| 2021-02-16 13:35:14 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20101431 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE HEATING AND COOLING SIZING |
| | CALCULATIONS, I DO NOT SEE THE CALCULATIONS IN THIS |
| | SUBMITTAL. FBC EC C403.2.1 |
| | |
| | 2) PLEASE PROVIDE RESPONSE FOR QUESTION NUMBER 4 OF |
| | FIRST REVIEW. THE ENGINEER MUST ADDRESS THE RESTRICTION |
| | OF THE XVENT LOUVER FOR DRYER EXHAUST. THE DOCUMENT |
| | MENTIONED IN RESPONSE LETTER FROM XVENT WAS NOT |
| | INCLUDED IN THIS SUBMITTAL. FBC M 504.8.5.2 |
| | |
| | 3) SHEET M1.1.1B: PLEASE PROVIDE NOTES FOR EXHAUST FANS |
| | 6 AND 8 SHOWING THEY COMPLY WITH FBC 717.5.4 EXCEPTION |
| | 3.2 AND 3.6. |
| | |
| | 4) SHEET M1.1.1B: PLEASE PROVIDE NOTES FOR THE FRESH |
| | AIR DUCT FOR AHU-A7 SHOWING IT COMPLIES WITH FBC |
| | 717.5.4 EXCEPTION 3.2 AND 3.6. |
| | |
| | 5) SHEET M1.2.1A: PLEASE PROVIDE NOTES FOR EF-1 DUCT |
| | SHOWING IT WILL COMPLY WITH FBC 717.5.4 EXCEPTION 3.2 |
| | AND 3.6. |
| | |
| | 6) SHEET M1.2.1B: THERE ARE SEVERAL KEYNOTE NUMBERS ON |
| | THIS SHEET BUT THERE ARE NO KEYNOTES CORRESPONDING WITH |
| | THESE NUMBERS. PLEASE ADD THE CORRESPONDING KEYNOTES TO |
| | THIS SHEET. FBC 107.2.1 |
| | |
| | 7) SHEET M1.3.1A: PLEASE EXPLAIN NOTE 6, IS THIS NOTE |
| | ONLY FOR THE EXHAUST DUCT FROM ELECTRIC ROOM TO SHAFT? |
| | HOW ARE YOU PROTECTING THE EXHAUST DUCT FOR THE |
| | CORRIDOR EXHAUST? IF THE DUCT MEETS 717.5.4 (3) WHY USE |
| | THE FIRE WRAP? FBC 107.2.1 |
| | |
| | 8) PLEASE PROVIDE A RISER DETAIL DRAWING OF THE |
| | SUBDUCT AND SHOW SIZE OF DUCT AND EACH FLOOR WITH ALL |
| | DUCTS. FBC 107.2.1 |
| | |
| | 9) PLEASE SHOW THE EXHAUST DUCT IN THE ELECTRIC ROOMS |
| | IN THE CORRIDORS DOES NOT STOP AT THE RATED WALL AS |
| | THIS DOES NOT MEET FBC 717.5.4 (3.5) |
| | |
| | 10) SHEET M1.3.1B: PLEASE PROVIDE A DETAIL DRAWING OF |
| | THE GENERATOR EXHAUST FLUE. FBC 107.2.1 |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |