL AREA, SO |
| | MANY MISSING CIRCLES AND LINES INDICATE THAT A PIPE IS |
| | GOING UP OR DOWN IN THE POOL AREA. PLEASE OVERLAY AND |
| | MATCH TO P 1.6.B; THERE ARE TOO MANY TO MENTION ON THIS |
| | PAGE I. E. PD, TD PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 42. DONE. |
| | |
| | A. DONE |
| | |
| | B. DONE. |
| | |
| | 43. DONE. |
| | |
| | A. SECOND REQUEST, THERE IS ON V.2 FOR P0.2.1, PLEASE |
| | PROVIDE DETAILS FOR PLANT DRAINS AND PUT A REFERENCE ON |
| | KEYNOTE LEGEND PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. DONE. |
| | |
| | C. DONE. |
| | |
| | D. DONE. |
| | |
| | E. DONE. |
| | |
| | 44. SECOND REQUEST; SHEET P 1.7.1A, THE GRID LINES ON |
| | THE LEFT BOTTOM ARE OFF THE PLOTTED DRAWING AND OTHER |
| | OVERLAPPED (AS MENTION BEFORE, PLEASE CORRECT ALL |
| | OVERLAPS IN ALL PAGES); PLEASE MOVE OVER PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 45. DONE. |
| | |
| | A. SECOND REQUEST, PLEASE GIVE THE LOCATION. THERE IS |
| | NO LAYOUT SHOWING THE RD-1 AND HB-3; PLEASE PROVIDE A |
| | REFERENCE IF ON ANOTHER PAGE OR GENERATE ONE PLEASE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 46. SECOND REQUEST, THERE IS NO V.2 AVAILABLE; SHEET P |
| | 1.8.1B, THERE IS AN AREA WHERE THE TRENCH DRAINS ARE, |
| | AND THEY ARE NOT LABELED. PLEASE LABEL PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | A. SECOND REQUEST, THERE IS NO V.2 AVAILABLE; SHEET; |
| | THERE IS NO LAYOUT SHOWING THE RD-1 AND TD-1; PLEASE |
| | PROVIDE ON PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 47. SECOND REQUEST; SHEET P 9.0.1, DETAIL 2 FOR THE |
| | FITNESS CENTER IT HAS A 6" PIPE COMING UP, NOT SIZED |
| | AND NOT LABELED OR WITH A REFERENCE POINT, ALSO SIZE |
| | THE HORIZONTAL 4" LINE GOING TO THE MEN'S ROOM, AND THE |
| | LADIES ROOM DOWNSTREAM HAS A FEW 3" AND 4" NOT SIZED AS |
| | WELL. PLEASE PROVIDE SIZES PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | A. SECOND REQUEST; ON THAT SAME DETAIL, THERE IS A 4" |
| | SANITARY LINE WITH NO LABEL AS TO WHERE IT IS GOING. |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. SECOND REQUEST; PLEASE SHOW ALL TRAP PRIMERS ON THE |
| | FLOOR DRAINS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. SECOND REQUEST; LAVATORIES ON ALL AP-3 NEED TO BE |
| | SHOWN HORIZONTALLY AS THEY SEEM TO BE IN AN S-TRAP |
| | POSITION. PLEASE CHANGE PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. SECOND REQUEST; THERE ARE THREE 3" SANITARY PIPES |
| | GOING UP WITH NO DESTINATION VENT. PLEASE LABEL PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | E. SECOND REQUEST; THERE ARE TWO FLOATING FITTING AND A |
| | PIPE WITH A 90-DEGREE ELBOW GOING DOWN AND A WYE AT THE |
| | END; IT DOESN'T HAVE A SIZE OR DESTINATION; PLEASE |
| | REMOVE AND OR GIVE A REFERENCE TO ITS USE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | F. SECOND REQUEST; ON DETAIL FOUR, PLEASE SHOW SHUTOFF |
| | VALVES FOR THE RECIRCULATING PUMP AT THE FITNESS ROOM |
| | AREA WITH AN ACCESS BOX ON BOTH SIDES OF THE |
| | RECIRCULATING PUMP FOR THE WATER HEATER AND ALL |
| | FIXTURES PER THE 2017 FBC SEC. P 606.1. |
| | |
| | G. SECOND REQUEST; PLEASE SHOW AND LABEL ON ISOMETRIC |
| | THE HAMMER ARRESTOR FOR THE DRINKING FOUNTAIN AND ALL |
| | QUICK CLOSING VALVES PER THE 2017 FBC SEC. P 604.9. |
| | |
| | H. SECOND REQUEST; PLEASE SHOW AND LABEL CHECK VALVES |
| | ON THE RECIRCULATING SYSTEM PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | I. SECOND REQUEST; THE RECIRCULATING MANIFOLD TO THE |
| | HOT WATER LINES MAY NEED TO BE CLOSER TO THE OUTLET |
| | SOURCE; PLEASE REFER TO THE 2017 FBC ENERGY CODE TABLE |
| | C404.5.1. |
| | |
| | J. DONE. |
| | |
| | K. SECOND REQUEST; ON DETAIL ONE, AP-9 IS LABELED AS A |
| | FLOOR DRAIN; PLEASE MARK AS MOP SINK AND HAVE A NOTE |
| | THAT SURROUNDING THE WALL SHALL BE NON-ABSORBENT |
| | SURFACE IN ACCORDANCE WITH THE 2017 FBC BUILDING SEC. |
| | 1210.2.2. |
| | |
| | L. SECOND REQUEST; IN THAT SAME DETAIL, THE MOP SINK |
| | AND DRINKING FOUNTAIN CANNOT DISCHARGE INTO A |
| | HORIZONTAL WET VENT PER THE 2017 FBC SEC. P 912.1. |
| | |
| | M. SECOND REQUEST; IN THAT SAME DETAIL, THE WATER |
| | CLOSET IS ON A SANITARY TEE ON ITS BACK; A WATER CLOSET |
| | BEND IS REQUIRED PER THE 2017 FBC SEC. P 420.4. |
| | |
| | 48. DONE. |
| | |
| | A. DONE. |
| | |
| | B. DONE. |
| | |
| | C. SECOND REQUEST; NOT ALL COMMENTS WERE ADDRESSED. ON |
| | DETAIL 6/P 9.0.2, THE ARMS FOR THE STACK BY THE |
| | TWO-FLOOR DRAINS HAVE THE ARMS IN AN S-TRAP. PLEASE |
| | SHOW IN A HORIZONTAL POSITION. THE FLOOR DRAIN NEXT TO |
| | AP-10 IS MISSING A TRAP PRIMER #. THE LAVATORY IN THE |
| | DOG SPA IS NOT SHOWN ON THE ISOMETRIC. PLEASE |
| | INCORPORATE IT IN THE SYSTEM OF THIS ISOMETRIC PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. DONE. |
| | |
| | E. DONE. |
| | |
| | F. DONE. |
| | |
| | G. DONE. |
| | |
| | 49. SECOND REQUEST; SHEET P 9.0.3, IN DETAIL 1/P 9.0.3 |
| | AND 2/P 9.0.3, IN THE JANITOR'S ROOM, THE MOP SINK IS |
| | LABELED AS FD-2, PLEASE CORRECT, PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | A. DONE. |
| | |
| | B. DONE. |
| | |
| | PLEASE ADD A NOTE THAT A SEPARATE PERMIT IS REQUIRED |
| | FOR THE GREASE INTERCEPTOR. |
| | |
| | C. SECOND REQUEST HERE IS NO NOTE ON TEMPERED WATER |
| | SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO |
| | (ASSE 1070 OR CSA B125.3) PER THE 2017 FBC SEC. 416.5 |
| | TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | |
| | D. DONE. |
| | |
| | E. DONE. |
| | |
| | 50. DONE. |
| | |
| | A. DONE. |
| | |
| | B. DONE. |
| | |
| | C. DONE. |
| | |
| | D. DONE. |
| | |
| | E. DONE. |
| | |
| | F. SECOND REQUEST; ON DETAIL 9/P 9.0.4, PLEASE SHOW |
| | SHUT-OFF VALVES TO THE MOP SINK, SIZE, AND LABEL THEM |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | G. DONE. |
| | |
| | 51. SECOND REQUEST; SHEET P 9.0.5, THE DRAWING HAS |
| | MISSING DECK DRAINS AND EXTRA ROOF DRAINS, RISERS ARE |
| | CONNECTING TO DRAINS THAT ARE MISSING FITTINGS, TOO |
| | MANY TO CALL OUT PLEASE GO BACK AND REFER TO THE FLAT |
| | DRAWING AND MAKE CORRECTIONS FOR CLARITY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 52. SECOND REQUEST; SHEET P 9.0.6, PLEASE SIZE BOTH, |
| | PLEASE SHOW CLEAN CLEAN-OUTS ON VERTICALS, AND LABEL |
| | THE VENTS. THERE IS A 6" 121 GPM PIPE GOING WITH NO DD |
| | R? UP. WHERE IS THE NEW 3" CD COMING FROM AND PIPES |
| | GOING NOT SIZED, AND ARE THEY VENTS? PLEASE CLARIFY PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 53. SHEET P 9.0.7, THE DP-8 AND DP-9 SIZES ARE NOT |
| | LABELED, CD-1 AND CD-2 SIZES ARE NOT LABELED, AND THE |
| | THREE 1" CONDENSATE TIED TOGETHER IS GOING DOWN THAT IS |
| | MISSING WHERE IT'S GOING TO AND SIZE, CONDENSATE NUMBER |
| | DOES NOT CONNECT AT 90 GOING DOWN. PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 54. DONE. |
| | |
| | A. DONE. |
| | |
| | B. DONE. |
| | |
| | C. DONE. |
| | |
| | 55. SHEET P 9.0.9, PLEASE PROVIDE CLEAN-OUT ON THESE |
| | STORM RISERS PER 2017 FBC SEC. 1101.8 CLEANOUTS |
| | REQUIRED. |
| | |
| | 56. SHEET P 9.0.12, NEW COMMENT THERE IS A 12" 45 |
| | MISSINGS ON THE DRAIN AND DIRECTIONAL FITTING UPSTREAM |
| | OF THAT IS NOT DIRECTIONAL ALSO THE ONE ON BATHROOM |
| | GROUP IS WRONG, PLEASE CORRECT. S/R-9 IS NOT CONNECTED |
| | TO THE TRUNK LINE, AND THE TRAP FOR THE LAST FLOOR |
| | DRAIN WITH A VENT IS DRAWN WRONG. THE 4" FUTURE PIPE |
| | NUMBER S/R-9 DOES NOT HAVE A DIRECTIONAL FITTING. S/R-3 |
| | PIPE SIZE IS WRONG, AND ALSO UPSTREAM LOOKS OVERSIZED. |
| | PLEASE FIX ALL SANTEE ON ITS SIDE AND USE WYE FITTINGS |
| | AND CORRECT ALL DIRECTIONAL FITTINGS. ALL DRAINS FROM |
| | ELEVATORS REQUIRE A TRAP AND A TRAP PRIMER, AND THE |
| | PUMP TWO ELEVATOR TRAP HAS NOWHERE TO CONNECT BY |
| | S/R-11. PIPES ARE FLOATING; PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | A. DONE. |
| | |
| | B. STILL NOT ADDRESSED. PLEASE SHOW THE STACK BY THE |
| | TWO-FLOOR DRAINS WITH THE ARMS IN AN S-TRAP. PLEASE |
| | SHOW IN A HORIZONTAL POSITION PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | C. DONE. |
| | |
| | D. THE THREE FD-1 NEXT TO STACK S/R-9 NOT DRAWN |
| | CORRECTLY, PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 57. DONE. |
| | |
| | A. DONE. |
| | |
| | B. DONE. |
| | |
| | C. DONE. |
| | |
| | 58. DONE. |
| | |
| | A. NEW COMMENT; IN DETAIL ELEVEN, THE RIGHT BOTTOM |
| | CORNER 1/P 0.3.0 HAS A PIPE WITH TWO NINETY DOWN AND NO |
| | REFERENCE; PLEASE LABEL OR DELETE IF NOT NEEDED PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. DONE. |
| | |
| | C. NEW COMMENT; IN DETAIL EIGHT, THE LEFT TOP CORNER |
| | TWO PIPES ARE FLOATING AND NO REFERENCE POINT OR USE. |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 59. DONE. |
| | |
| | 60. SHEET P 9.0.16, PLEASE SHOW AND LABEL ALL SHUT-OFF |
| | VALVES FOR HOSE BIBBS. FOUR RISERS ARE NOT LABELED WITH |
| | SIZE AND NO REFINANCE POINT NEXT TO THE WATER |
| | DISTRIBUTION ISOMETRIC VERBIAGE. PLEASE LABEL |
| | REFERENCES TO WHERE WATER LINES COME FROM AND GO PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 61. SHEET P 9.0.18, IT SEEMS THE PIPES WERE MOVED AND |
| | FITTING AND PIPES' CONNECTION IS FLOATING IN DRAWING; |
| | PLEASE CONNECT AND SIZE TO ITS PERSPECTIVE POINTS OF |
| | CONNECTIONS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 61B. NEW COMMENT ON P 9.0.19; DETAIL TWO HAS GRIDLINE |
| | NUMBERS OF THE DRAWING; PLEASE LOWER PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 62. DONE. |
| | |
| | A. DONE. |
| | |
| | 63. DONE. |
| | |
| | 64.DONE. |
| | |
| | 65. IT LOOKS LIKE THE PAGE UPLOADED HAS CHANGED AND |
| | DOES NOT REFLECT WHAT WAS REQUESTED; PLEASE CORRECT AND |
| | RESUBMIT. SHEET P 9.1.5, IN DETAIL THREE, 1/2" H & C |
| | LINES TO THE SHOWER, C WATER CLOSET, AND H & C TO THE |
| | LAV NOT SIZED OR LABELED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 66. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.6; |
| | NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 67. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.7; |
| | NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 68. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.9; |
| | NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR LABELED |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | A. DONE. |
| | |
| | 69. SECOND REQUEST; SHEET P 9.1.9, 1/2" H & C TO THE |
| | WASHING MACHINE, FRIG, LAV, SHOWER, AND WATER CLOSET |
| | ARE NOT SIZED OR LABELED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 70. SHEET P 9.1.10, 1/2" HOT AND COLD WATER NOT SIZED |
| | TO THE FRIG AND THE TWO WATER CLOSET AND TUB PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 71. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.11; |
| | NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR LABELED |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | A. THE RESPONSE TO THIS WILL NOT WORK AS THE SHOWER MAY |
| | BE OVER 8' IN THE DISTANCE TO UP AND DOWN VENT; PLEASE |
| | CLARIFY; DETAIL ONE SHOWS WATER CLOSET AND SHOWER NOT |
| | VENTED; TRAPS REQUIRE A SYSTEM OF VENTING SO THAT A |
| | PRESSURE DIFFERENTIAL OF NOT MORE THAN 1" FOR EACH PER |
| | THE 2017 FBC SEC. 901.2. |
| | |
| | 72. SECOND REQUEST; SHEET P 9.1.12, 1/2" H & C NOT |
| | LABELED OR SIZED TO BOTH LAVS AND WATER CLOSET PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 73. SECOND REQUEST; SHEET P 9.1.13, 1/2" H & C NOT |
| | LABELED OR SIZED TO LAVS, TUB, AND WATER CLOSET AND |
| | 1/2" H & C NOT LABELED OR SIZED TO LAV AND WATER CLOSET |
| | THEN TO SHOWER PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | |
| | SWIMMING POOL |
| | |
| | 1. PROVISO FOR THE OPERATING PERMIT STAMPED BY THE |
| | FLORIDA DEPARTMENT OF HEALTH PER FL. STATUTES 514.03, |
| | 553.79 (11). |
| | |
| | 2. DONE. |
| | |
| | 3. ATTACHMENT NOT FOUND OR UPLOADED; SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR THE POOL SHOWER. THE |
| | POOL SHOWER SHALL COMPLY WITH THE REQUIREMENTS OF ANSI |
| | A117.1 FOR COMPLIANCE WITH FAIR HOUSING REQUIREMENTS. |
| | |
| | 4 DONE. |
| | |
| | 5. DONE. |
| | |
| | 6. DONE. |
| | |
| | 7. DONE. |
| | |
| | 8. DONE. |
| | |
| | 9. SECOND REQUEST; SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE POOL HEATER. THE POOL HEATER SHALL HAVE A |
| | MINIMUM THERMAL EFFICIENCY OF 82% PER 2017 FBC-ENERGY |
| | TABLE C404.2. |
| | |
| | 10. DONE. |
| | |
| | 11. DONE. |
| | |
| | 12. DONE. |
| | |
| | 13. PLEASE PLACE A NOTE ON THE PLANS; SHEET. P2.3 - |
| | THERE IS A NOTE ON THE COLLECTOR TANK DETAIL THAT |
| | STATES" COLLECTOR TANK PIT DRAINAGE BY G.C." SUBMIT |
| | DETAILS ON THIS DRAINAGE AND ITS TERMINATION POINT OR |
| | PROVIDE THE PLAN SHEETS OF THIS PROJECT WHERE THIS |
| | INFORMATION CAN BE FOUND. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | 14. DONE. |
| | |