| 2021-02-22 15:25:04 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) & CITY OF W.P.B. |
| | CHAPTER 1 AMENDMENTS |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | 345 BANYAN BLVD. |
| | PERMIT #20101431 |
| | 170 MPH, EXPOSURE "D" |
| | FLOOD ZONE "X" |
| | HIGH-RISE BLDG. PER FBC 403 (15 STORIES, 177'-8" TO TOP |
| | OF OCCUPIED FLOOR, 188'-0" TO HIGHEST ROOF OF OCCUPIED |
| | SPACE) |
| | CONSTRUCTION TYPE: IA (REDUCED TO IB FOR FIRE |
| | RESISTANCE RATING OF BUILDING MATERIALS PER FBC |
| | 403.2.1.1) |
| | OCCUPANCY TYPE: (MIXED USE) R-2, S-2, S-1, M, B, A-3 |
| | BLDG. AND GARAGE ARE FULLY SPRINKLERED |
| | GARAGE IS ENCLOSED |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PARTIALLY RESOLVED. [THE SIGNED AND NOTARIZED |
| | THRESHOLD FORMS FROM THE OWNER, CONTRACTOR, THRESHOLD |
| | ENGINEER AND DELEGATE INSPECTORS WERE NOT SUBMITTED. NO |
| | JOB HISTORY FROM THE CONTRACTOR WAS SUBMITTED. PROVIDE |
| | AN EMAIL ADDRESS AND I WILL SEND YOU THE CURRENT |
| | THRESHOLD DOCUMENTS AND FORMS.] THIS PROJECT IS A |
| | THRESHOLD BUILDING PER FL S. S. 553.71(7) "THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION |
| | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL THRESHOLD BUILDING INSPECTION PLAN IS |
| | TO PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE. |
| | |
| | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | |
| | J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL |
| | BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER |
| | 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS. |
| | |
| | 2) NOT RESOLVED. ART IN PUBLIC PLACES |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT |
| | 822-1515 OR E-MAIL: [email protected] |
| | |
| | 3) NOT RESOLVED. [SUBMIT DIGITALLY SIGNED SOIL REPORT.] |
| | SUBMIT A SIGNED AND SEALED GEOTECHNICAL REPORT FROM A |
| | FLORIDA LICENSED ENGINEER WITH THE RECOMMENDED SOIL |
| | PREPARATION METHOD AND THE SOIL BEARING CAPACITY. FBC |
| | 1801.2 |
| | |
| | 4) NOT RESOLVED. [SUBMIT A MOT PLAN.] SPECIFY HOW |
| | COMPLIANCE WITH FBC CHAPTER 33 SAFEGUARDS DURING |
| | CONSTRUCTION FOR THE FOUNDATION PERMIT WILL BE MET. |
| | PROVIDE A MOT (MANAGEMENT OF TRAFFIC) PLAN. RIGHT OF |
| | WAY PERMITS WILL BE REQUIRED TO CLOSE SIDEWALKS, |
| | STREETS, ETC. |
| | |
| | 5) NOT RESOLVED. [IN ORDER TO AVOID ANY CONFUSION, |
| | PLEASE IDENTIFY THE VERTICAL DATUM FOR THE ELEVATIONS |
| | ON THE SITE PLANS. I DID SEE A SMALL NOTE ON THE |
| | ARCHITECTURAL PLANS THAT ALL ELEVATIONS ARE NAVD. FBC |
| | 107.2.1 |
| | |
| | 6) RESOLVED. THE EXIT PASSAGEWAY AT STAIR 3 IS |
| | INCORRECTLY LABELED AS AN EGRESS PASSAGEWAY. PLEASE |
| | CHANGE LABEL TO EXIT PASSAGEWAY AND ADD NOTE THAT |
| | OPENINGS AND PENETRATIONS INTO IT ARE ONLY ALLOWED FOR |
| | EXITING PURPOSES AND ITEMS SERVING THE PASSAGEWAY. AN |
| | EXIT PASSAGEWAY IS AN EXTENSION OF THE ENCLOSED |
| | INTERIOR EXIT STAIRWAY AND HAS REQUIREMENTS SIMILAR TO |
| | THE STAIRWAY. SEE FBC 1023.1 AND 1024. |
| | |
| | 7) NOT RESOLVED. [VERTICAL DATUM WAS NOT PROVIDED ON |
| | SHEETS SP1.0.1 OR SP1.1.1.] THE EXIT DISCHARGE FROM |
| | STAIR 3 IS NOT TO A PUBLIC WAY. IT APPEARS THAT THE |
| | OCCUPANTS WILL NEED TO TRAVEL THROUGH THE ADJACENT |
| | PROPERTY TO REACH THE PUBLIC WAY. [A] PUBLIC WAY. A |
| | STREET, ALLEY OR OTHER PARCEL OF LAND OPEN TO THE |
| | OUTSIDE AIR LEADING TO A STREET, THAT HAS BEEN DEEDED, |
| | DEDICATED OR OTHERWISE PERMANENTLY APPROPRIATED TO THE |
| | PUBLIC FOR PUBLIC USE AND WHICH HAS A CLEAR WIDTH AND |
| | HEIGHT OF NOT LESS THAN 10 FEET (3048 MM). PLEASE |
| | CLARIFY. FBC 1022 |
| | |
| | 8) NOT RESOLVED. [I DID NOT SEE THE APPROVAL LETTER |
| | FROM ZONING MENTIONED IN YOUR RESPONCE LETTER. SPECIFY |
| | THE FIRE SEPARATION DISTANCE BETWEEN THE PROPOSED |
| | BUILDING AND THE EXISTING BUILDING ON THE LOT. SHOW |
| | THAT THE AREA OF OPENINGS ON EACH FLOOR OF THE EXISTING |
| | BUILDING AND THE PROPOSED BUILDING WITH BOTH COMPLY |
| | WITH FBC 705.8.1.] THE EAST WALL IS NOT LISTED IN THE |
| | FIRE SEPARATION TABLE 705.8 ON SHEET ALS.0.1. FBC |
| | 107.2.1 |
| | |
| | 9) NOT RESOLVED. [SEE COMMENT NUMBER 8.] THE SITE PLANS |
| | APPEAR TO SHOW A PORTION OF THE EAST WALL IS ON THE |
| | PROPERTY LINE. THE DOORS TO THE TRANSFORMER ROOM SWING |
| | OUT OVER THE PROPERTY LINE WHICH IS NOT ALLOWED. PLEASE |
| | PROVIDE CLARIFICATION. FBC 107.2.1 |
| | |
| | 10) NOT RESOLVED. [PROVIDE THE REQUESTED CALCULATIONS.] |
| | THERE ARE MULTIPLE OPENINGS IN THE EAST WALL THAT ARE |
| | NOT ALLOWED BASED THE FIRE SEPARATION DISTANCE AND |
| | TABLE 705.8. NO OPENINGS ARE ALLOWED FROM 0<3 FEET AND |
| | 15 PERCENT FROM 3<5 FEET. PROVIDE CALCULATIONS FOR THE |
| | ALLOWABLE AREA OF OPENINGS ON THE EAST AND NORTH WALLS |
| | OF THE BUILDING. FBC 107.2.1.2 |
| | |
| | 11) RESOLVED. PLEASE REVISE GENERAL NOTE 21 ON SHEET |
| | ALS.0.1 TO REFERENCE THE 2017 FBC ACCESSIBILITY RATHER |
| | THAN THE 2003 IBC FOR ACCESSIBILITY. |
| | |
| | 12) RESOLVED. PLEASE REVISE THE NOTES ON ALS.0.2 THAT |
| | REFERENCE THE 2012 N.C. BUILDING CODE TO THE 2017 FBC. |
| | |
| | 13) RESOLVED. SHOW COMPLIANCE. FBC 3002.4 REQUIRES ANY |
| | BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET TO |
| | BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER |
| | ELEVATOR THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND |
| | FIRE DEPARTMENT ACCESS TO ALL FLOORS. THE ELEVATOR CAR |
| | SHALL BE OF A SIZE AND ARRANGEMENT TO ACCOMMODATE AN |
| | AMBULANCE STRETCHER 24 INCHES BY 76 INCHES WITH NOT |
| | LESS THAN 5-INCH RADIUS CORNERS, IN THE HORIZONTAL, |
| | OPEN POSITION AND SHALL BE IDENTIFIED BY THE |
| | INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES |
| | (STAR OF LIFE). |
| | |
| | 14) RESOLVED. [THE BUILDING OFFICIAL AND FIRE MARSHAL |
| | HAVE ACCEPTED THIS CONDITION.] THE ELEVATOR LOBBIES |
| | HAVE DIMENSIONS THAT ARE LESS THAN THE REQUIRED 8 FEET. |
| | 3007.6.4 LOBBY SIZE. REGARDLESS OF THE NUMBER OF FIRE |
| | SERVICE ACCESS ELEVATORS SERVED BY THE SAME ELEVATOR |
| | LOBBY, THE ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY |
| | SHALL BE NOT LESS THAN 150 SQUARE FEET (14 M2) IN AN |
| | AREA WITH A DIMENSION OF NOT LESS THAN 8 FEET (2440 |
| | MM). SEE SHEET A6.1.2 (PG. 157) AND OTHER SHEETS. |
| | |
| | 15) RESOLVED. SHOW COMPLIANCE. 403.6.1 FIRE SERVICE |
| | ACCESS ELEVATOR. IN BUILDINGS WITH AN OCCUPIED FLOOR |
| | MORE THAN 120 FEET (36 576 MM), MEASURED FROM THE |
| | ELEVATION OF STREET-LEVEL ACCESS TO THE LEVEL OF THE |
| | HIGHEST OCCUPIABLE FLOOR, NO FEWER THAN TWO FIRE |
| | SERVICE ACCESS ELEVATORS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION 3007. ALL REMAINING ELEVATORS, |
| | IF ANY, SHALL BE PROVIDED WITH PHASE I AND II EMERGENCY |
| | OPERATION. EACH FIRE SERVICE ACCESS ELEVATOR SHALL HAVE |
| | A CAPACITY OF NOT LESS THAN 3,500 POUNDS (1588 KG). |
| | |
| | 16) RESOLVED. ON SHEET ALS.1.1 THE MAXIMUM OVERALL |
| | DIAGONAL DIMENSION OF THE LOBBY AREA NEEDS TO INCLUDE |
| | THE MANAGERS OFFICE, WHICH IS PART OF THAT AREA. THE |
| | LONGEST DIAGONAL SHOULD BE TO THE EXTERIOR WALLS OFNTHE |
| | AREA FROM THE MANAGER'S OFFICE TO THE SOUTHEAST CORNER |
| | OF THE LOBBY. FBC 1007.1.1 TWO EXITS OR EXIT ACCESS |
| | DOORWAYS. |
| | |
| | 17) RESOLVED. ON SHEET ALS.4.1 THE SEPARATION DISTANCE |
| | OF THE TWO EXITS FROM UNIT 15 IS SHOWN ON THE PLANS, |
| | HOWEVER, THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE |
| | UNIT IS NOT PROVIDED. FBC 107.2.3 |
| | |
| | 18) RESOLVED. ON ALL LIFE SAFETY PLANS, SPECIFY THE |
| | COMMON PATH OF TRAVEL DISTANCE FROM THE MOST REMOTE |
| | POINT OF THE BALCONIES IN THE LARGER UNITS AND SHOW THE |
| | EXIT ACCESS TRAVEL DISTANCE FROM THE MOST REMOTE POINT |
| | OF THE MOST REMOTE UNIT ON THE FLOOR TO THE NEAREST |
| | EXIT COMPLIES WITH FBC 1017. |
| | |
| | 19) RESOLVED. ON ALL LIFE SAFETY PLANS, SPECIFY THE |
| | EXIT ACCESS TRAVEL DISTANCES IN THE PARKING GARAGE ON |
| | THE PLANS TO COMPLY WITH FBC 1017. |
| | |
| | 20) RESOLVED. ON SHEET ALS.6.1, THE EXIT PATH OF TRAVEL |
| | IS NOT SHOWN FROM THE MOST REMOTE POINT OF THE BALCONY |
| | IN UNIT 8. FBC 1017 |
| | |
| | 21) RESOLVED. ON SHEET ALS.7.1, THE MAXIMUM OVERALL |
| | DIAGONAL DIMENSION OF THE BUILDING AND THE 1/3 DIAGONAL |
| | EXIT SEPARATION DISTANCE ARE NOT PROVIDED. FBC 107.2.3 |
| | |
| | 22) RESOLVED. ON SHEET ALS.8.1, SPECIFY THE TOTAL |
| | OCCUPANT LOAD IN THE TABLE. IT APPEARS THAT THE TOTAL |
| | LOAD IS 94 OCCUPANTS. THE NUMBERS SPECIFIED AT THE EXIT |
| | STAIRS ARE FOR ONLY 47 OCCUPANTS. PLEASE CORRECT. FBC |
| | 107.2.3 |
| | |
| | 23) RESOLVED. THE MEAN ROOF HEIGHT IS NOT SPECIFIED IN |
| | THE GN - DESIGNER LOADS TABLE ON SHEET S0.1. (PG 272). |
| | FBC 107.2.1 |
| | |
| | 24) RESOLVED. ON SHEET S0.1, CONCRETE NOTE #1 NEEDS TO |
| | BE UPDATED TO THE 2017 FBC. FBC 107 |
| | |
| | 25) RESOLVED. ON SHEET S0.0.5, NOTE #5 IN THE WIND |
| | DIAGRAM NOTES SPECIFIES THE MEAN ROOF HEIGHT AS 118'-2" |
| | AND THE PLANS LIST 188'-0" AS THE HIGHEST ROOF OF THE |
| | OCCUPIED SPACE. PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 26) RESOLVED. THE WASTE (TRASH) CHUTE IS REQUIRED TO |
| | HAVE A 2 HOUR FIRE RESISTIVE RATING PER FBC 713.4 AND |
| | THE CHUTE ACCESS ROOMS ARE REQUIRED TO BE A MINIMUM 1 |
| | HOUR FIRE BARRIER PER FBC 713.13. SOME OF LIFE SAFETY |
| | PLANS SHEETS DO NOT CLEARLY SHOW THIS. PLEASE CORRECT. |
| | FBC 107.2.1 |
| | |
| | 27) RESOLVED. SHOW COMPLIANCE WITH FBC 2304.12 FOR |
| | TERMITE PROTECTION. |
| | |
| | 28) RESOLVED. VERIFY THE REQUIRED VERTICAL CLEARANCE OF |
| | 98 INCHES FOR THE VAN PARKING SPACE, ACCESS AISLE AND |
| | VEHICULAR ROUTE SERVING IT AS REQUIRED BY FBC |
| | ACCESSIBILITY SECTION 502.5. THERE HAVE BEEN ISSUES |
| | WITH EQUIPMENT OR SYSTEMS INSTALLED BELOW THE REQUIRED |
| | 98" IN THESE AREAS OF PARKING GARAGES. PLEASE PROVIDE |
| | NOTES ON THE DRAWINGS TO HELP AVOID THIS ISSUE. |
| | |
| | 29) NOT RESOLVED. [WHERE PROVIDED KITCHEN APPLIANCES |
| | ARE REQUIRED TO COMPLY WITH FBC ACCESSIBILITY SECTION |
| | 804.6] THE MICROWAVE OVEN IN THE WORK ROOM SHOWN IN |
| | ELEVATION 6 ON SHEET A9.50.5 DOES NOT APPEAR TO COMPLY |
| | WITH THE REQUIRED REACH RANGES OF FBC ACCESSIBILITY |
| | SECTIONS 308, 309.3 AND 804.6.2. |
| | |
| | 30) RESOLVED. SHOW COMPLIANCE FBC ACCESSIBILITY SECTION |
| | 242 FOR ACCESSIBLE ENTRY INTO THE POOL OR SPECIFY ON |
| | THE PLANS WHY IT IS NOT REQUIRED. COMMUNITY POOLS THAT |
| | ARE ASSOCIATED WITH A PRIVATE RESIDENTIAL COMMUNITY |
| | THAT DO NOT RECEIVE GOVERNMENTAL FINANCIAL ASSISTANCE |
| | OR SPONSORSHIP AND ARE LIMITED TO THE EXCLUSIVE OF |
| | RESIDENTS AND THEIR GUESTS ARE NOT COVERED BY THE ADA |
| | ACCESSIBILITY REQUIREMENTS, INCLUDING PROVISIONS FOR |
| | POOL LIFTS OR SLOPED ENTRIES. IF A SWIMMING POOL |
| | LOCATED IN A RESIDENTIAL COMMUNITY IS MADE AVAILABLE TO |
| | THE PUBLIC FOR RENTAL OR USE IT IS REQUIRED TO COMPLY |
| | WITH TITLE II OF THE ADA. SPECIFY ON THE PLANS THE |
| | FORMER OR SHOW COMPLIANCE WITH THE LATTER STATEMENTS. |
| | SEE DECLARATORY STATEMENT, DS 2013-011. (NOTE: A |
| | SEPARATE PERMIT WILL BE REQUIRED FOR THE POOL.) |
| | |
| | 31) RESOLVED. THE MAXIMUM DISTANCE FROM THE WATER'S |
| | EDGE OF THE SWIMMING POOL TO THE RESTROOMS IS NOT SHOWN |
| | CORRECTLY ON THE PLAN SHEET ALS.6.1. FBC454.1.6.1 THE |
| | ENTRY DOORS OF ALL RESTROOMS SHALL BE LOCATED WITHIN A |
| | 200-FOOT (60 960 MM) WALKING DISTANCE OF THE NEAREST |
| | WATER'S EDGE OF EACH POOL SERVED BY THE FACILITIES. |
| | PLEASE CORRECT. |
| | |
| | 32) RESOLVED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT |
| | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE |
| | DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE |
| | SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT |
| | BEFORE THEY CAN BE INSTALLED. |
| | |
| | 33) RESOLVED. FBC 107.3.4.1 DEFERRED SUBMITTALS. (I |
| | NOTED THAT THERE IS A LIST OF DEFERRED SUBMITTALS AND |
| | SEPARATE PERMITS ON SHEET ALS.0.1) FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 34) NOT RESOLVED. [SOUND INSULATION IS REQUIRED FOR |
| | HARD FLOORING MATERIALS SUCH AS TILE, LAMINATE, WOOD, |
| | ETC. ADD NOTE TO PLANS. IF YOU WISH TO SUBMIT THE TEST |
| | REPORTS LATER, ADD TO THE LIST OF DEFERRED ITEMS. SHOW |
| | COMPLIANCE WITH FBC SECTION 1207 SOUND TRANSMISSION, |
| | 1207.2 AIR-BORNE SOUND AND 1207.3 STRUCTURE-BORNE |
| | SOUND. TEST REPORTS WILL NEED TO BE SUBMITTED FOR THE |
| | SOUND INSULATION THAT WILL BE INSTALLED UNDER FINISH |
| | FLOORING. |
| | |
| | 35) NOT RESLOVED. [AREA TABULATIONS TO BE PROVIDED BY |
| | THE DESIGNER.] IN ORDER TO VERIFY THE BUILDING |
| | VALUATION, PLEASE PROVIDE AREA TABULATIONS FOR THE |
| | ENTIRE BUILDING. PLEASE SEPARATE AREA TABULATIONS BY |
| | OCCUPANCY TYPE. FBC 109.3 BUILDING PERMIT VALUATION. |
| | FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN |
| | FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST |
| | ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS |
| | PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL |
| | BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 36) NOT RESOLVED. SEPARATE PERMITS, REVIEWS AND FEES |
| | ARE REQUIRED FOR SOME ITEMS THAT MAY HAVE BEEN INCLUDED |
| | IN THE VALUE FOR THIS PROJECT. ITEMS SUCH AS FIRE |
| | ALARM, FIRE SPRINKLER, LOW VOLTAGE, LANDSCAPING, |
| | IRRIGATION AND ALL ITEMS OTHER THAN BUILDING, |
| | MECHANICAL, ELECTRIC AND PLUMBING. PLEASE PROVIDE A |
| | COST BREAKDOWN SO THAT WE CAN DEDUCT THESE ITEMS FROM |
| | THE PERMIT VALUE SO THAT YOU WILL NOT BE CHARGED TWICE |
| | FOR THE SAME ITEM. |
| | |
| | 37) RESOLVED. [WILL REMAIN AS ONE PARCEL WITH TWO |
| | BUILDINGS. APPROVAL LETTER FROM ZONING TO BE |
| | SUBMITTED.] THE P.B.C. PROPERTY APPRAISER SHOWS THIS |
| | PROJECT IS LOCATED ON A LARGER PARCEL THAN THE SITE |
| | PLAN AND SURVEY THAT WAS SUBMITTED. IS THIS PARCEL |
| | BEING SUBDIVIDED OR TO REMAIN AS ONE PARCEL WITH TWO |
| | BUILDINGS ON IT? PLEASE CLARIFY. |
| | |
| | 38) NOT RESOLVED. THE ADDRESS OF THE PROJECT HAS BEEN |
| | CHANGED TO 345 BANYAN BLVD. PLEASE CHANGE THE ADDRESS |
| | IN THE TITLE BLOCK OF THE PLANS. THE DESCRIPTION OF THE |
| | PROJECT AS PARKING LOT REDEVELOPEMENT IN THE TITLE |
| | BLOCK IS NOT SPECIFIC. A MORE ACCURATE DISCRIPTION |
| | WOULD BE A NEW RESIDENTIAL HIGH RISE BUILDING AND |
| | PARKING GARAGE. FBC 107.2.1 |
| | |
| | 39) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | NEW COMMENTS: |
| | |
| | 40) THE ACCESSIBLE ROUTE FROM THE PARKING GARAGE TO |
| | CORRIDOR 186 APPEARS TO GO THROUGH A WALL. SEE SHEETS |
| | 057-ALS1.1, 070 - A1.1.2B AND 066 - A1.1.1. PLEASE |
| | CLARIFY. FBC 107.2.1 |
| | |
| | 41) SHOW ACCESS TO THE ELEVATOR MACHINERY THAT WILL BE |
| | LOCATED ON TOP OF ELEVATORS 2 AND 3. 3005.1 ACCESS. AN |
| | APPROVED MEANS OF ACCESS SHALL BE PROVIDED TO ELEVATOR |
| | MACHINE ROOMS, CONTROL ROOMS, CONTROL SPACES AND |
| | MACHINERY SPACES. |
| | |
| | ****PROVISOS**** |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO |
| | INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH |
| | PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND |
| | ENGINEERING (IF APPLICABLE). |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | |
| | DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE |
| | FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS |
| | SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR |
| | PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS, |
| | STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS |
| | REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW |
| | AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION. |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH |
| | PRESSURES SHOWN ON SHEET S0.0.5) |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5 |
| | PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, |
| | INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS |
| | COMPLY WITH MINIMUM DESIGN PRESSURES. |
| | |
| | SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | PARKING LOT |
| | SWIMMING POOLS |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR |
| | TO C.O. |
| | |
| | SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED |
| | TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS |
| | TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE |
| | POUR. |
| | |
| | A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED |
| | TO BE PROVIDED PRIOR TO INSTALLATION. |
| | |
| | CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |