Plan Review Notes
Plan Review Notes For Permit 20101431
Permit Number 20101431
Review Stop P
Sequence Number 2
Notes
Date Text
2021-03-12 13:40:0203/12/21 2ND REVIEW PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 PLEASE NOTE THAT WE CAN DO A ZOOM MEETING FOR THIS
 REVIEW TO CLARIFY THE IN-QUESTION COMMENT IF NEEDED.
 YOU MAY CONTACT ME VIA PHONE OR EMAIL TO SET THIS
 MEETING UP AT YOUR CONVENIENCE.
  
 1. THE RESPONSE TO COMMENT NOT FOUND OR NEW DRAWING;
 PLEASE PROVIDE PAGE AND OR DETAIL REFERENCE; SHEET 5 OF
 16 REFERS TO 45,800 CUBIC FOOT TANK STORAGE CHAMBERS.
 SUBMIT A DETAIL OF THIS STORAGE ARRANGEMENT, IT'S
 PURPOSE AND ANY/ ALL ASSOCIATED PIPING, PUMPS AND/OR
 ANY OTHER DETAILS ASSOCIATED WITH THIS SYSTEM. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 2. SHEETS, ALS 0.2, ALS 0.3, ALS 0.4, ALS 0.5, THE
 REFERENCE NOTES HAVE FAIR HOUSING ACT DESIGN MANUAL
 (1998), WHICH IS FINE BUT ALSO NEEDS TO HAVE THE
 REFERENCES TO THE ANSI A117.1 1986, AND THIS IS THE ONE
 THAT SHOULD BE USED IN COMMON AREAS. THE ANSI 2009 WAS
 USED IN SOME COMMENT IN THE LAST REVIEW WHICH DOES NOT
 APPLY AND SHOULD BE NOTED THE SAFE HARBORS IN USE.
 PLEASE MAKE CHANGES PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 A. ON SHEET ALS 0.1, PLEASE PLACE A NOTE THAT THE BUILT
 OUT AREA SHALL BE BUILT TO THE CURRENT FLORIDA BUILDING
 CODE ACCESSIBILITY.
  
 B. A. ON ALL NOTE ON THESE PAGES, A NOTE THAT STATES
 FHA DESIGN MANUAL (1998 ED.) IS FINE, BUT THE PART OF
 ADA FBC 2017 WILL NEED TO BE REMOVED. ANY CODE
 REFERENCE NOTES TO THE ACCESSIBILITY CODE FBC NEED TO
 BE REMOVED AS WELL.
  
 C. ON ALS 0.02, PLEASE PROVIDE THE DISTANCE FROM THE
 WALL ON THE TOILET WHERE IT GIVES THE REAR GRAB OF THE
 BAR OF 1'- 6" ABSOLUTE AND REMOVES THE 16? FROM THE
 COMPARTMENT DRAWING PER THE ANSI 117.1 1886 4.16.2. THE
 GRAB BARS FOR THE SUPPORT NEED TO COMPLY WITH THE ANSI
 117 4.24.3, AND THE BACKING ON THE DETAIL MAY NOT BE
 ENOUGH FOR THE ALLOWABLE STRESS OF 250 LBS. PLEASE
 ADDRESS THE APPLICATION OR INCREASE THE SIZE OF THE
 BACKING; PROVIDE DETAIL IF POSSIBLE. THE HEIGHT OF GRAB
 BARS FOR THE TOILET IS NOT CONSISTENT, AND THEY NEED TO
 MEASURE TO THE CENTER OF THE BAR PER THE ANSI 4.17.6.
 THE GRAB BAR IN A VERTICAL POSITION IS NOT IN ANY OF
 THE STANDARDS REFERENCES, AND THERE ARE NO EXCEPTIONS.
 PLEASE REMOVE ALL DRAWINGS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 D. ON SHEET ALS.0.4, NO ACTION WAS TAKEN ON THIS
 COMMENT. THERE ARE FHA DETAILS WITH ADA, ACCESSIBLY /
 ICC ANSI A117.1-2009 NOTES; PLEASE CORRECT THEM. PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. PLEASE PROVIDE THE MAXIMUM HEIGHT AND CLEARANCE FOR
 URINAL PARTITIONS PER THE 2017 FBC P 405.3.5 URINAL
 PARTITIONS.
  
 3. HUD RECOGNIZES TEN SAFE HARBORS FOR COMPLIANCE WITH
 THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS. THE ICC/ANSI A117.1 - 2009 IS NOT LISTED
 AS A SAFE HARBOR. HUD SAID IN THE INTRODUCTION TO THE
 ACCESSIBILITY GUIDELINES, "BUILDERS AND DEVELOPERS MAY
 CHOOSE TO DEPART FROM THESE GUIDELINES AND SEEK
 ALTERNATE WAYS TO DEMONSTRATE THAT THEY HAVE MET THE
 REQUIREMENTS OF THE FAIR HOUSING ACT." THE STANDARD
 EMPLOYED MUST MEET ALL OF THE DESIGN AND CONSTRUCTION
 REQUIREMENTS SPECIFIED IN THE FAIR HOUSING ACT AND
 HUD'S FAIR HOUSING ACT REGULATIONS, AND PROVIDE THE
 SAME OR A STRICTER DEGREE OF ACCESSIBILITY THAN THE
 RECOGNIZED SAFE HARBORS. FAIR HOUSING ACT DESIGN
 MANUAL, PAGE 13. PREAMBLE TO THE GUIDELINES, 56 FR
 9478-79, MARCH 6, 1991. THE PURPOSE OF THE FAIR HOUSING
 ACT GUIDELINES IS "TO DESCRIBE THE MINIMUM STANDARDS OF
 COMPLIANCE WITH THE SPECIFIC ACCESSIBILITY REQUIREMENTS
 OF THE ACT." PREAMBLE TO THE GUIDELINES, 56 FR 9472,
 9476, MARCH 6, 1991. VERIFICATION MUST BE PROVIDED THAT
 THE 2009 EDITION OF THE ANSI A117.1 PROVIDES THE SAME
 OR A STRICTER DEGREE OF ACCESSIBILITY THE RECOGNIZED
 SAFE HARBORS.
  
 4. DONE.
  
 5. PLEASE ADDRESS COMMENT TWO AND REMOVE ADA FBC 2017
 DETAIL ON TITLE BLOCK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PLEASE REFER TO COMMENT TWO FOR CORRECTIONS; SHEET.
 ALS 0.2 - DRINKING FOUNTAIN DETAILS - THE DETAIL TITLE
 REFERS TO THE ANSI 2009 EDITION BUT NOTE #1 REFERS TO
 THE FLORIDA BUILDING CODE. THE COMMON AREAS SHALL
 COMPLY WITH THE APPLICABLE STANDARD USED FOR FAIR
 HOUSING DESIGN COMPLIANCE. THE FLORIDA BUILDING CODE
 DOES NOT APPLY TO THE COMMON AREAS OF THE BUILDING. THE
 FLORIDA BUILDING CODE WOULD APPLY TO ANY RETAIL OR
 TENANT SPACES THAT DO NOT FALL UNDER FAIR HOUSING
 REQUIREMENTS. THE SAME APPLIES TO THE URINAL DETAIL.
 REVISE THE NOTES.
  
 7. DONE.
  
 8. DONE.
  
 9. DONE.
  
 10. THERE IS NO INFORMATION ON THIS PAGE THAT SEEMS TO
 HAVE TWO-THIRD OF THE DETAILS DELETE. IF THIS IS IN
 ERROR, PLEASE CLARIFY. PLEASE REFER TO COMMENT TWO AND,
 IF NEEDED, PUT BACK INFORMATION THAT WILL BE REQUIRED
 FOR THESE PLANS; SHT. ALS 0.3 - ACCESSIBLE WATER
 CLOSETS DETAIL - SECTION 1003.11.2.4.4 OF THE NOTED
 ANSI STANDARD REQUIRES THE CLEARANCE AT THE WATER
 CLOSET TO BE 66 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL WHEN A LAVATORY IS LOCATED NEXT TO
 THE WATER CLOSET FOR TYPE "A" ACCESSIBLE WATER CLOSETS.
 THE DEPTH OF THE LAVATORY SHALL BE A MAXIMUM OF 24
 INCHES.
  
 11. SOME GRAB BARS ARE 36" TO THE TOP AND OTHERS 36" TO
 THE MIDDLE. ARE THESE FHA OR ACC REFERENCES? SEE
 COMMENT TWO? PLEASE CLARIFY PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 12. THIS COMMENT IS NOT CLEAR ABOUT WHAT WAS CORRECTED
 TO ITS REFERENCE OF THE DETAILS; SHOW THE CLEAR FLOOR
 SPACE DIMENSIONS FOR THE WATER CLOSETS ON ALL THE WATER
 CLOSET DETAILS ON THE FHA DRAWINGS. COMPLY WITH THE
 REQUIREMENTS FROM THE DESIGN STANDARD BEING USED.WPB
 AMEND. TO FBC
 SEC. 107.2.1.
  
 13. ITEM REMOVE.
  
 14. DONE.
  
 15. DONE.
  
 16. DONE.
  
 17. COULD NOT LOCATE THE PAGE REFERENCE GIVEN ALS 6.1.
 NO SUCH PAGE NUMBER. PLEASE CLARIFY.
  
 18. COULD NOT LOCATE THE PAGE REFERENCE GIVEN ALS 6.1.
 NO SUCH PAGE NUMBER. PLEASE CLARIFY.
  
 19. DONE.
  
 20. DONE.
  
 21. DONE.
  
 22. DONE.
  
 23. DONE.
  
 24. THE RESPONSE TO THE COMMENT IS NOT CORRECT; PLEASE
 REFER TO THE DESIGN MANUAL PAGE 7.43 AND FIGURE 7.44;
 THE MAXIMUM DEPTH OF THE LAVATORIES SHALL BE 24 INCHES.
 THE PLANS SHOW SOME OF THE LAVATORIES AS 25 1/2 INCHES
 DEEP. INDICATE ON THE UNIT FLOOR PLANS THAT THE
 LAVATORIES' MAXIMUM DEPTH IS 24 INCHES PER ANSI A117.1.
  
 25. DONE.
  
 26 SECOND REQUEST; SHEET A9.17.1 - UNIT 17 - SHOWS THE
 WATER CLOSET IN THE MASTER BATH LOCATED 2 FEET 5 INCHES
 ( 2'- 5" ) FROM THE ADJACENT WALL TO THE WATER CLOSET'S
 CENTERLINE. THE WATER CLOSET SHALL BE 18 INCHES FROM
 SIDE TO ITS CENTERLINE PER THE FHAGL PAGE 6.5.
  
 27. SHEET A9.20.1 - UNIT 20 ? IS MISSING THE TYPE FOR
 FHA; IS IT AN A OR A B UNIT?? PLEASE PROVIDE PER WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 28. DONE.
  
 29. DONE.
  
 30. DONE.
  
 31. DONE.
  
 32. DONE.
  
 A. DONE.
  
 33. DONE.
  
 34. DONE.
  
 35. PLEASE HAVE ENGINEER ADDRESS SHEET P 1.0.1. THE
 GRID NUMBERS AND LETTERS ARE ON TOP OF EACH OTHER IN
 SOME PLACES, AND PLEASE OFFSET OR MOVE AWAY FOR CLARITY
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. THIS IS TYPICAL
 ON ALL PLUMBING PAGES, SO NOT TO REPEAT EVERY COMMENT;
 IT IS NOTED IN THIS ONE ONLY.
  
 A. DONE.
  
 36. PLUMBING RISERS WILL BE MOVED TO THE INSIDE FACE OF
 THE COLUMN DURING THE SHOP DRAWING COORDINATION TO
 ALLOW THE CONCRETE COLUMN TO PROVIDE PROTECTION. PLEASE
 PLACE A NOTE ON THE PLANS ON THIS COMMENT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 IN ANSWER TO THE RESPONSE, PLEASE NOTE THE REFERENCE
 PAGES; PLUMBING RISERS WILL BE MOVED TO THE INSIDE FACE
 OF THE COLUMN DURING THE SHOP DRAWING COORDINATION TO
 ALLOW THE CONCRETE COLUMN TO PROVIDE PROTECTION.
  
 A. GRIDLINE LETTERS ARE NOT SHOWN. PLEASE MOVE THE
 DRAWING OVER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. DONE.
  
 C. SECOND REQUEST; THE STORAGE ROOM WITH THE LAUNDRY
 TRAY IS NOT LABELED NEXT TO THE ELEVATORS; PLEASE LABEL
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. DONE.
  
 37. DONE.
  
 A. DONE.
  
 38. DONE.
  
 39. DONE.
  
 40 DONE.
  
 41. SECOND REQUEST; SHEET P 1.5.B, IN THE POOL AREA, SO
 MANY MISSING CIRCLES AND LINES INDICATE THAT A PIPE IS
 GOING UP OR DOWN IN THE POOL AREA. PLEASE OVERLAY AND
 MATCH TO P 1.6.B; THERE ARE TOO MANY TO MENTION ON THIS
 PAGE I. E. PD, TD PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 42. DONE.
  
 A. DONE
  
 B. DONE.
  
 43. DONE.
  
 A. SECOND REQUEST, THERE IS ON V.2 FOR P0.2.1, PLEASE
 PROVIDE DETAILS FOR PLANT DRAINS AND PUT A REFERENCE ON
 KEYNOTE LEGEND PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. DONE.
  
 44. SECOND REQUEST; SHEET P 1.7.1A, THE GRID LINES ON
 THE LEFT BOTTOM ARE OFF THE PLOTTED DRAWING AND OTHER
 OVERLAPPED (AS MENTION BEFORE, PLEASE CORRECT ALL
 OVERLAPS IN ALL PAGES); PLEASE MOVE OVER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 45. DONE.
  
 A. SECOND REQUEST, PLEASE GIVE THE LOCATION. THERE IS
 NO LAYOUT SHOWING THE RD-1 AND HB-3; PLEASE PROVIDE A
 REFERENCE IF ON ANOTHER PAGE OR GENERATE ONE PLEASE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 46. SECOND REQUEST, THERE IS NO V.2 AVAILABLE; SHEET P
 1.8.1B, THERE IS AN AREA WHERE THE TRENCH DRAINS ARE,
 AND THEY ARE NOT LABELED. PLEASE LABEL PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 A. SECOND REQUEST, THERE IS NO V.2 AVAILABLE; SHEET;
 THERE IS NO LAYOUT SHOWING THE RD-1 AND TD-1; PLEASE
 PROVIDE ON PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 47. SECOND REQUEST; SHEET P 9.0.1, DETAIL 2 FOR THE
 FITNESS CENTER IT HAS A 6" PIPE COMING UP, NOT SIZED
 AND NOT LABELED OR WITH A REFERENCE POINT, ALSO SIZE
 THE HORIZONTAL 4" LINE GOING TO THE MEN'S ROOM, AND THE
 LADIES ROOM DOWNSTREAM HAS A FEW 3" AND 4" NOT SIZED AS
 WELL. PLEASE PROVIDE SIZES PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 A. SECOND REQUEST; ON THAT SAME DETAIL, THERE IS A 4"
 SANITARY LINE WITH NO LABEL AS TO WHERE IT IS GOING.
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. SECOND REQUEST; PLEASE SHOW ALL TRAP PRIMERS ON THE
 FLOOR DRAINS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. SECOND REQUEST; LAVATORIES ON ALL AP-3 NEED TO BE
 SHOWN HORIZONTALLY AS THEY SEEM TO BE IN AN S-TRAP
 POSITION. PLEASE CHANGE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. SECOND REQUEST; THERE ARE THREE 3" SANITARY PIPES
 GOING UP WITH NO DESTINATION VENT. PLEASE LABEL PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. SECOND REQUEST; THERE ARE TWO FLOATING FITTING AND A
 PIPE WITH A 90-DEGREE ELBOW GOING DOWN AND A WYE AT THE
 END; IT DOESN'T HAVE A SIZE OR DESTINATION; PLEASE
 REMOVE AND OR GIVE A REFERENCE TO ITS USE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. SECOND REQUEST; ON DETAIL FOUR, PLEASE SHOW SHUTOFF
 VALVES FOR THE RECIRCULATING PUMP AT THE FITNESS ROOM
 AREA WITH AN ACCESS BOX ON BOTH SIDES OF THE
 RECIRCULATING PUMP FOR THE WATER HEATER AND ALL
 FIXTURES PER THE 2017 FBC SEC. P 606.1.
  
 G. SECOND REQUEST; PLEASE SHOW AND LABEL ON ISOMETRIC
 THE HAMMER ARRESTOR FOR THE DRINKING FOUNTAIN AND ALL
 QUICK CLOSING VALVES PER THE 2017 FBC SEC. P 604.9.
  
 H. SECOND REQUEST; PLEASE SHOW AND LABEL CHECK VALVES
 ON THE RECIRCULATING SYSTEM PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 I. SECOND REQUEST; THE RECIRCULATING MANIFOLD TO THE
 HOT WATER LINES MAY NEED TO BE CLOSER TO THE OUTLET
 SOURCE; PLEASE REFER TO THE 2017 FBC ENERGY CODE TABLE
 C404.5.1.
  
 J. DONE.
  
 K. SECOND REQUEST; ON DETAIL ONE, AP-9 IS LABELED AS A
 FLOOR DRAIN; PLEASE MARK AS MOP SINK AND HAVE A NOTE
 THAT SURROUNDING THE WALL SHALL BE NON-ABSORBENT
 SURFACE IN ACCORDANCE WITH THE 2017 FBC BUILDING SEC.
 1210.2.2.
  
 L. SECOND REQUEST; IN THAT SAME DETAIL, THE MOP SINK
 AND DRINKING FOUNTAIN CANNOT DISCHARGE INTO A
 HORIZONTAL WET VENT PER THE 2017 FBC SEC. P 912.1.
  
 M. SECOND REQUEST; IN THAT SAME DETAIL, THE WATER
 CLOSET IS ON A SANITARY TEE ON ITS BACK; A WATER CLOSET
 BEND IS REQUIRED PER THE 2017 FBC SEC. P 420.4.
  
 48. DONE.
  
 A. DONE.
  
 B. DONE.
  
 C. SECOND REQUEST; NOT ALL COMMENTS WERE ADDRESSED. ON
 DETAIL 6/P 9.0.2, THE ARMS FOR THE STACK BY THE
 TWO-FLOOR DRAINS HAVE THE ARMS IN AN S-TRAP. PLEASE
 SHOW IN A HORIZONTAL POSITION. THE FLOOR DRAIN NEXT TO
 AP-10 IS MISSING A TRAP PRIMER #. THE LAVATORY IN THE
 DOG SPA IS NOT SHOWN ON THE ISOMETRIC. PLEASE
 INCORPORATE IT IN THE SYSTEM OF THIS ISOMETRIC PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. DONE.
  
 E. DONE.
  
 F. DONE.
  
 G. DONE.
  
 49. SECOND REQUEST; SHEET P 9.0.3, IN DETAIL 1/P 9.0.3
 AND 2/P 9.0.3, IN THE JANITOR'S ROOM, THE MOP SINK IS
 LABELED AS FD-2, PLEASE CORRECT, PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 A. DONE.
  
 B. DONE.
  
 PLEASE ADD A NOTE THAT A SEPARATE PERMIT IS REQUIRED
 FOR THE GREASE INTERCEPTOR.
  
 C. SECOND REQUEST HERE IS NO NOTE ON TEMPERED WATER
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO
 (ASSE 1070 OR CSA B125.3) PER THE 2017 FBC SEC. 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
  
 D. DONE.
  
 E. DONE.
  
 50. DONE.
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. DONE.
  
 F. SECOND REQUEST; ON DETAIL 9/P 9.0.4, PLEASE SHOW
 SHUT-OFF VALVES TO THE MOP SINK, SIZE, AND LABEL THEM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. DONE.
  
 51. SECOND REQUEST; SHEET P 9.0.5, THE DRAWING HAS
 MISSING DECK DRAINS AND EXTRA ROOF DRAINS, RISERS ARE
 CONNECTING TO DRAINS THAT ARE MISSING FITTINGS, TOO
 MANY TO CALL OUT PLEASE GO BACK AND REFER TO THE FLAT
 DRAWING AND MAKE CORRECTIONS FOR CLARITY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 52. SECOND REQUEST; SHEET P 9.0.6, PLEASE SIZE BOTH,
 PLEASE SHOW CLEAN CLEAN-OUTS ON VERTICALS, AND LABEL
 THE VENTS. THERE IS A 6" 121 GPM PIPE GOING WITH NO DD
 R? UP. WHERE IS THE NEW 3" CD COMING FROM AND PIPES
 GOING NOT SIZED, AND ARE THEY VENTS? PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 53. SHEET P 9.0.7, THE DP-8 AND DP-9 SIZES ARE NOT
 LABELED, CD-1 AND CD-2 SIZES ARE NOT LABELED, AND THE
 THREE 1" CONDENSATE TIED TOGETHER IS GOING DOWN THAT IS
 MISSING WHERE IT'S GOING TO AND SIZE, CONDENSATE NUMBER
 DOES NOT CONNECT AT 90 GOING DOWN. PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 54. DONE.
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 55. SHEET P 9.0.9, PLEASE PROVIDE CLEAN-OUT ON THESE
 STORM RISERS PER 2017 FBC SEC. 1101.8 CLEANOUTS
 REQUIRED.
  
 56. SHEET P 9.0.12, NEW COMMENT THERE IS A 12" 45
 MISSINGS ON THE DRAIN AND DIRECTIONAL FITTING UPSTREAM
 OF THAT IS NOT DIRECTIONAL ALSO THE ONE ON BATHROOM
 GROUP IS WRONG, PLEASE CORRECT. S/R-9 IS NOT CONNECTED
 TO THE TRUNK LINE, AND THE TRAP FOR THE LAST FLOOR
 DRAIN WITH A VENT IS DRAWN WRONG. THE 4" FUTURE PIPE
 NUMBER S/R-9 DOES NOT HAVE A DIRECTIONAL FITTING. S/R-3
 PIPE SIZE IS WRONG, AND ALSO UPSTREAM LOOKS OVERSIZED.
 PLEASE FIX ALL SANTEE ON ITS SIDE AND USE WYE FITTINGS
 AND CORRECT ALL DIRECTIONAL FITTINGS. ALL DRAINS FROM
 ELEVATORS REQUIRE A TRAP AND A TRAP PRIMER, AND THE
 PUMP TWO ELEVATOR TRAP HAS NOWHERE TO CONNECT BY
 S/R-11. PIPES ARE FLOATING; PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 A. DONE.
  
 B. STILL NOT ADDRESSED. PLEASE SHOW THE STACK BY THE
 TWO-FLOOR DRAINS WITH THE ARMS IN AN S-TRAP. PLEASE
 SHOW IN A HORIZONTAL POSITION PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. DONE.
  
 D. THE THREE FD-1 NEXT TO STACK S/R-9 NOT DRAWN
 CORRECTLY, PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 57. DONE.
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 58. DONE.
  
 A. NEW COMMENT; IN DETAIL ELEVEN, THE RIGHT BOTTOM
 CORNER 1/P 0.3.0 HAS A PIPE WITH TWO NINETY DOWN AND NO
 REFERENCE; PLEASE LABEL OR DELETE IF NOT NEEDED PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. DONE.
  
 C. NEW COMMENT; IN DETAIL EIGHT, THE LEFT TOP CORNER
 TWO PIPES ARE FLOATING AND NO REFERENCE POINT OR USE.
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 59. DONE.
  
 60. SHEET P 9.0.16, PLEASE SHOW AND LABEL ALL SHUT-OFF
 VALVES FOR HOSE BIBBS. FOUR RISERS ARE NOT LABELED WITH
 SIZE AND NO REFINANCE POINT NEXT TO THE WATER
 DISTRIBUTION ISOMETRIC VERBIAGE. PLEASE LABEL
 REFERENCES TO WHERE WATER LINES COME FROM AND GO PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 61. SHEET P 9.0.18, IT SEEMS THE PIPES WERE MOVED AND
 FITTING AND PIPES' CONNECTION IS FLOATING IN DRAWING;
 PLEASE CONNECT AND SIZE TO ITS PERSPECTIVE POINTS OF
 CONNECTIONS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 61B. NEW COMMENT ON P 9.0.19; DETAIL TWO HAS GRIDLINE
 NUMBERS OF THE DRAWING; PLEASE LOWER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 62. DONE.
  
 A. DONE.
  
 63. DONE.
  
 64.DONE.
  
 65. IT LOOKS LIKE THE PAGE UPLOADED HAS CHANGED AND
 DOES NOT REFLECT WHAT WAS REQUESTED; PLEASE CORRECT AND
 RESUBMIT. SHEET P 9.1.5, IN DETAIL THREE, 1/2" H & C
 LINES TO THE SHOWER, C WATER CLOSET, AND H & C TO THE
 LAV NOT SIZED OR LABELED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 66. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.6;
 NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 67. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.7;
 NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 68. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.9;
 NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR LABELED
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 A. DONE.
  
 69. SECOND REQUEST; SHEET P 9.1.9, 1/2" H & C TO THE
 WASHING MACHINE, FRIG, LAV, SHOWER, AND WATER CLOSET
 ARE NOT SIZED OR LABELED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 70. SHEET P 9.1.10, 1/2" HOT AND COLD WATER NOT SIZED
 TO THE FRIG AND THE TWO WATER CLOSET AND TUB PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 71. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.11;
 NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR LABELED
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 A. THE RESPONSE TO THIS WILL NOT WORK AS THE SHOWER MAY
 BE OVER 8' IN THE DISTANCE TO UP AND DOWN VENT; PLEASE
 CLARIFY; DETAIL ONE SHOWS WATER CLOSET AND SHOWER NOT
 VENTED; TRAPS REQUIRE A SYSTEM OF VENTING SO THAT A
 PRESSURE DIFFERENTIAL OF NOT MORE THAN 1" FOR EACH PER
 THE 2017 FBC SEC. 901.2.
  
 72. SECOND REQUEST; SHEET P 9.1.12, 1/2" H & C NOT
 LABELED OR SIZED TO BOTH LAVS AND WATER CLOSET PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 73. SECOND REQUEST; SHEET P 9.1.13, 1/2" H & C NOT
 LABELED OR SIZED TO LAVS, TUB, AND WATER CLOSET AND
 1/2" H & C NOT LABELED OR SIZED TO LAV AND WATER CLOSET
 THEN TO SHOWER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 SWIMMING POOL
  
 1. PROVISO FOR THE OPERATING PERMIT STAMPED BY THE
 FLORIDA DEPARTMENT OF HEALTH PER FL. STATUTES 514.03,
 553.79 (11).
  
 2. DONE.
  
 3. ATTACHMENT NOT FOUND OR UPLOADED; SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE POOL SHOWER. THE
 POOL SHOWER SHALL COMPLY WITH THE REQUIREMENTS OF ANSI
 A117.1 FOR COMPLIANCE WITH FAIR HOUSING REQUIREMENTS.
  
 4 DONE.
  
 5. DONE.
  
 6. DONE.
  
 7. DONE.
  
 8. DONE.
  
 9. SECOND REQUEST; SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE POOL HEATER. THE POOL HEATER SHALL HAVE A
 MINIMUM THERMAL EFFICIENCY OF 82% PER 2017 FBC-ENERGY
 TABLE C404.2.
  
 10. DONE.
  
 11. DONE.
  
 12. DONE.
  
 13. PLEASE PLACE A NOTE ON THE PLANS; SHEET. P2.3 -
 THERE IS A NOTE ON THE COLLECTOR TANK DETAIL THAT
 STATES" COLLECTOR TANK PIT DRAINAGE BY G.C." SUBMIT
 DETAILS ON THIS DRAINAGE AND ITS TERMINATION POINT OR
 PROVIDE THE PLAN SHEETS OF THIS PROJECT WHERE THIS
 INFORMATION CAN BE FOUND. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 14. DONE.
  