Plan Review Notes
Plan Review Notes For Permit 20101431
Permit Number 20101431
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2021-01-29 11:28:12*********UPDATE:********
  
 2/3/20
  
 SPOKE WITH MR LEBLANC FROM SPINAOROUKE VIA TELEPHONE
 AND HE EXPLAINED HIS COMMENTS. THE BELOW COMMENTS HAS
 BEEN ADDRESSED AND ACCEPTED.
  
  
  
  
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 ***THE FOLLOWING COMMENTS ARE RESUBMITTED FOR
 CLARIFICATIONS:
  
 1) SHEET ALS 6.1 - IT IS NOT CLEAR WHERE THE 2ND EXIT
 OFF THE RECREATIONAL DECK IS LOCATED.
  
 PLEASE REVIEW AND CLEARLY INDICATE AND ACCOUNTING FOR
 THE REQUIRED SEPARATION DISTANCE AND OCCUPANT LOAD.
  
 NEW COMMENT:
  
 *** BASED ON THE RESPONSE PROVIDED OF 532 OCCUPANTS TO
 THE POOL DECK A 3RD EXIT IS REQUIRED
  
 7.4.1.2 THE NUMBER OF MEANS OF EGRESS FROM ANY STORY OR
 PORTION
 THEREOF, OTHER THAN FOR EXISTING BUILDINGS AS PERMITTED
 IN CHAPTERS
 11 THROUGH 43, SHALL BE AS FOLLOWS:
 (1) OCCUPANT LOAD MORE THAN 500 BUT NOT MORE THAN 1000
 ? NOT
 LESS THAN 3
 (2) OCCUPANT LOAD MORE THAN 1000 ? NOT LESS THAN 4
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FIRE
 CODE REFERENCES.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  