| Date |
Text |
| 2020-12-12 07:57:05 | 1) SHT. 5 OF 16 REFERS TO 45,800 CUBIC FOOT TANK |
| | STORAGE CHAMBERS. SUBMIT A DETAIL OF THIS STORAGE |
| | ARRANGEMENT, IT'S PURPOSE AND ANY/ ALL ASSOCIATED |
| | PIPING, PUMPS AND/OR ANY OTHER DETAILS ASSOCIATED WITH |
| | THIS SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHEETS ALS 0.1, ALS 0.2, ALS 0..3, ALS 0.4, ALS 0.5 |
| | - THERE ARE REFERENCES IN THE NOTES ON THE FAIR HOUSING |
| | DETAILS AND ALSO IN THE DETAIL TITLES TO 6 DIFFERENT |
| | FAIR HOUSING DESIGN STANDARDS AND AT THIS POINT I HAVE |
| | NO IDEA AS TO WHAT DESIGN STANDARD YOU ARE USING AS A |
| | SAFE HARBOR FOR COMPLIANCE WITH THE FAIR HOUSING ACT. |
| | THERE IS ALSO A REFERENCE TO THE NORTH CAROLINA |
| | BUILDING CODE.THEREFORE, A THOROUGH AND COMPREHENSIVE |
| | REVIEW COULD NOT BE DONE FOR COMPLIANCE WITH FAIR |
| | HOUSING REQUIREMENTS. ONE DESIGN STANDARD ONLY MUST BE |
| | CHOSEN FOR COMPLIANCE WITH FAIR HOUSING REQUIREMENTS. |
| | REVISE ALL THE AFFECTED NOTES AND DETAIL TITLES ON THE |
| | FAIR HOUSING DETAIL SHEETS TO REFLECT THE CORRECT |
| | DESIGN STANDARD TO BE USED FOR COMPLIANCE. WPB AMEND. |
| | TO FBC SEC. 107..2.1. |
| | 3) HUD RECOGNIZES TEN SAFE HARBORS FOR COMPLIANCE WITH |
| | THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION |
| | REQUIREMENTS. THE ICC/ANSI A117.1 - 2009 IS NOT LISTED |
| | AS A SAFE HARBOR. HUD SAID IN THE INTRODUCTION TO THE |
| | ACCESSIBILITY GUIDELINES, "BUILDERS AND DEVELOPERS MAY |
| | CHOOSE TO DEPART FROM THESE GUIDELINES AND SEEK |
| | ALTERNATE WAYS TO DEMONSTRATE THAT THEY HAVE MET THE |
| | REQUIREMENTS OF THE FAIR HOUSING ACT." THE STANDARD |
| | EMPLOYED MUST MEET ALL OF THE DESIGN AND CONSTRUCTION |
| | REQUIREMENTS SPECIFIED IN THE FAIR HOUSING ACT AND |
| | HUD'S FAIR HOUSING ACT REGULATIONS, AND PROVIDE THE |
| | SAME OR A STRICTER DEGREE OF ACCESSIBILITY THAN THE |
| | RECOGNIZED SAFE HARBORS. FAIR HOUSING ACT DESIGN |
| | MANUAL, PAGE 13. PREAMBLE TO THE GUIDELINES, 56 FR |
| | 9478-79, MARCH 6, 1991. THE PURPOSE OF THE FAIR HOUSING |
| | ACT GUIDELINES IS "TO DESCRIBE THE MINIMUM STANDARDS OF |
| | COMPLIANCE WITH THE SPECIFIC ACCESSIBILITY REQUIREMENTS |
| | OF THE ACT." PREAMBLE TO THE GUIDELINES, 56 FR 9472, |
| | 9476, MARCH 6, 1991. VERIFICATION MUST BE PROVIDED THAT |
| | THE 2009 EDITION OF THE ANSI A117.1 PROVIDES THE SAME |
| | OR A STRICTER DEGREE OF ACCESSIBILITY THE RECOGNIZED |
| | SAFE HARBORS. |
| | 4) SHEET ALS 0.1 - ITEMS UNDER SEPARATE PERMIT - |
| | INCLUDE GREASE INTERCEPTOR, GAS, BACKFLOW DEVICES, AND |
| | IRRIGATION SYSTEMS. |
| | 5) SHT.ALS 0.2 - FHA NOTES - COMMON USE FACILITIES - |
| | THE NOTE REFERS TO THE ANSI A117.1 - 1988 STANDARD. I |
| | AM NOT AWARE OF AN 1988 ANSI A117.1 STANDARD. CLARIFY |
| | AND REVISE THE NOTE TO REFLECT THE DESIGN STANDARD |
| | BEING USED FOR THIS PROJECT. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 6) SHT. ALS 0.2 - DRINKING FOUNTAIN DETAILS - THE |
| | DETAIL TITLE REFERS TO THE ANSI 2009 EDITION BUT NOTE |
| | #1 REFERS TO THE FLORIDA BUILDING CODE. THE COMMON |
| | AREAS SHALL COMPLY WITH THE APPLICABLE STANDARD USED |
| | FOR FAIR HOUSING DESIGN COMPLIANCE. THE FLORIDA UILDING |
| | CODE DOES NOT APPLY TO THE COMMON AREAS OF THE |
| | BUILDING. THE FLORIDA BUILDING CODE WOULD APPLY TO ANY |
| | RETAIL OR TENANT SPACES THAT DO NOT FALL UNDER FAIR |
| | HOUSING REQUIREMENTS.THE SAME APPLIES TO THE URINAL |
| | DETAIL.REVISE THE NOTES. |
| | 7) SHT. ALS 0.2 - ROLL- IN SHOWER DETAIL - THE DETAIL |
| | SHOWS A SEAT IN THE SHOWER. IF A SEAT IS INSTALLED, HOW |
| | WILL A PERSON ON THE SEAT BE ABLE TO REACH AND USE THE |
| | CONTROLS? CLARIFY. |
| | 8) THE FAIR HOUSING DETAIL SHEETS HAVE NOTES REFERRING |
| | TO TYPE "A" AND TYPE "B" PLUMBING FIXTURES AND LAUNDRY |
| | EQUIPMENT. IF THE INTENT IS TO USE THE 2009 ICC/ANSI |
| | A117.1 STANDARD AS THE BASIS FOR FAIR HOUSING ACT |
| | COMPLIANCE, THEN SPECIFY THE TYPE OF UNIT ("A" UNIT OR |
| | "B" UNIT ) AND ALSO THE OPTION ( OPTION "A" OR "B" ) |
| | BEING USED FROM CHAPTER 10 OF THE 2009 STANDARD. |
| | 9) SHT. ALS 0.2 - WATER CLOSET COMPARTMENT-PUBLIC - |
| | NOTE #4 - DOOR PULLS SHALL BE LOCATED 34 INCHES MINIMUM |
| | AND 48 INCHES MAXIMUM ABOVE THE FLOOR. ANSI A117.1 |
| | SEC.404.2.6, 604.9.3. |
| | 10) SHT. ALS 0.3 - ACCESSIBLE WATER CLOSETS DETAIL - |
| | SECTION 1003.11.2.4.4 OF THE NOTED ANSI STANDARD |
| | REQUIRES THE CLEARANCE AT THE WATER CLOSET TO BE 66 |
| | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL WHEN A LAVATORY IS LOCATED NEXT TO THE WATER |
| | CLOSET FOR TYPE "A" ACCESSIBLE WATER CLOSETS. THE DEPTH |
| | OF THE LAVATORY SHALL BE A MAXIMUM OF 24 INCHES. |
| | 11) FHA COMPLIANT WATER CLOSETS DETAILS - SHOW THE |
| | LENGTH OF ALL THE REINFORCEMENT FOR THE GRAB BARS. |
| | ALSO, SHOW THE HEIGHT OF THE REINFORCEMENT FROM THE |
| | FLOOR TO THE BOTTOM OF THE REINFORCEMENT. |
| | 12) SHOW THE CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER |
| | CLOSETS ON ALL THE WATER CLOSET DETAILS ON THE FHA |
| | DRAWINGS. COMPLY WITH THE REQUIREMENTS FROM THE DESIGN |
| | STANDARD BEING USED.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 13) SHT. ALS 0.3 - ACCESSIBLE BATHTUBS W/O PERMANENT |
| | SEATS - NOTE #1 REFERS TO SEC.1003.11.2.5.1 OF THE ANSI |
| | STANDARD WHICH REFERS TO SEC. 607 WHICH REQUIRES THE 30 |
| | INCH WIDE CLEAR FLOOR SPACE TO EXTEND THE LENGTH OF THE |
| | BATHTUB BUT THE DETAIL SHOWS THE LENGTH AS 48 |
| | INCHES.THIS ALSO OCCURS ON SHT. ALS 0.5. CLARIFY. |
| | 14) SHTS. A1.1.1A & A 9.50.1 - TOILET ROOM #104 - THE |
| | DOOR IS SWINGING INTO THE CLEAR FLOOR SPACE FOR THE |
| | LAVATORY.COMPLY WITH ANSI A117.1 SEC. 603.2.2. |
| | 15) SHTS. A1.2.1 & A 9.51.1 - TOILET ROOM #M02 - THE |
| | DOOR IS SWINGING INTO THE CLEAR FLOOR SPACE FOR THE |
| | LAVATORY.COMPLY WITH ANSI A117.1 SEC. 603.2.2. |
| | 16) 5TH FLOOR PLANS - AMENITY & POOL DECK - TOILET |
| | ROOMS #517 & #521 - TOILET COMPARTMENT DOORS SHALL NOT |
| | SWING INTO THE REQUIRED MINIMUM AREA OF THE |
| | COMPARTMENT. SHOW COMPLIANCE WITH ANSI A117.1 |
| | SEC.604.9.3. SEE SHT. A9.52.1. |
| | 17) SHT. A1.6.1 - CLEARLY SHOW THE ACESSIBLE ROUTE FROM |
| | THE SWIMMING POOL AREA TO THE TOILET FACILITIES. ANSI |
| | A117.1 SEC. 401.1 |
| | 18) THE ENTRY DOORS OF ALL RESTROOMS SHALL BE LOCATED |
| | WITHIN A 200 - FOOT WALKING DISTANCE OF THE NEAREST |
| | WATER'S EDGE OF EACH POOL SERVED BY THE FACILITIES. |
| | 2017 FBC SEC.454.1.6.1. |
| | 19) SHTS. A1.8.1, A9.54.1, & A9.54.3 - TOILET ROOMS |
| | #1601 & #1602 - THE DOOR IS SWINGING INTO THE CLEAR |
| | FLOOR SPACE FOR THE LAVATORY.COMPLY WITH ANSI A117.1 |
| | SEC. 603.2.2. |
| | 20) THE INTERIOR ELEVATION DRAWINGS FOR THE DWELLING |
| | UNITS- DETAIL #1 SHOWS THE HEIGHT OF THE KITCHEN SINK |
| | CABINET AS 36 INCHES IN HEIGHT YET THE FHA DETAIL |
| | SHEETS SHOW THE SINK HEIGHT AS 34 INCHES. CLARIFY. |
| | 21) INDICATE ON THE FLOOR PLANS OF THE INDIVIDUAL |
| | DWELLING UNITS WHICH KITCHENS ARE TYPE "A" ACCESSIBLE |
| | KITCHENS AND WHICH ARE TYPE "B" ACCESSIBLE KITCHENS. |
| | WPB AMEND. TO FBC SEC.107.2.1. |
| | 22) SHT. A9.8.1 - UNIT 8 - SHOW THE CLEAR FLOOR SPACE |
| | FOR ALL THE FIXTURES PER ANSI A117.1. |
| | 23) SHT. A9.10.1 - UNIT 10 - DETAIL #2 - THE WATER |
| | CLOSET IS SHOWN AS 1 FOOT 11 INCHES (1'-11") FROM ITS |
| | CENTERLINE FROM THE EDGE OF THE LAVATORY AND THE |
| | WRAPPED EDGE OF THE COLUMN. THE WATER CLOSET SHALLL BE |
| | 16-18 INCHES TO ITS CENTERLINE PER ANSI A117.1 |
| | SEC.1003.11.2.4. |
| | 24) THE MAXIMUM DEPTH OF THE LAVATORIES SHALL BE 24 |
| | INCHES. THE PLANS SHOW SOME OF THE LAVATORIES AS 25 1/2 |
| | INCHES DEEP. INDICATE ON THE UNIT FLOOR PLANS THAT THE |
| | MAXIMUM DEPTH OF THE LAVATORIES IS 24 INCHES PER ANSI |
| | A117.1. |
| | 25) SHT. A9.16.1 - UNIT 16 - SHOWS THE WATER CLOSET IN |
| | THE MASTER BATH LOCATED 1 FOOT 10 INCHES (1'-10" ) FROM |
| | THE EDGE OF THE LAVATORY AND THE ADJACENT WALL TO THE |
| | CENTERLINE OF THE WATER CLOSET. THE WATER CLOSET SHALLL |
| | BE 16-18 INCHES TO ITS CENTERLINE PER ANSI A117.1 |
| | SEC.1004.11..3.2.2 |
| | 26) SHT. A9.17.1 - UNIT 17 - SHOWS THE WATER CLOSET IN |
| | THE MASTER BATH LOCATED 2 FEET 5 INCHES ( 2'- 5" ) FROM |
| | THE ADJACENT WALL TO THE CENTERLINE OF THE WATER |
| | CLOSET. THE WATER CLOSET SHALLL BE 16-18 INCHES TO ITS |
| | CENTERLINE PER ANSI A117.1 SEC.1004.11.3.2.2. |
| | 27) SHT. A9.20.1 - UNIT 20 - INDICATE ON THE PLAN THE |
| | UNIT TYPE BATHROOM AND OPTION TYPE ON THE PLAN PER ANSI |
| | A117.1. THE CENTERLINE OF THE WATER CLOSET FROM THE |
| | EDGE OF THE LAVATORY IS SHOWN AS 1 FOOT 9 INCHES (1'- |
| | 9" ). CLARIFY. |
| | 28) SHT. A9.52.3 - IDENTIFY THE WALL FINISH AROUND THE |
| | JANITOR SINK. COMPLY WITH FBC-BUILDING SEC.1210.2.2. |
| | 29) SHT. A9.52.4 - SHOW THE INSIDE CLEAR DIMENSIONS (L |
| | X W) FOR THE TOILET STALLS IN THE WOMEN'S RESTROOM. |
| | COMPLY WITH FBC-PLUMBING SEC. 405.3.1. |
| | 30) SHT. A9.54.1 - SHOW THE WIDTH DIMENSION BETWEEN THE |
| | SINK AND THE GRILL AND THE REQUIRED CLEAR FLOOR SPACES |
| | FOR EACH PER ANSI A117.1 SEC. 305. |
| | 31) SHT. A9.54.1 - SHOW THE WIDTH OF TOILET ROOM #1602 |
| | ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1, ANSI |
| | A117.1 SEC. 604. |
| | 32) SHEET P 0.3.0, ON THE TYPICAL KITCHEN, A SANITARY |
| | RISER WITH AN AIR ADMITTANCE VALVE IS RESTRICTED ON THE |
| | HIGH RISE DUE TO THE HYDRAULIC JUMP CAUSED IN A STACK |
| | THAT WITHSTANDS LIMITED POSITIVE PRESSURES. BECAUSE |
| | EXTREME PRESSURES MAY DAMAGE THE DEVICES, THE AIR |
| | ADMITTANCE VALVES MAY BE USED IN THE BUILDING'S TOP 4 |
| | STORIES. PLEASE REFER TO THE CODE SECTION, WHICH |
| | REQUIRES RELIEF VENTS PER THE 2017 FBC SEC. P 918.3.1. |
| | A) ON THE TYPICAL CONDENSATE LINE, THE FLOOR HAS A |
| | KEYNOTE SIX, WHICH REFERS TO AN AUTOMATIC AIR VENT |
| | TYPE. PLEASE GIVE DETAIL OF A STANDARD FOR THIS TYPE OF |
| | VALVE. THIS NOTED IT MIGHT NOT BE IN A CAVITY WALL AS |
| | THERE IS NO NEGATIVE OR POSITIVE PRESSURE. YOU MAY |
| | OFFSET IT IN AN A/C CLOSET, AND IT SHALL BE |
| | NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF |
| | NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT |
| | MORE THAN 50 PER THE 2017 FBC SEC M 602.2.1. |
| | 33) SHEET P 0.3.1, NOTE FIVE HAS THE LAST FEW WORDS ON |
| | TOP OF EACH OTHER. ON DETAIL ONE, PLEASE LABEL THE |
| | RE-VENT OF THE WASHING MACHINE. THE RE-VENT SIZE FROM |
| | SECOND TO THIRD LOOKS LIKE IT SHOULD BE 2" SO THE 3" |
| | SHOULD BE MOVED UP TO THE FOURTH FLOOR. DO THE SAME FOR |
| | THE 6TH FLOOR ON THE SECOND RISER PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 34) SHEET P 0.3.2, RISER ONE THE MOP SINK HAS ONLY ONE |
| | SHUT OFF VALVE ON THE COLD, BUT IT REQUIRES A SHUT OFF |
| | AT EACH ENTRY FOR HOT AND COLD ALONG WITH THE PRV; A |
| | VALVE MAY BE NEEDED ON THE HOT SIDE OF THE HEATER FOR |
| | SERVICE, PLEASE SHOW AND LABEL PER THE 2017 FBC SEC. P |
| | 606.1(2). |
| | 35) SHEET P 1.0.1, THE GRID NUMBERS AND LETTERS ARE ON |
| | TOP OF EACH OTHER IN SOME PLACES, AND PLEASE OFFSET OR |
| | MOVE AWAY FOR CLARITY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | THIS IS TYPICAL ON ALL PLUMBING PAGES, SO NOT TO REPEAT |
| | EVERY COMMENT; IT IS NOTED IN THIS ONE ONLY. |
| | A) THE FIRE ROOM HAS THREE-FLOOR DRAINS, THE TRASH ROOM |
| | HAS ONE, AND THE ELEVATOR HAS A FUNNEL DRAIN WITHOUT |
| | TRAP SEAL PROTECTION. PLEASE SHOW TRAP PRIMER AND GIVE |
| | DETAIL OR SPECIFICATION, ALSO WHERE THE SOURCE OF WATER |
| | IS COMING FROM IF APPLICABLE PER THE 2017 FBC SEC. |
| | 1002.4.1. IF AN APPROVED TRAP SEAL IS USED THAT |
| | CONFORMS TO ASSE 1044 IN SOME AREAS, THE AHJ MAY NOT |
| | APPROVE THE DUE TO DEBRIS. PLEASE PROVIDE DETAILS OF |
| | THE SANITARY ISOMETRIC ON P 9.0.4 FOR THESE DRAINS, |
| | CLOUDS, OR BOXES AND GIVE REFERENCE NUMBERS; THESE |
| | TRAPS IN THESE AREAS ARE MISSING VENT PER THE 2017 FBC |
| | SEC. 1002.1. |
| | 36) SHEET P 1.0.1B, PLEASE PROVIDE DETAIL OR SHOW HOW |
| | PIPES WILL BE PROTECTED FROM VEHICULAR TRAFFIC PER THE |
| | 2017 FBC SEC. P 305.7. THIS IS TYPICAL ON ALL PLUMBING |
| | PAGES, SO NOT TO REPEAT EVERY COMMENT; IT IS NOTED IN |
| | THIS ONE ONLY. |
| | A) GRIDLINE LETTERS ARE NOT SHOWN. PLEASE MOVE THE |
| | DRAWING OVER PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | B) IN THE MAINTENANCE ROOM AND THE DOG SPA, THEY BOTH |
| | HAVE A FLOOR DRAIN, AND BEHIND THE TWO ELEVATORS, IT |
| | HAS A FUNNEL DRAIN WITHOUT TRAP SEAL PROTECTION. PLEASE |
| | SHOW THE TRAP PRIMER AND GIVE DETAIL AND OR |
| | SPECIFICATION, ALSO WHERE THE SOURCE OF WATER IS COMING |
| | FROM IF APPLICABLE PER THE 2017 FBC SEC. 1002.4.1. IF |
| | AN APPROVED TRAP SEAL IS USED THAT CONFORMS TO ASSE |
| | 1044 IN SOME AREAS, THE AHJ MAY NOT APPROVE THE DUE TO |
| | DEBRIS. PLEASE PROVIDE DETAIL OF THE SANITARY ISOMETRIC |
| | ON P 9.0.4 FOR THESE DRAINS, CLOUDS, OR BOXES AND GIVE |
| | REFERENCE NUMBERS. |
| | C) THE STORAGE ROOM WITH THE LAUNDRY TRAY IS NOT |
| | LABELED NEXT TO THE ELEVATORS; PLEASE LABEL PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS |
| | D) THE TRAPS IN THESE AREAS ARE MISSING A VENT PER THE |
| | 2017 FBC SEC. 1002.1. |
| | 37) SHEET P 1.1.1A, THE BOOSTER PUMPS IN THE FIRE ROOM |
| | HAS NO BYPASS OR SHUT OFF VALVES FOR MAINTENANCE |
| | PURPOSES. PLEASE SHOW PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | A) TRASH ROOM HAS NO HOSE BIBB, AND IT IS STRONGLY |
| | SUGGESTED BUT NOT ENFORCED. THE TRASH SHOOT MAY HAVE A |
| | SANITIZER IN MOST CASES, BUT NO WATER IS SHOWN OR |
| | DETAILS FOR IT; IF APPLICABLE, PLEASE GIVE A POINT AND |
| | REFERENCE TO THE PAGE THAT WILL BE USED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 38) SHEET P 1.1.1B, THE MAINTENANCE ROOM, DOES NOT HAVE |
| | ANY DETAILS; PLEASE ADD A DETAIL P 9.0.2 SINCE THEY ARE |
| | NEXT TO EACH OTHER AND REFERENCE IT ON THIS PAGE. IT |
| | WILL NEED TO SHOW TRAP PRIMER, FLOOR DRAIN, AND VENT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 39) SHEET P 1.3.1A, THE MECHANICAL ROOM, AND BIKE ROOM |
| | ARE NOT LABELED; PLEASE LABEL PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | 40) SHEET P 1.4.1A, THE MECHANICAL ROOM REQUIRES A TRAP |
| | PRIMER AND WATER ALONG WITH A VENT: IF USING A TRAP |
| | PRIMER THAT INVOLVES WATER, PLEASE SHOW THE SOURCE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | 41) SHEET P 1.5.B, IN THE POOL AREA, THERE ARE MANY |
| | MISSING CIRCLES WHICH INDICATE THAT A PIPE IS GOING UP |
| | OR DOWN. PLEASE OVERLAY AND MATCH TO P 1.6.B; THERE ARE |
| | TOO MANY TO MENTION ON THIS PAGE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | 42) SHEET P 1.6.1A, PLEASE REFER TO GRID LINES |
| | B-B.5/2-2.3; THE 4" DD IS A DECK DRAIN AS A ROOF DRAIN |
| | ON TOP; PLEASE REMOVE FOR CLARITY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A) ON-GRID LINES 4.6-.5/A.1-B, THE PD IS NOT LABELED OR |
| | HAS SF SIZE FOR IT; PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | B) ON-GRID LINES 4-5/D-E THE BATHROOMS HAVE TOO MANY |
| | WATER LINES AND LABELS, MAKING IT HARD TO SEE OTHER |
| | DETAILS; PLEASE LIGHTEN THE OR REMOVE FOR CLARITY PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | 43) SHEET P 1.6.1B, PLEASE GIVE DETAILS OR PROVIDE THE |
| | SPECIFICATION FOR THE GAS SOLENOID VALVE PANIC SHUT OFF |
| | AND PRESSURE REDUCING VALVES, LABEL THEM TO WHERE THEY |
| | ARE REFERENCED AT, IF A PAGE OF DETAIL IS AVAILABLE FOR |
| | THEM, PLEASE NOTE ON KEYNOTE LEGEND PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A) PLEASE PROVIDE DETAILS FOR PLANT DRAINS AND PUT A |
| | REFERENCE ON KEYNOTE LEGEND PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | B) ON-GRID LINES 8-8.78 AND B-B.5, THERE IS A TRENCH |
| | DRAIN BUT LOOKS TO BE A PLANT DRAIN NEXT TO THE POOL, |
| | AND ON TOP, THERE IS ANOTHER PLANT DRAIN, AND IT HAS NO |
| | LABEL OR SIZE; PLEASE CLARIFY PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | C) ON-GRID LINES 8-8.78 AND D-D,8, THERE IS A 4" PLANT |
| | DRAIN LABELED -SF ON THE POOL DECK; DOES IT BELONG |
| | THERE, OR IS IT IN THE WRONG LOCATION? PLEASE CLARIFY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | D) ON-GRID LINES 7.2-8/D.8-F THERE IS A PLANT DRAIN |
| | SHOWN, BUT IT'S LABELED 4" DD (123). PLEASE CLARIFY PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | E) IN THE POOL EQUIPMENT ROOM, THERE IS A 4" FLOOR |
| | DRAIN THAT REQUIRES A VENT, PRIMER, SOURCE OF WATER, |
| | AND DETAIL WITH A REFERENCE NUMBER; ON THE FLOOR BELOW, |
| | IT SAYS 4" S UP ONLY. PLEASE CLARIFY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 44) SHEET P 1.7.1A, THE GRID LINES ON THE LEFT BOTTOM |
| | ARE OFF THE PLOTTED DRAWING AND OTHER OVERLAPPED (AS |
| | MENTION BEFORE, PLEASE CORRECT ALL OVERLAPS IN ALL |
| | PAGES); PLEASE MOVE OVER PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 45) SHEET P 1.8.1A, WHERE THE TWO RESTROOMS ARE, THE |
| | ROOM BEHIND THEM HAS NO LABEL; PLEASE LABEL ALL PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A)THERE IS NO LAYOUT SHOWING THE RD-1 AND HB-3; PLEASE |
| | PROVIDE A REFERENCE IF ON ANOTHER PAGE OR GENERATE ONE |
| | PLEASE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 46) SHEET P 1.8.1B, THERE IS AN AREA WHERE THE TRENCH |
| | DRAINS ARE, AND THEY ARE NOT LABELED. PLEASE LABEL PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | A) THERE IS NO LAYOUT SHOWING THE RD-1 AND TD-1; PLEASE |
| | PROVIDE ON PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 47) SHEET P 9.0.1, DETAIL 2 FOR THE FITNESS CENTER IT |
| | HAS A 6? PIPE COMING UP, NOT SIZED AND NOT LABELED OR |
| | WITH A REFERENCE POINT, ALSO SIZE THE HORIZONTAL 4? |
| | LINE GOING TO THE MEN'S ROOM, AND THE LADIES ROOM |
| | DOWNSTREAM HAS A FEW 3? AND 4? NOT SIZED AS WELL. |
| | PLEASE PROVIDE SIZES PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | A) ON THAT SAME DETAIL, THERE IS A 4" SANITARY LINE |
| | THAT HAS NO LABEL TO WHERE IT IS GOING. PLEASE CLARIFY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | B) PLEASE SHOW ALL TRAP PRIMERS ON THE FLOOR DRAINS PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | C) LAVATORIES ON ALL AP-3 NEED TO BE SHOWN HORIZONTALLY |
| | AS THEY SEEM TO BE IN AN S-TRAP POSITION. PLEASE CHANGE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | D) THERE ARE THREE 3" SANITARY PIPES GOING UP WITH NO |
| | DESTINATION VENT AS WELL, PLEASE LABEL PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | E) THERE ARE TWO FLOATING FITTING AND A PIPE WITH A |
| | 90-DEGREE ELBOW GOING DOWN AND A WYE AT THE END; IT |
| | DOESN?T HAVE A SIZE OR DESTINATION; PLEASE REMOVE AND |
| | OR GIVE A REFERENCE TO ITS USE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | F) ON DETAIL FOUR, PLEASE SHOW SHUTOFF VALVES FOR THE |
| | RECIRCULATING PUMP AT THE FITNESS ROOM AREA WITH AN |
| | ACCESS BOX ON BOTH SIDES OF THE RECIRCULATING PUMP FOR |
| | THE WATER HEATER, AND ALL FIXTURES PER THE 2017 FBC |
| | SEC. P 606.1. |
| | G) PLEASE SHOW AND LABEL THE HAMMER ARRESTOR FOR THE |
| | DRINKING FOUNTAIN AND ALL QUICK CLOSING VALVES PER THE |
| | 2017 FBC SEC. P 604.9. |
| | H) PLEASE SHOW AND LABEL CHECK VALVES ON THE |
| | RECIRCULATING SYSTEM PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | I) THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES |
| | MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE |
| | REFER TO THE 2017 FBC ENERGY CODE TABLE C404.5.1. |
| | J) ON DETAIL SIX, PLEASE SHOW A BYPASS FOR THE BOOSTER |
| | PUMPS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | K) ON DETAIL ONE, AP-9 IS LABELED AS A FLOOR DRAIN; |
| | PLEASE MARK AS MOP SINK AND HAVE A NOTE THAT |
| | SURROUNDING THE WALL SHALL BE NON-ABSORBENT SURFACE IN |
| | ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2. |
| | L) IN THAT SAME DETAIL, THE MOP SINK, AND DRINKING |
| | FOUNTAIN CANNOT DISCHARGE INTO A HORIZONTAL WET VENT |
| | PER THE 2017 FBC SEC. P 912.1. |
| | M) IN THAT SAME DETAIL, THE WATER CLOSET IS ON A |
| | SANITARY TEE ON ITS BACK; A WATER CLOSET BEND IS |
| | REQUIRED PER THE 2017 FBC SEC. P 420.4. |
| | 48) SHEET P 9.0.2, ON DETAIL 2/P 9.0.2, PLEASE SHOW |
| | LABELING ON THE SANITARY DOWN FROM WHERE IT'S COMING |
| | FROM AND WHERE IT IS GOING TO PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | A. ON DETAIL 4/P 9.0.2, PLEASE SHOW LABELING ON THE |
| | SANITARY DOWN FROM WHERE IT'S COMING FROM AND GOING TO |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | B. ON DETAIL 5/P 9.0.2, IT SHOWS TWO DOG SPAS, ARE |
| | THESE STAND-ALONE UNITS AND IF SO, PLEASE PROVIDE |
| | MANUFACTURES SPECIFICATION TO SEE IF THEY REQUIRE A |
| | BACKFLOW DEVICE. THE DOG SPA SHOWS A LAV THAT IS NOT |
| | LABELED, AND IT IS MISSING WATER, VALVES, AND SANITARY |
| | DRAINAGE TO IT; PLEASE GIVE DETAIL. PLEASE SHOW THE |
| | FLOOR DRAIN IN THE DOG SPA PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | C. ON DETAIL 6/P 9.0.2, THE ARMS FOR THE STACK BY THE |
| | TWO-FLOOR DRAINS HAVE THE ARMS IN AN S-TRAP, PLEASE |
| | SHOW IN A HORIZONTAL POSITION. THE FLOOR DRAIN IS |
| | MISSING A TRAP PRIMER ALONG WITH A SOURCE OF WATER TO |
| | PRIME. THERE IS A SECOND-FLOOR DRAIN IN THE ROOM NEXT |
| | TO IT AND NOT SHOWN, AND IT MAY NEED TO BE VENTED IN |
| | THIS SYSTEM. THE LAVATORY IS NOT SHOWN ON THE |
| | ISOMETRIC, AND PLEASE INCORPORATE IT IN THE SYSTEM OF |
| | THIS ISOMETRIC. PLEASE SHOW WHERE AND SIZE OF THE MAIN |
| | TRUNK LINE IS COMING AND HEADS TO PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | D. ON DETAIL 7/P 9.0.2, THE TOILET ROOM SHALL HAVE |
| | TEMPERED WATER. IT SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC |
| | SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | E. ON THAT SAME DETAIL, IT SHOWS A COFFEE STATION ON |
| | THE MEZZ NEXT TO THE TOILET ROOM; IS THIS A UNIT THAT |
| | REQUIRES WATER TO IT. IF SO, IT MUST BE EQUIPPED WITH |
| | AN INLINE VACUUM BREAKER THAT CONFORMS TO ASSE 1024 PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | F. ON DETAIL 8/P 9.0.2, PLEASE SHOW THE SHUT-OFF VALVE |
| | A LITTLE LARGER AND VALVES ON EACH FIXTURE; IF AN |
| | ACCESS BOX IS REQUIRED, PLEASE SHOW IT AS WELL PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | G. ON DETAILS 11 AND 12/P 9.0.2, PLEASE SHOW THE |
| | SHUT-OFF VALVES FOR THE WATER HEATER, DOG SPA, AND LAV. |
| | PLEASE SHOW A DRAIN PAN FOR THE WATER HEATER AND THE |
| | LOCATION WHERE IT WILL DISCHARGE PER THE 2017 FBC SEC. |
| | P 504.7.2. |
| | 49) SHEET P 9.0.3, IN DETAIL 1/P 9.0.3 AND 2/P 9.0.3, |
| | IN THE JANITOR'S ROOM THE MOP SINK IS LABELED AS FD-2, |
| | PLEASE CORRECT, PLEASE SHOW HOT AND COLD WATER LINE TO |
| | THE MOP SINK AND SHUT OFF VALVES PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | A) ON DETAIL 4/P 9.0.3, IT DOES NOT SHOW WHERE 4" |
| | SANITARY DOWN IS COMING FROM, AND THERE IS NO VENT |
| | TYING TO THE OUTSIDE AS IT IS LOOPED TO ITSELF; PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | B) ON DETAIL 5, 6, 7, AND 8/P 9.0.3, IT SHOWS A UNIT |
| | UNDER THE CABINET LABELED G-1, AND ON THE DESCRIPTION, |
| | IT IS CALLING A GRILLE; IS THIS A GREASE INTERCEPTOR. |
| | IF THIS IS A GREASE INTERCEPTOR, PLEASE PROVIDE THE |
| | FOLLOWING; |
| | PLEASE SHOW HOW YOU DETERMINE THE SIZE OF THE GREASE |
| | TRAP PRESUMING YOU ARE USING 14 LB. GREASE CAPACITY, |
| | (7) GALLONS PER MINUTE RATE FLOW; THIS UNIT SHALL BE |
| | SIZED IN ACCORDANCE WITH THE SIZING REQUIREMENTS PER |
| | THE 2017 FBC SEC P 1003.3.4 AND TABLE 1003.3.4.1. 10. |
| | PROVIDE CALCULATIONS USED IN THE SIZING OF A GREASE |
| | INTERCEPTOR, AND PLEASE PROVIDE MANUFACTURER |
| | SPECIFICATION PER THE WPB FBC 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A SEPARATE PERMIT IS REQUIRED FOR THE GREASE |
| | INTERCEPTOR PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | C) ON DETAIL 11/P 9.0.3, THE TOILET ROOM SHALL HAVE |
| | TEMPERED WATER. IT SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC |
| | SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | D) ON DETAIL 12/P 9.0.3, PLEASE PROVIDE A SHUT-OFF |
| | VALVE FOR EACH FIXTURE AND THE TOILET ROOM AND DRINKING |
| | FOUNTAIN AREA. PLEASE PROVIDE A HAMMER ARRESTOR FOR THE |
| | ELECTRIC WATER COOLER PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | E) ON DETAIL 1/P 9.0.3, FOR THE MOP SINK, THE |
| | SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN |
| | ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2 AND |
| | 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS |
| | SHEET. |
| | 50) SHEET P 9.0.4, ON DETAIL P 9.0.4 IS LABELED AS AN |
| | FD-2, AND IT SHOULD BE A MOP SINK; PLEASE LABEL |
| | ACCORDINGLY FOR CLARITY IN THE FIELD PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A) ON DETAIL 2/P 9.0.4, PLEASE SHOW REFERENCE, WHERE |
| | THE 4" SANITARY IS COMING FROM AND, WHERE THE VENT IS |
| | CONNECTING TO, ALSO SHOW WHERE THE 3? SANITARY IS GOING |
| | TO. PLEASE SIZE THAT SAME RISER GOING UP PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | B) ON DETAIL 3/P 9.0.4, FOR THE MOP SINK, THE |
| | SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN |
| | ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2 AND |
| | 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS |
| | SHEET. |
| | C) ON DETAIL 5/P 9.0.4, IT SHOWS A COFFEE STATION ON |
| | THE GROUND FLOOR; IS THIS A UNIT THAT REQUIRES WATER TO |
| | IT. IF SO, IT MUST BE EQUIPPED WITH AN INLINE VACUUM |
| | BREAKER THAT CONFORMS TO ASSE 1024 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | D) ON DETAIL 6/P 9.0.4, PLEASE SHOW A TEMPERING DEVICE |
| | FOR THE ACCESSIBLE LAV THAT COMPLIES WITH ASSE 1070 OR |
| | GIVES DETAIL ON ANOTHER PAGE AND REFERENCES THAT DETAIL |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | E) ON DETAIL 7/P 9.0.4, PLEASE PROVIDE A SHUT-OFF VALVE |
| | FOR EACH FIXTURE AND THE MANAGER'S AREA. PLEASE PROVIDE |
| | A HAMMER ARRESTOR FOR THE ELECTRIC WATER COOLER PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | F.)ON DETAIL 9/P 9.0.4, PLEASE PROVIDE SHUT-OFF VALVES |
| | TO THE MOP SINK, SIZE, AND LABEL THEM PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | G) ON THE SAME DETAIL ABOVE, IT HAS A DOG SPA; IS THIS |
| | A MANUFACTURED UNIT? WHICH MAY REQUIRE A VACUUM BREAKER |
| | OR BACKFLOW DEVICE. PLEASE CLARIFY AND ADD MORE |
| | INFORMATION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 51) SHEET P 9.0.5, THE DRAWING HAS MISSING DECK DRAINS, |
| | AND EXTRA ROOF DRAINS, RISERS ARE CONNECTING TO DRAINS |
| | THAT ARE MISSING FITTINGS, TOO MANY TO CALL OUT PLEASE |
| | GO BACK AND REFER TO THE FLAT DRAWING AND MAKE |
| | CORRECTIONS FOR CLARITY PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 52) SHEET P 9.0.6, PLEASE SIZE BOTH, CLEAN-OUTS AND |
| | LABEL THE ONE OUTSIDE AND DELETE TWO FLOATING FITTINGS |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 53) SHEET P 9.0.7, THE DP-8 AND DP-9 SIZES ARE NOT |
| | LABELED, CD-1 AND CD-2 SIZES ARE NOT LABELED, AND THE |
| | THREE 1? CONDENSATE TIED TOGETHER IS GOING DOWN THAT IS |
| | MISSING WHERE IT?S GOING TO AND SIZE. PLEASE CORRECT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 54) SHEET P 9.0.8, CONDENSATE NUMBER 16, HAS NO LABEL |
| | AS TO WHERE IT IS GOING; PLEASE PROVIDE INFORMATION |
| | LIKE OTHER STACKS PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | A) PLEASE LABEL ALL CLEAN-OUTS, IT SHOWS CLEAN-OUTS AT |
| | ALL BASE OF STACKS IN THE DETAILS ON 2/P 0.3.0, BUT |
| | NONE IS SHOWN ON THIS PAGE; PLEASE ADD TO COINCIDE WITH |
| | BOTH DRAWINGS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | B) THERE ARE THREE FITTING FLOATINGS IN THIS DRAWING ( |
| | TWO DRAINS AND ONE COMBO); PLEASE REMOVE THEM TO |
| | PREVENT CONFUSION PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | C) PAN DRAINS ARE TERMINATING IS IN THE PARKING DECK, |
| | AND THEY MUST GO TO THE EXTERIOR OF THE BUILDING TO |
| | COMPLY WITH THE 2017 FBC SEC. P 507.7.2. |
| | 55) SHEET P 9.0.9, PLEASE REFER TO P 1.6.1 FOR OVERLAYS |
| | AND CORRECTIONS OF ALL THE ROOF, TRENCH, AND PLANT |
| | DRAINS TO COINCIDE WITH EACH OTHER PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 56) SHEET P 9.0.12, PLEASE LABEL CHECK VALVES AND |
| | SHUTOFF VALVES FOR BOTH ELEVATOR PUMPS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A) PLEASE SHOW TRAP PRIMERS, SOURCE OF WATER, AND VENT |
| | ALL FLOOR DRAINS PROPERLY, TYPES 1 AND 2 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | B) THE STACK BY THE TWO-FLOOR DRAINS THAT HAVE THE ARMS |
| | IN AN S-TRAP, PLEASE SHOW IN A HORIZONTAL POSITION PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | C) ALL THE PIPES GOING UP, SANITARY AND VENTS, PLEASE |
| | GIVE A REFERENCE POINT OF CONNECTION AND PLEASE LABEL |
| | AND SIZE THE CLEAN-OUT UPSTREAM OF THE 8" BY 6" WYE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | D) THE THREE FD-1 NEXT TO STACK S/R-9 ARE NOT LABELED; |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 57) SHEET P 9.0.13, IN DETAIL THREE, LEFT-RIGHT CORNER, |
| | 1/P 0.3.0 (22 DFU) SHOULD BE 4", AND THE P 0.3.1 (66 |
| | DFU) THEY ARE CROSSED, PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A) IN DETAIL FIVE IN THE LOWER-LEFT CORNER, AS NOTED ON |
| | COMMENT 17 LETTER B, I, M, AND N. PLEASE FIX TO MATCH P |
| | 9.0.1 ON THE ISOMETRIC, PLEASE SIZE RIGHT SIDE ON |
| | DOUBLE 6? WYE AND UPSTREAM OF THAT IS 4/P 0.3.0 (4 DFU) |
| | THAT IS MISSING A PIPE SIZE AND ALL OTHER BRANCHES IN |
| | BOTH BATHROOM GROUPS ARE MISSING SIZES, PLEASE SIZE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | B) IN DETAIL SIX, THE MIDDLE BOTTOM TWO 1/P 0.3.0 (60 |
| | DFU) AND 4/ P 0..3.0 (20 DFU) ARE MISSING SIZES. THERE |
| | IS A 2" SANITARY THAT IS NOT LABELED TO WHERE IT IS |
| | GOING. PLEASE LABEL PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | C) IN DETAIL SEVEN, THE RIGHT BOTTOM CORNER, 2/P 0.3.0 |
| | IS REFERENCED AS A SANITARY BUT IS A DETAIL FOR |
| | CONDENSATE; PLEASE CORRECT PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | 58) SHEET P 9.0.14, IN DETAIL TEN IN THE LEFT CORNER, |
| | THE 4" S (84) DFU HAS NO LABEL FOR A RISER. PLEASE |
| | LABEL PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | A) IN DETAIL ELEVEN, THE RIGHT BOTTOM CORNER 1/P 0.3.0 |
| | (84 DFU) HAS NO SIZE ON THE HORIZONTAL PIPE. PLEASE |
| | SIZE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | B) IN DETAIL NINE, THE TOP RIGHT CORNER 4/P 0.3.0 (28 |
| | DFU) IS SIZED AS 4" BUT NEEDS TO BE 3" ALSO, IN THE |
| | SAME RUN DOWNSTREAM SIZE, THE 6" SANITARY IS MISSING; |
| | DOWNSTREAM FROM THE WYE, THERE IS 1/P 0.3.0 (84) THAT |
| | IS MISSING A SIZE. ON THE OTHER SIDE OF THAT BRANCH, |
| | TWO 1/P 0.3.0 (84 DFU) ARE MISSING THEIR SIZES, AND |
| | UPSTREAM OF THAT, 1/P0.3.1 IS MISSING A SIZE AS WELL. |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | C) IN DETAIL EIGHT, THE LEFT TOP CORNER OF THE LAST |
| | RISER IS MISSING THE SIZE AND DFU, AND THE 1/P 0.3.0 IS |
| | NOT POINTING TO IT. PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 59) SHEET P 9.0.15, PLEASE SHOW BYPASS AND SHUTOFF |
| | VALVES ON BOOSTER PUMPS, PLEASE LABEL ALL SHUT OFF |
| | VALVED AND ACCESS PANELS, 6? WATER MAIN, PLEASE LABEL |
| | WHERE IT'S COMING FROM, PLEASE LABEL ALL WATER GOING UP |
| | TO WHERE IT CONTINUES PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 60) SHEET P 9.0.16, PLEASE LABEL ALL SHUT OFF VALVED |
| | AND ACCESS PANELS; PLEASE SHOW A SHUTOFF VALVE FOR ALL |
| | HB-3 ON THE ROOF; AP-5 HAS NO REFERENCE POINT TO WHAT |
| | IT SERVES. PLEASE LABEL REFERENCES TO WHERE WATER LINES |
| | COME FROM AND GO PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 61) SHEET P 9.0.18, IN THE FIRST AREA DRAIN NEXT TO THE |
| | TRENCH DRAIN, AN AD-1 IS NOT LABELED OR SIZED PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 62) SHEET P 9.1.2, IN DETAIL TWO, 3/4" H & C LINES FROM |
| | WATER HEATER NOT SIZED OR LABELED AND 1/2" H & C TO THE |
| | TUB'S LINES ARE NOT LABELED, PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A) IN DETAIL TWO, THE DISTANCE FROM THE STACK TO THE |
| | SHOWER SHALL NOT EXCEED 8 FEET PER THE 2017 FBC SEC. |
| | TABLE P 909.1 |
| | 63) SHEET P 9.1.3, IN DETAIL TWO, 3/4" H & C LINES FROM |
| | WATER HEATER NOT SIZED OR LABELED, 1/2" H & C TO THE |
| | LINES TO THE TUB, WATER CLOSET, LAVE AND SHOWER NOT |
| | SIZED AND LABELED THE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 64) SHEET P 9.1.4, IN DETAIL ONE, H & C WATER LINES |
| | COMING OUT OF THE HEATER NOT SIZED OR LABELED / ALSO IN |
| | DETAIL THREE, 1/2" H & C LINES TO THE WASHING MACHINE |
| | AND THE KITCHEN NOT SIZED OR LABELED PER THE PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 65) SHEET P 9.1.5, IN DETAIL THREE, 1/2" H & C LINES TO |
| | THE SHOWER, C WATER CLOSET, AND H & C TO THE LAV NOT |
| | SIZED OR LABELED PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 66) SHEET P 9.1.6, IN DETAIL TWO, 3/4" HOT ON WATER |
| | HEATER NOT SIZED OR LABELED, IN DETAIL FOUR, 1/2" H & C |
| | TO THE LINES TO THE KITCHEN AND FRIG NOT SIZED OR |
| | LABELED PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 67) SHEET P 9.1.7, IN DETAIL ONE, 3/4" H & C LINES FROM |
| | WATER HEATER NOT SIZED OR LABELED, IN DETAIL TWO 1/2" H |
| | & C TO THE LAV NOT SIZED OR LABELED PER THE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 68) SHEET P 9.1.8, 1/2" H & C TO THE TUB LINES ON TUB |
| | AND WATER CLOSET NOT SIZED OR LABELED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A) THE LAVATORY ARM SHOWS A HORIZONTAL SANITARY TEE ON |
| | A DOUBLE LAVATORY WHICH IS NOT PERMITTED PER THE 2017 |
| | FBC TABLE P 706.3. |
| | 69) SHEET P 9.1.9, 1/2" H & C TO THE WASHING MACHINE, |
| | FRIG, LAV, AND WATER CLOSET ARE NOT SIZED OR LABELED |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 70) SHEET P 9.1.10, 3/4" HOT COMING OUT THE WATER |
| | HEATER NOT LABELED OR SIZED, 1/2" H & C LINES NOT |
| | LABELED OR SIZE ON THE WATER TO THE FRIG AND THE TWO |
| | WATER CLOSET AND TUB PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 71) SHEET P 9.1.11, 1/2" H & C LAV NOT SIZED OR LABELED |
| | AND H & C TO THE KITCHEN NOT SIZED OR LABELED PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | A) DETAIL ONE SHOWS WATER CLOSET AND SHOWER NOT VENTED; |
| | TRAPS REQUIRE A SYSTEM OF VENTING SO THAT A PRESSURE |
| | DIFFERENTIAL OF NOT MORE THAN 1? FOR EACH PER THE 2017 |
| | FBC SEC. 901.2. |
| | 72) SHEET P 9.1.12, 1/2" H & C NOT LABELED OR SIZED TO |
| | BOTH LAVS AND WATER CLOSET PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | 73) SHEET P 9.1.13, 1/2" H & C NOT LABELED OR SIZED TO |
| | LAVS, TUB, AND WATER CLOSET AND 1/2" H & C NOT LABELED |
| | OR SIZED TO LAV AND WATER CLOSET THEN TO SHOWER PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | SWIMMING POOL |
| | 1) SUBMIT A COPY OF THE APPLICATION FOR THE OPERATING |
| | PERMIT STAMPED BY THE FLORIDA DEPARTMENT OF HEALTH PER |
| | FL. STATUTES 514.03, 553.79 (11). |
| | 2) SHT. P1.1 -THE PLAN SHOWS THE DISTANCE TO THE |
| | SANITARY FACILITIES AS 184 FEET THAT TRAVERSES A SET OF |
| | STAIRS. WHAT IS THE DISTANCE OF THE ACCESSIBLE ROUTE |
| | FROM THE NEAREST WATER'S EDGE TO THE ENTRY DOORS OF THE |
| | RESTROOMS? THIS MUST BE TTAKEN INTO CONSIDERATION. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| | SHOWER. THE POOL SHOWER SHALL COMPLY WITH THE |
| | REQUIREMENTS OF ANSI A117.1 FOR COMPLIANCE WITH FAIR |
| | HOUSING REQUIREMENTS. |
| | 4) SHT. P2.0 - THERE IS A NOTE UNDER THE FRICTION LOSS |
| | TABLE THAT REFERS TO THE BENDING OF PVC PIPING WITH |
| | HEAT. APPROVAL OF THIS PROCESS WILL BE BASED ON |
| | DOCUMENTATION FROM THE MANUFACTURER THAT SPECIFICALLY |
| | ALLOWS THIS PRROCESS. |
| | 5) FBC-BUILDING SEC.454.1.1.1 STATES THE FILTRATION |
| | SYSTEM SHALL BE CAPABLE OF PROVIDING A FLOW RATE OF AT |
| | LEAST .75 GPMM FOR EACH LIVING UNIT AT NONTRANSIENT |
| | FACILITIES WHICH WOULD BE 174.75 GPM BUT THE DESIGN |
| | FLOW RATE OR THIS POOL IS 170 GPM. CLARIFY. |
| | 6) FBC-BUILDING SEC. 454.1.6.1.2 - DOORS TO THE |
| | RESTROOMS SHALL BE WITHIN 50 FEET OF THE BUILDING'S |
| | EXTERIOR DOOR. INDICATE THIS ON THE SHT. P1.1. |
| | 7) SHOW THE SPACING OF THE WALL INLETS ON SHT. P2.0. |
| | COMPLY WITH FBC-BULDING SEC. 454.1.6.5.9.1. |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN |
| | DRAINS. THE MAIN DRAIN COVERS SHALL COMPLY WITH |
| | ANSI/APSP/ICC 7 - 2013 SEC.4.3.1.1. |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| | HEATER. THE POOL HEATER SHALL HAVE A MINIMUM THERMAL |
| | EFFICIENCY OF 82% PER 2017 FBC-ENERGY TABLE C404.2. |
| | 10) OUTDOOR HEATED SWIMMING POOLS SHALL BE EQUIPPED |
| | WITH A VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE |
| | OR A LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT |
| | LOSS. SHOW HOW THIS WILL BE ACHIEVEDFBC-ENERGY SEC. |
| | C404.9.3. |
| | 11) SHOW THE TEMINATION OF THE POOL WASTE LINE ON THE |
| | PLANS. THE WASTE LLINE SHALL NOT DISCHARGE TO THE STORM |
| | OR SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES ARTICLE III, SEC. 90-126 (B) (5) (SANITARY |
| | SEWERS), AND ARTICLE IV, SEC. 90-203 (A). CONTACT MANNY |
| | GONZALEZ IN THE CITY OF WEST PALM BEACH ENGINEERING |
| | DEPARTMENT AT 561-494-1040 FOR FURTHER INFORMATION. |
| | 12) SHT. P2.3 SHOWS A FLOOR DRAIN IN THE POOL EQUIPMENT |
| | ROOM DISCHARGING TO THE STORM SEWER. THIS FLOOR DRAIN |
| | SHALL DISCHARGE TO THE SANITARY SEWER AND WILL REQUIRE |
| | A NEUTRALIZATION TANK DUE TO THE CHEMICALS LLOCATED IN |
| | THIS ROOM PER FBC-PLUMBING SEC. 803.1,, |
| | 13) SHT. P2.3 - THERE IS A NOTE ON THE COLLECTOR TANK |
| | DETAIL THAT STATES" COLLLECTOR TANK PIT DRAINAGE BY |
| | G.C." SUBMIT DETAILS ON THIS DRAINAGE AND IT'S |
| | TERMINATION POINT OR PROVIDE THE PLAN SHEETS OF THIS |
| | PROJECT WHHERE THIS INORMATION CAN BE FOUND. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 14) SHT. P2.4 - POOL EQUIPMENT PLUMBING DIAGRAM - THERE |
| | IS AN ITEM LOCATED NEXT TO ITEM PH ON THE DIAGRAM THAT |
| | IS LABELED AS "PI". PI IS FOR THE COLLECTOR TANK. |
| | CORRECTLY IDENTIFY THIS ITEM. WPB AMENND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |