Plan Review Notes
Plan Review Notes For Permit 20101431
Permit Number 20101431
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-12 07:57:051) SHT. 5 OF 16 REFERS TO 45,800 CUBIC FOOT TANK
 STORAGE CHAMBERS. SUBMIT A DETAIL OF THIS STORAGE
 ARRANGEMENT, IT'S PURPOSE AND ANY/ ALL ASSOCIATED
 PIPING, PUMPS AND/OR ANY OTHER DETAILS ASSOCIATED WITH
 THIS SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHEETS ALS 0.1, ALS 0.2, ALS 0..3, ALS 0.4, ALS 0.5
 - THERE ARE REFERENCES IN THE NOTES ON THE FAIR HOUSING
 DETAILS AND ALSO IN THE DETAIL TITLES TO 6 DIFFERENT
 FAIR HOUSING DESIGN STANDARDS AND AT THIS POINT I HAVE
 NO IDEA AS TO WHAT DESIGN STANDARD YOU ARE USING AS A
 SAFE HARBOR FOR COMPLIANCE WITH THE FAIR HOUSING ACT.
 THERE IS ALSO A REFERENCE TO THE NORTH CAROLINA
 BUILDING CODE.THEREFORE, A THOROUGH AND COMPREHENSIVE
 REVIEW COULD NOT BE DONE FOR COMPLIANCE WITH FAIR
 HOUSING REQUIREMENTS. ONE DESIGN STANDARD ONLY MUST BE
 CHOSEN FOR COMPLIANCE WITH FAIR HOUSING REQUIREMENTS.
 REVISE ALL THE AFFECTED NOTES AND DETAIL TITLES ON THE
 FAIR HOUSING DETAIL SHEETS TO REFLECT THE CORRECT
 DESIGN STANDARD TO BE USED FOR COMPLIANCE. WPB AMEND.
 TO FBC SEC. 107..2.1.
 3) HUD RECOGNIZES TEN SAFE HARBORS FOR COMPLIANCE WITH
 THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS. THE ICC/ANSI A117.1 - 2009 IS NOT LISTED
 AS A SAFE HARBOR. HUD SAID IN THE INTRODUCTION TO THE
 ACCESSIBILITY GUIDELINES, "BUILDERS AND DEVELOPERS MAY
 CHOOSE TO DEPART FROM THESE GUIDELINES AND SEEK
 ALTERNATE WAYS TO DEMONSTRATE THAT THEY HAVE MET THE
 REQUIREMENTS OF THE FAIR HOUSING ACT." THE STANDARD
 EMPLOYED MUST MEET ALL OF THE DESIGN AND CONSTRUCTION
 REQUIREMENTS SPECIFIED IN THE FAIR HOUSING ACT AND
 HUD'S FAIR HOUSING ACT REGULATIONS, AND PROVIDE THE
 SAME OR A STRICTER DEGREE OF ACCESSIBILITY THAN THE
 RECOGNIZED SAFE HARBORS. FAIR HOUSING ACT DESIGN
 MANUAL, PAGE 13. PREAMBLE TO THE GUIDELINES, 56 FR
 9478-79, MARCH 6, 1991. THE PURPOSE OF THE FAIR HOUSING
 ACT GUIDELINES IS "TO DESCRIBE THE MINIMUM STANDARDS OF
 COMPLIANCE WITH THE SPECIFIC ACCESSIBILITY REQUIREMENTS
 OF THE ACT." PREAMBLE TO THE GUIDELINES, 56 FR 9472,
 9476, MARCH 6, 1991. VERIFICATION MUST BE PROVIDED THAT
 THE 2009 EDITION OF THE ANSI A117.1 PROVIDES THE SAME
 OR A STRICTER DEGREE OF ACCESSIBILITY THE RECOGNIZED
 SAFE HARBORS.
 4) SHEET ALS 0.1 - ITEMS UNDER SEPARATE PERMIT -
 INCLUDE GREASE INTERCEPTOR, GAS, BACKFLOW DEVICES, AND
 IRRIGATION SYSTEMS.
 5) SHT.ALS 0.2 - FHA NOTES - COMMON USE FACILITIES -
 THE NOTE REFERS TO THE ANSI A117.1 - 1988 STANDARD. I
 AM NOT AWARE OF AN 1988 ANSI A117.1 STANDARD. CLARIFY
 AND REVISE THE NOTE TO REFLECT THE DESIGN STANDARD
 BEING USED FOR THIS PROJECT. WPB AMEND. TO FBC SEC.
 107.2.1.
 6) SHT. ALS 0.2 - DRINKING FOUNTAIN DETAILS - THE
 DETAIL TITLE REFERS TO THE ANSI 2009 EDITION BUT NOTE
 #1 REFERS TO THE FLORIDA BUILDING CODE. THE COMMON
 AREAS SHALL COMPLY WITH THE APPLICABLE STANDARD USED
 FOR FAIR HOUSING DESIGN COMPLIANCE. THE FLORIDA UILDING
 CODE DOES NOT APPLY TO THE COMMON AREAS OF THE
 BUILDING. THE FLORIDA BUILDING CODE WOULD APPLY TO ANY
 RETAIL OR TENANT SPACES THAT DO NOT FALL UNDER FAIR
 HOUSING REQUIREMENTS.THE SAME APPLIES TO THE URINAL
 DETAIL.REVISE THE NOTES.
 7) SHT. ALS 0.2 - ROLL- IN SHOWER DETAIL - THE DETAIL
 SHOWS A SEAT IN THE SHOWER. IF A SEAT IS INSTALLED, HOW
 WILL A PERSON ON THE SEAT BE ABLE TO REACH AND USE THE
 CONTROLS? CLARIFY.
 8) THE FAIR HOUSING DETAIL SHEETS HAVE NOTES REFERRING
 TO TYPE "A" AND TYPE "B" PLUMBING FIXTURES AND LAUNDRY
 EQUIPMENT. IF THE INTENT IS TO USE THE 2009 ICC/ANSI
 A117.1 STANDARD AS THE BASIS FOR FAIR HOUSING ACT
 COMPLIANCE, THEN SPECIFY THE TYPE OF UNIT ("A" UNIT OR
 "B" UNIT ) AND ALSO THE OPTION ( OPTION "A" OR "B" )
 BEING USED FROM CHAPTER 10 OF THE 2009 STANDARD.
 9) SHT. ALS 0.2 - WATER CLOSET COMPARTMENT-PUBLIC -
 NOTE #4 - DOOR PULLS SHALL BE LOCATED 34 INCHES MINIMUM
 AND 48 INCHES MAXIMUM ABOVE THE FLOOR. ANSI A117.1
 SEC.404.2.6, 604.9.3.
 10) SHT. ALS 0.3 - ACCESSIBLE WATER CLOSETS DETAIL -
 SECTION 1003.11.2.4.4 OF THE NOTED ANSI STANDARD
 REQUIRES THE CLEARANCE AT THE WATER CLOSET TO BE 66
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL WHEN A LAVATORY IS LOCATED NEXT TO THE WATER
 CLOSET FOR TYPE "A" ACCESSIBLE WATER CLOSETS. THE DEPTH
 OF THE LAVATORY SHALL BE A MAXIMUM OF 24 INCHES.
 11) FHA COMPLIANT WATER CLOSETS DETAILS - SHOW THE
 LENGTH OF ALL THE REINFORCEMENT FOR THE GRAB BARS.
 ALSO, SHOW THE HEIGHT OF THE REINFORCEMENT FROM THE
 FLOOR TO THE BOTTOM OF THE REINFORCEMENT.
 12) SHOW THE CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER
 CLOSETS ON ALL THE WATER CLOSET DETAILS ON THE FHA
 DRAWINGS. COMPLY WITH THE REQUIREMENTS FROM THE DESIGN
 STANDARD BEING USED.WPB AMEND. TO FBC SEC. 107.2.1.
 13) SHT. ALS 0.3 - ACCESSIBLE BATHTUBS W/O PERMANENT
 SEATS - NOTE #1 REFERS TO SEC.1003.11.2.5.1 OF THE ANSI
 STANDARD WHICH REFERS TO SEC. 607 WHICH REQUIRES THE 30
 INCH WIDE CLEAR FLOOR SPACE TO EXTEND THE LENGTH OF THE
 BATHTUB BUT THE DETAIL SHOWS THE LENGTH AS 48
 INCHES.THIS ALSO OCCURS ON SHT. ALS 0.5. CLARIFY.
 14) SHTS. A1.1.1A & A 9.50.1 - TOILET ROOM #104 - THE
 DOOR IS SWINGING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY.COMPLY WITH ANSI A117.1 SEC. 603.2.2.
 15) SHTS. A1.2.1 & A 9.51.1 - TOILET ROOM #M02 - THE
 DOOR IS SWINGING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY.COMPLY WITH ANSI A117.1 SEC. 603.2.2.
 16) 5TH FLOOR PLANS - AMENITY & POOL DECK - TOILET
 ROOMS #517 & #521 - TOILET COMPARTMENT DOORS SHALL NOT
 SWING INTO THE REQUIRED MINIMUM AREA OF THE
 COMPARTMENT. SHOW COMPLIANCE WITH ANSI A117.1
 SEC.604.9.3. SEE SHT. A9.52.1.
 17) SHT. A1.6.1 - CLEARLY SHOW THE ACESSIBLE ROUTE FROM
 THE SWIMMING POOL AREA TO THE TOILET FACILITIES. ANSI
 A117.1 SEC. 401.1
 18) THE ENTRY DOORS OF ALL RESTROOMS SHALL BE LOCATED
 WITHIN A 200 - FOOT WALKING DISTANCE OF THE NEAREST
 WATER'S EDGE OF EACH POOL SERVED BY THE FACILITIES.
 2017 FBC SEC.454.1.6.1.
 19) SHTS. A1.8.1, A9.54.1, & A9.54.3 - TOILET ROOMS
 #1601 & #1602 - THE DOOR IS SWINGING INTO THE CLEAR
 FLOOR SPACE FOR THE LAVATORY.COMPLY WITH ANSI A117.1
 SEC. 603.2.2.
 20) THE INTERIOR ELEVATION DRAWINGS FOR THE DWELLING
 UNITS- DETAIL #1 SHOWS THE HEIGHT OF THE KITCHEN SINK
 CABINET AS 36 INCHES IN HEIGHT YET THE FHA DETAIL
 SHEETS SHOW THE SINK HEIGHT AS 34 INCHES. CLARIFY.
 21) INDICATE ON THE FLOOR PLANS OF THE INDIVIDUAL
 DWELLING UNITS WHICH KITCHENS ARE TYPE "A" ACCESSIBLE
 KITCHENS AND WHICH ARE TYPE "B" ACCESSIBLE KITCHENS.
 WPB AMEND. TO FBC SEC.107.2.1.
 22) SHT. A9.8.1 - UNIT 8 - SHOW THE CLEAR FLOOR SPACE
 FOR ALL THE FIXTURES PER ANSI A117.1.
 23) SHT. A9.10.1 - UNIT 10 - DETAIL #2 - THE WATER
 CLOSET IS SHOWN AS 1 FOOT 11 INCHES (1'-11") FROM ITS
 CENTERLINE FROM THE EDGE OF THE LAVATORY AND THE
 WRAPPED EDGE OF THE COLUMN. THE WATER CLOSET SHALLL BE
 16-18 INCHES TO ITS CENTERLINE PER ANSI A117.1
 SEC.1003.11.2.4.
 24) THE MAXIMUM DEPTH OF THE LAVATORIES SHALL BE 24
 INCHES. THE PLANS SHOW SOME OF THE LAVATORIES AS 25 1/2
 INCHES DEEP. INDICATE ON THE UNIT FLOOR PLANS THAT THE
 MAXIMUM DEPTH OF THE LAVATORIES IS 24 INCHES PER ANSI
 A117.1.
 25) SHT. A9.16.1 - UNIT 16 - SHOWS THE WATER CLOSET IN
 THE MASTER BATH LOCATED 1 FOOT 10 INCHES (1'-10" ) FROM
 THE EDGE OF THE LAVATORY AND THE ADJACENT WALL TO THE
 CENTERLINE OF THE WATER CLOSET. THE WATER CLOSET SHALLL
 BE 16-18 INCHES TO ITS CENTERLINE PER ANSI A117.1
 SEC.1004.11..3.2.2
 26) SHT. A9.17.1 - UNIT 17 - SHOWS THE WATER CLOSET IN
 THE MASTER BATH LOCATED 2 FEET 5 INCHES ( 2'- 5" ) FROM
 THE ADJACENT WALL TO THE CENTERLINE OF THE WATER
 CLOSET. THE WATER CLOSET SHALLL BE 16-18 INCHES TO ITS
 CENTERLINE PER ANSI A117.1 SEC.1004.11.3.2.2.
 27) SHT. A9.20.1 - UNIT 20 - INDICATE ON THE PLAN THE
 UNIT TYPE BATHROOM AND OPTION TYPE ON THE PLAN PER ANSI
 A117.1. THE CENTERLINE OF THE WATER CLOSET FROM THE
 EDGE OF THE LAVATORY IS SHOWN AS 1 FOOT 9 INCHES (1'-
 9" ). CLARIFY.
 28) SHT. A9.52.3 - IDENTIFY THE WALL FINISH AROUND THE
 JANITOR SINK. COMPLY WITH FBC-BUILDING SEC.1210.2.2.
 29) SHT. A9.52.4 - SHOW THE INSIDE CLEAR DIMENSIONS (L
 X W) FOR THE TOILET STALLS IN THE WOMEN'S RESTROOM.
 COMPLY WITH FBC-PLUMBING SEC. 405.3.1.
 30) SHT. A9.54.1 - SHOW THE WIDTH DIMENSION BETWEEN THE
 SINK AND THE GRILL AND THE REQUIRED CLEAR FLOOR SPACES
 FOR EACH PER ANSI A117.1 SEC. 305.
 31) SHT. A9.54.1 - SHOW THE WIDTH OF TOILET ROOM #1602
 ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1, ANSI
 A117.1 SEC. 604.
 32) SHEET P 0.3.0, ON THE TYPICAL KITCHEN, A SANITARY
 RISER WITH AN AIR ADMITTANCE VALVE IS RESTRICTED ON THE
 HIGH RISE DUE TO THE HYDRAULIC JUMP CAUSED IN A STACK
 THAT WITHSTANDS LIMITED POSITIVE PRESSURES. BECAUSE
 EXTREME PRESSURES MAY DAMAGE THE DEVICES, THE AIR
 ADMITTANCE VALVES MAY BE USED IN THE BUILDING'S TOP 4
 STORIES. PLEASE REFER TO THE CODE SECTION, WHICH
 REQUIRES RELIEF VENTS PER THE 2017 FBC SEC. P 918.3.1.
 A) ON THE TYPICAL CONDENSATE LINE, THE FLOOR HAS A
 KEYNOTE SIX, WHICH REFERS TO AN AUTOMATIC AIR VENT
 TYPE. PLEASE GIVE DETAIL OF A STANDARD FOR THIS TYPE OF
 VALVE. THIS NOTED IT MIGHT NOT BE IN A CAVITY WALL AS
 THERE IS NO NEGATIVE OR POSITIVE PRESSURE. YOU MAY
 OFFSET IT IN AN A/C CLOSET, AND IT SHALL BE
 NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 50 PER THE 2017 FBC SEC M 602.2.1.
 33) SHEET P 0.3.1, NOTE FIVE HAS THE LAST FEW WORDS ON
 TOP OF EACH OTHER. ON DETAIL ONE, PLEASE LABEL THE
 RE-VENT OF THE WASHING MACHINE. THE RE-VENT SIZE FROM
 SECOND TO THIRD LOOKS LIKE IT SHOULD BE 2" SO THE 3"
 SHOULD BE MOVED UP TO THE FOURTH FLOOR. DO THE SAME FOR
 THE 6TH FLOOR ON THE SECOND RISER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 34) SHEET P 0.3.2, RISER ONE THE MOP SINK HAS ONLY ONE
 SHUT OFF VALVE ON THE COLD, BUT IT REQUIRES A SHUT OFF
 AT EACH ENTRY FOR HOT AND COLD ALONG WITH THE PRV; A
 VALVE MAY BE NEEDED ON THE HOT SIDE OF THE HEATER FOR
 SERVICE, PLEASE SHOW AND LABEL PER THE 2017 FBC SEC. P
 606.1(2).
 35) SHEET P 1.0.1, THE GRID NUMBERS AND LETTERS ARE ON
 TOP OF EACH OTHER IN SOME PLACES, AND PLEASE OFFSET OR
 MOVE AWAY FOR CLARITY PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 THIS IS TYPICAL ON ALL PLUMBING PAGES, SO NOT TO REPEAT
 EVERY COMMENT; IT IS NOTED IN THIS ONE ONLY.
 A) THE FIRE ROOM HAS THREE-FLOOR DRAINS, THE TRASH ROOM
 HAS ONE, AND THE ELEVATOR HAS A FUNNEL DRAIN WITHOUT
 TRAP SEAL PROTECTION. PLEASE SHOW TRAP PRIMER AND GIVE
 DETAIL OR SPECIFICATION, ALSO WHERE THE SOURCE OF WATER
 IS COMING FROM IF APPLICABLE PER THE 2017 FBC SEC.
 1002.4.1. IF AN APPROVED TRAP SEAL IS USED THAT
 CONFORMS TO ASSE 1044 IN SOME AREAS, THE AHJ MAY NOT
 APPROVE THE DUE TO DEBRIS. PLEASE PROVIDE DETAILS OF
 THE SANITARY ISOMETRIC ON P 9.0.4 FOR THESE DRAINS,
 CLOUDS, OR BOXES AND GIVE REFERENCE NUMBERS; THESE
 TRAPS IN THESE AREAS ARE MISSING VENT PER THE 2017 FBC
 SEC. 1002.1.
 36) SHEET P 1.0.1B, PLEASE PROVIDE DETAIL OR SHOW HOW
 PIPES WILL BE PROTECTED FROM VEHICULAR TRAFFIC PER THE
 2017 FBC SEC. P 305.7. THIS IS TYPICAL ON ALL PLUMBING
 PAGES, SO NOT TO REPEAT EVERY COMMENT; IT IS NOTED IN
 THIS ONE ONLY.
 A) GRIDLINE LETTERS ARE NOT SHOWN. PLEASE MOVE THE
 DRAWING OVER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) IN THE MAINTENANCE ROOM AND THE DOG SPA, THEY BOTH
 HAVE A FLOOR DRAIN, AND BEHIND THE TWO ELEVATORS, IT
 HAS A FUNNEL DRAIN WITHOUT TRAP SEAL PROTECTION. PLEASE
 SHOW THE TRAP PRIMER AND GIVE DETAIL AND OR
 SPECIFICATION, ALSO WHERE THE SOURCE OF WATER IS COMING
 FROM IF APPLICABLE PER THE 2017 FBC SEC. 1002.4.1. IF
 AN APPROVED TRAP SEAL IS USED THAT CONFORMS TO ASSE
 1044 IN SOME AREAS, THE AHJ MAY NOT APPROVE THE DUE TO
 DEBRIS. PLEASE PROVIDE DETAIL OF THE SANITARY ISOMETRIC
 ON P 9.0.4 FOR THESE DRAINS, CLOUDS, OR BOXES AND GIVE
 REFERENCE NUMBERS.
 C) THE STORAGE ROOM WITH THE LAUNDRY TRAY IS NOT
 LABELED NEXT TO THE ELEVATORS; PLEASE LABEL PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS
 D) THE TRAPS IN THESE AREAS ARE MISSING A VENT PER THE
 2017 FBC SEC. 1002.1.
 37) SHEET P 1.1.1A, THE BOOSTER PUMPS IN THE FIRE ROOM
 HAS NO BYPASS OR SHUT OFF VALVES FOR MAINTENANCE
 PURPOSES. PLEASE SHOW PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A) TRASH ROOM HAS NO HOSE BIBB, AND IT IS STRONGLY
 SUGGESTED BUT NOT ENFORCED. THE TRASH SHOOT MAY HAVE A
 SANITIZER IN MOST CASES, BUT NO WATER IS SHOWN OR
 DETAILS FOR IT; IF APPLICABLE, PLEASE GIVE A POINT AND
 REFERENCE TO THE PAGE THAT WILL BE USED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 38) SHEET P 1.1.1B, THE MAINTENANCE ROOM, DOES NOT HAVE
 ANY DETAILS; PLEASE ADD A DETAIL P 9.0.2 SINCE THEY ARE
 NEXT TO EACH OTHER AND REFERENCE IT ON THIS PAGE. IT
 WILL NEED TO SHOW TRAP PRIMER, FLOOR DRAIN, AND VENT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 39) SHEET P 1.3.1A, THE MECHANICAL ROOM, AND BIKE ROOM
 ARE NOT LABELED; PLEASE LABEL PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 40) SHEET P 1.4.1A, THE MECHANICAL ROOM REQUIRES A TRAP
 PRIMER AND WATER ALONG WITH A VENT: IF USING A TRAP
 PRIMER THAT INVOLVES WATER, PLEASE SHOW THE SOURCE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 41) SHEET P 1.5.B, IN THE POOL AREA, THERE ARE MANY
 MISSING CIRCLES WHICH INDICATE THAT A PIPE IS GOING UP
 OR DOWN. PLEASE OVERLAY AND MATCH TO P 1.6.B; THERE ARE
 TOO MANY TO MENTION ON THIS PAGE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 42) SHEET P 1.6.1A, PLEASE REFER TO GRID LINES
 B-B.5/2-2.3; THE 4" DD IS A DECK DRAIN AS A ROOF DRAIN
 ON TOP; PLEASE REMOVE FOR CLARITY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) ON-GRID LINES 4.6-.5/A.1-B, THE PD IS NOT LABELED OR
 HAS SF SIZE FOR IT; PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 B) ON-GRID LINES 4-5/D-E THE BATHROOMS HAVE TOO MANY
 WATER LINES AND LABELS, MAKING IT HARD TO SEE OTHER
 DETAILS; PLEASE LIGHTEN THE OR REMOVE FOR CLARITY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 43) SHEET P 1.6.1B, PLEASE GIVE DETAILS OR PROVIDE THE
 SPECIFICATION FOR THE GAS SOLENOID VALVE PANIC SHUT OFF
 AND PRESSURE REDUCING VALVES, LABEL THEM TO WHERE THEY
 ARE REFERENCED AT, IF A PAGE OF DETAIL IS AVAILABLE FOR
 THEM, PLEASE NOTE ON KEYNOTE LEGEND PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) PLEASE PROVIDE DETAILS FOR PLANT DRAINS AND PUT A
 REFERENCE ON KEYNOTE LEGEND PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 B) ON-GRID LINES 8-8.78 AND B-B.5, THERE IS A TRENCH
 DRAIN BUT LOOKS TO BE A PLANT DRAIN NEXT TO THE POOL,
 AND ON TOP, THERE IS ANOTHER PLANT DRAIN, AND IT HAS NO
 LABEL OR SIZE; PLEASE CLARIFY PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 C) ON-GRID LINES 8-8.78 AND D-D,8, THERE IS A 4" PLANT
 DRAIN LABELED -SF ON THE POOL DECK; DOES IT BELONG
 THERE, OR IS IT IN THE WRONG LOCATION? PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 D) ON-GRID LINES 7.2-8/D.8-F THERE IS A PLANT DRAIN
 SHOWN, BUT IT'S LABELED 4" DD (123). PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 E) IN THE POOL EQUIPMENT ROOM, THERE IS A 4" FLOOR
 DRAIN THAT REQUIRES A VENT, PRIMER, SOURCE OF WATER,
 AND DETAIL WITH A REFERENCE NUMBER; ON THE FLOOR BELOW,
 IT SAYS 4" S UP ONLY. PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 44) SHEET P 1.7.1A, THE GRID LINES ON THE LEFT BOTTOM
 ARE OFF THE PLOTTED DRAWING AND OTHER OVERLAPPED (AS
 MENTION BEFORE, PLEASE CORRECT ALL OVERLAPS IN ALL
 PAGES); PLEASE MOVE OVER PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 45) SHEET P 1.8.1A, WHERE THE TWO RESTROOMS ARE, THE
 ROOM BEHIND THEM HAS NO LABEL; PLEASE LABEL ALL PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A)THERE IS NO LAYOUT SHOWING THE RD-1 AND HB-3; PLEASE
 PROVIDE A REFERENCE IF ON ANOTHER PAGE OR GENERATE ONE
 PLEASE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 46) SHEET P 1.8.1B, THERE IS AN AREA WHERE THE TRENCH
 DRAINS ARE, AND THEY ARE NOT LABELED. PLEASE LABEL PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 A) THERE IS NO LAYOUT SHOWING THE RD-1 AND TD-1; PLEASE
 PROVIDE ON PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 47) SHEET P 9.0.1, DETAIL 2 FOR THE FITNESS CENTER IT
 HAS A 6? PIPE COMING UP, NOT SIZED AND NOT LABELED OR
 WITH A REFERENCE POINT, ALSO SIZE THE HORIZONTAL 4?
 LINE GOING TO THE MEN'S ROOM, AND THE LADIES ROOM
 DOWNSTREAM HAS A FEW 3? AND 4? NOT SIZED AS WELL.
 PLEASE PROVIDE SIZES PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A) ON THAT SAME DETAIL, THERE IS A 4" SANITARY LINE
 THAT HAS NO LABEL TO WHERE IT IS GOING. PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) PLEASE SHOW ALL TRAP PRIMERS ON THE FLOOR DRAINS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 C) LAVATORIES ON ALL AP-3 NEED TO BE SHOWN HORIZONTALLY
 AS THEY SEEM TO BE IN AN S-TRAP POSITION. PLEASE CHANGE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 D) THERE ARE THREE 3" SANITARY PIPES GOING UP WITH NO
 DESTINATION VENT AS WELL, PLEASE LABEL PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 E) THERE ARE TWO FLOATING FITTING AND A PIPE WITH A
 90-DEGREE ELBOW GOING DOWN AND A WYE AT THE END; IT
 DOESN?T HAVE A SIZE OR DESTINATION; PLEASE REMOVE AND
 OR GIVE A REFERENCE TO ITS USE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 F) ON DETAIL FOUR, PLEASE SHOW SHUTOFF VALVES FOR THE
 RECIRCULATING PUMP AT THE FITNESS ROOM AREA WITH AN
 ACCESS BOX ON BOTH SIDES OF THE RECIRCULATING PUMP FOR
 THE WATER HEATER, AND ALL FIXTURES PER THE 2017 FBC
 SEC. P 606.1.
 G) PLEASE SHOW AND LABEL THE HAMMER ARRESTOR FOR THE
 DRINKING FOUNTAIN AND ALL QUICK CLOSING VALVES PER THE
 2017 FBC SEC. P 604.9.
 H) PLEASE SHOW AND LABEL CHECK VALVES ON THE
 RECIRCULATING SYSTEM PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 I) THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES
 MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE
 REFER TO THE 2017 FBC ENERGY CODE TABLE C404.5.1.
 J) ON DETAIL SIX, PLEASE SHOW A BYPASS FOR THE BOOSTER
 PUMPS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 K) ON DETAIL ONE, AP-9 IS LABELED AS A FLOOR DRAIN;
 PLEASE MARK AS MOP SINK AND HAVE A NOTE THAT
 SURROUNDING THE WALL SHALL BE NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2.
 L) IN THAT SAME DETAIL, THE MOP SINK, AND DRINKING
 FOUNTAIN CANNOT DISCHARGE INTO A HORIZONTAL WET VENT
 PER THE 2017 FBC SEC. P 912.1.
 M) IN THAT SAME DETAIL, THE WATER CLOSET IS ON A
 SANITARY TEE ON ITS BACK; A WATER CLOSET BEND IS
 REQUIRED PER THE 2017 FBC SEC. P 420.4.
 48) SHEET P 9.0.2, ON DETAIL 2/P 9.0.2, PLEASE SHOW
 LABELING ON THE SANITARY DOWN FROM WHERE IT'S COMING
 FROM AND WHERE IT IS GOING TO PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 A. ON DETAIL 4/P 9.0.2, PLEASE SHOW LABELING ON THE
 SANITARY DOWN FROM WHERE IT'S COMING FROM AND GOING TO
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B. ON DETAIL 5/P 9.0.2, IT SHOWS TWO DOG SPAS, ARE
 THESE STAND-ALONE UNITS AND IF SO, PLEASE PROVIDE
 MANUFACTURES SPECIFICATION TO SEE IF THEY REQUIRE A
 BACKFLOW DEVICE. THE DOG SPA SHOWS A LAV THAT IS NOT
 LABELED, AND IT IS MISSING WATER, VALVES, AND SANITARY
 DRAINAGE TO IT; PLEASE GIVE DETAIL. PLEASE SHOW THE
 FLOOR DRAIN IN THE DOG SPA PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 C. ON DETAIL 6/P 9.0.2, THE ARMS FOR THE STACK BY THE
 TWO-FLOOR DRAINS HAVE THE ARMS IN AN S-TRAP, PLEASE
 SHOW IN A HORIZONTAL POSITION. THE FLOOR DRAIN IS
 MISSING A TRAP PRIMER ALONG WITH A SOURCE OF WATER TO
 PRIME. THERE IS A SECOND-FLOOR DRAIN IN THE ROOM NEXT
 TO IT AND NOT SHOWN, AND IT MAY NEED TO BE VENTED IN
 THIS SYSTEM. THE LAVATORY IS NOT SHOWN ON THE
 ISOMETRIC, AND PLEASE INCORPORATE IT IN THE SYSTEM OF
 THIS ISOMETRIC. PLEASE SHOW WHERE AND SIZE OF THE MAIN
 TRUNK LINE IS COMING AND HEADS TO PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 D. ON DETAIL 7/P 9.0.2, THE TOILET ROOM SHALL HAVE
 TEMPERED WATER. IT SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC
 SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 E. ON THAT SAME DETAIL, IT SHOWS A COFFEE STATION ON
 THE MEZZ NEXT TO THE TOILET ROOM; IS THIS A UNIT THAT
 REQUIRES WATER TO IT. IF SO, IT MUST BE EQUIPPED WITH
 AN INLINE VACUUM BREAKER THAT CONFORMS TO ASSE 1024 PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 F. ON DETAIL 8/P 9.0.2, PLEASE SHOW THE SHUT-OFF VALVE
 A LITTLE LARGER AND VALVES ON EACH FIXTURE; IF AN
 ACCESS BOX IS REQUIRED, PLEASE SHOW IT AS WELL PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 G. ON DETAILS 11 AND 12/P 9.0.2, PLEASE SHOW THE
 SHUT-OFF VALVES FOR THE WATER HEATER, DOG SPA, AND LAV.
 PLEASE SHOW A DRAIN PAN FOR THE WATER HEATER AND THE
 LOCATION WHERE IT WILL DISCHARGE PER THE 2017 FBC SEC.
 P 504.7.2.
 49) SHEET P 9.0.3, IN DETAIL 1/P 9.0.3 AND 2/P 9.0.3,
 IN THE JANITOR'S ROOM THE MOP SINK IS LABELED AS FD-2,
 PLEASE CORRECT, PLEASE SHOW HOT AND COLD WATER LINE TO
 THE MOP SINK AND SHUT OFF VALVES PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 A) ON DETAIL 4/P 9.0.3, IT DOES NOT SHOW WHERE 4"
 SANITARY DOWN IS COMING FROM, AND THERE IS NO VENT
 TYING TO THE OUTSIDE AS IT IS LOOPED TO ITSELF; PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) ON DETAIL 5, 6, 7, AND 8/P 9.0.3, IT SHOWS A UNIT
 UNDER THE CABINET LABELED G-1, AND ON THE DESCRIPTION,
 IT IS CALLING A GRILLE; IS THIS A GREASE INTERCEPTOR.
 IF THIS IS A GREASE INTERCEPTOR, PLEASE PROVIDE THE
 FOLLOWING;
 PLEASE SHOW HOW YOU DETERMINE THE SIZE OF THE GREASE
 TRAP PRESUMING YOU ARE USING 14 LB. GREASE CAPACITY,
 (7) GALLONS PER MINUTE RATE FLOW; THIS UNIT SHALL BE
 SIZED IN ACCORDANCE WITH THE SIZING REQUIREMENTS PER
 THE 2017 FBC SEC P 1003.3.4 AND TABLE 1003.3.4.1. 10.
 PROVIDE CALCULATIONS USED IN THE SIZING OF A GREASE
 INTERCEPTOR, AND PLEASE PROVIDE MANUFACTURER
 SPECIFICATION PER THE WPB FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
 C) ON DETAIL 11/P 9.0.3, THE TOILET ROOM SHALL HAVE
 TEMPERED WATER. IT SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC
 SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 D) ON DETAIL 12/P 9.0.3, PLEASE PROVIDE A SHUT-OFF
 VALVE FOR EACH FIXTURE AND THE TOILET ROOM AND DRINKING
 FOUNTAIN AREA. PLEASE PROVIDE A HAMMER ARRESTOR FOR THE
 ELECTRIC WATER COOLER PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 E) ON DETAIL 1/P 9.0.3, FOR THE MOP SINK, THE
 SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2 AND
 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS
 SHEET.
 50) SHEET P 9.0.4, ON DETAIL P 9.0.4 IS LABELED AS AN
 FD-2, AND IT SHOULD BE A MOP SINK; PLEASE LABEL
 ACCORDINGLY FOR CLARITY IN THE FIELD PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) ON DETAIL 2/P 9.0.4, PLEASE SHOW REFERENCE, WHERE
 THE 4" SANITARY IS COMING FROM AND, WHERE THE VENT IS
 CONNECTING TO, ALSO SHOW WHERE THE 3? SANITARY IS GOING
 TO. PLEASE SIZE THAT SAME RISER GOING UP PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 B) ON DETAIL 3/P 9.0.4, FOR THE MOP SINK, THE
 SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2 AND
 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS
 SHEET.
 C) ON DETAIL 5/P 9.0.4, IT SHOWS A COFFEE STATION ON
 THE GROUND FLOOR; IS THIS A UNIT THAT REQUIRES WATER TO
 IT. IF SO, IT MUST BE EQUIPPED WITH AN INLINE VACUUM
 BREAKER THAT CONFORMS TO ASSE 1024 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 D) ON DETAIL 6/P 9.0.4, PLEASE SHOW A TEMPERING DEVICE
 FOR THE ACCESSIBLE LAV THAT COMPLIES WITH ASSE 1070 OR
 GIVES DETAIL ON ANOTHER PAGE AND REFERENCES THAT DETAIL
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 E) ON DETAIL 7/P 9.0.4, PLEASE PROVIDE A SHUT-OFF VALVE
 FOR EACH FIXTURE AND THE MANAGER'S AREA. PLEASE PROVIDE
 A HAMMER ARRESTOR FOR THE ELECTRIC WATER COOLER PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 F.)ON DETAIL 9/P 9.0.4, PLEASE PROVIDE SHUT-OFF VALVES
 TO THE MOP SINK, SIZE, AND LABEL THEM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 G) ON THE SAME DETAIL ABOVE, IT HAS A DOG SPA; IS THIS
 A MANUFACTURED UNIT? WHICH MAY REQUIRE A VACUUM BREAKER
 OR BACKFLOW DEVICE. PLEASE CLARIFY AND ADD MORE
 INFORMATION PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 51) SHEET P 9.0.5, THE DRAWING HAS MISSING DECK DRAINS,
 AND EXTRA ROOF DRAINS, RISERS ARE CONNECTING TO DRAINS
 THAT ARE MISSING FITTINGS, TOO MANY TO CALL OUT PLEASE
 GO BACK AND REFER TO THE FLAT DRAWING AND MAKE
 CORRECTIONS FOR CLARITY PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 52) SHEET P 9.0.6, PLEASE SIZE BOTH, CLEAN-OUTS AND
 LABEL THE ONE OUTSIDE AND DELETE TWO FLOATING FITTINGS
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 53) SHEET P 9.0.7, THE DP-8 AND DP-9 SIZES ARE NOT
 LABELED, CD-1 AND CD-2 SIZES ARE NOT LABELED, AND THE
 THREE 1? CONDENSATE TIED TOGETHER IS GOING DOWN THAT IS
 MISSING WHERE IT?S GOING TO AND SIZE. PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 54) SHEET P 9.0.8, CONDENSATE NUMBER 16, HAS NO LABEL
 AS TO WHERE IT IS GOING; PLEASE PROVIDE INFORMATION
 LIKE OTHER STACKS PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A) PLEASE LABEL ALL CLEAN-OUTS, IT SHOWS CLEAN-OUTS AT
 ALL BASE OF STACKS IN THE DETAILS ON 2/P 0.3.0, BUT
 NONE IS SHOWN ON THIS PAGE; PLEASE ADD TO COINCIDE WITH
 BOTH DRAWINGS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) THERE ARE THREE FITTING FLOATINGS IN THIS DRAWING (
 TWO DRAINS AND ONE COMBO); PLEASE REMOVE THEM TO
 PREVENT CONFUSION PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 C) PAN DRAINS ARE TERMINATING IS IN THE PARKING DECK,
 AND THEY MUST GO TO THE EXTERIOR OF THE BUILDING TO
 COMPLY WITH THE 2017 FBC SEC. P 507.7.2.
 55) SHEET P 9.0.9, PLEASE REFER TO P 1.6.1 FOR OVERLAYS
 AND CORRECTIONS OF ALL THE ROOF, TRENCH, AND PLANT
 DRAINS TO COINCIDE WITH EACH OTHER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 56) SHEET P 9.0.12, PLEASE LABEL CHECK VALVES AND
 SHUTOFF VALVES FOR BOTH ELEVATOR PUMPS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) PLEASE SHOW TRAP PRIMERS, SOURCE OF WATER, AND VENT
 ALL FLOOR DRAINS PROPERLY, TYPES 1 AND 2 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 B) THE STACK BY THE TWO-FLOOR DRAINS THAT HAVE THE ARMS
 IN AN S-TRAP, PLEASE SHOW IN A HORIZONTAL POSITION PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 C) ALL THE PIPES GOING UP, SANITARY AND VENTS, PLEASE
 GIVE A REFERENCE POINT OF CONNECTION AND PLEASE LABEL
 AND SIZE THE CLEAN-OUT UPSTREAM OF THE 8" BY 6" WYE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 D) THE THREE FD-1 NEXT TO STACK S/R-9 ARE NOT LABELED;
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 57) SHEET P 9.0.13, IN DETAIL THREE, LEFT-RIGHT CORNER,
 1/P 0.3.0 (22 DFU) SHOULD BE 4", AND THE P 0.3.1 (66
 DFU) THEY ARE CROSSED, PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) IN DETAIL FIVE IN THE LOWER-LEFT CORNER, AS NOTED ON
 COMMENT 17 LETTER B, I, M, AND N. PLEASE FIX TO MATCH P
 9.0.1 ON THE ISOMETRIC, PLEASE SIZE RIGHT SIDE ON
 DOUBLE 6? WYE AND UPSTREAM OF THAT IS 4/P 0.3.0 (4 DFU)
 THAT IS MISSING A PIPE SIZE AND ALL OTHER BRANCHES IN
 BOTH BATHROOM GROUPS ARE MISSING SIZES, PLEASE SIZE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 B) IN DETAIL SIX, THE MIDDLE BOTTOM TWO 1/P 0.3.0 (60
 DFU) AND 4/ P 0..3.0 (20 DFU) ARE MISSING SIZES. THERE
 IS A 2" SANITARY THAT IS NOT LABELED TO WHERE IT IS
 GOING. PLEASE LABEL PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 C) IN DETAIL SEVEN, THE RIGHT BOTTOM CORNER, 2/P 0.3.0
 IS REFERENCED AS A SANITARY BUT IS A DETAIL FOR
 CONDENSATE; PLEASE CORRECT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 58) SHEET P 9.0.14, IN DETAIL TEN IN THE LEFT CORNER,
 THE 4" S (84) DFU HAS NO LABEL FOR A RISER. PLEASE
 LABEL PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A) IN DETAIL ELEVEN, THE RIGHT BOTTOM CORNER 1/P 0.3.0
 (84 DFU) HAS NO SIZE ON THE HORIZONTAL PIPE. PLEASE
 SIZE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) IN DETAIL NINE, THE TOP RIGHT CORNER 4/P 0.3.0 (28
 DFU) IS SIZED AS 4" BUT NEEDS TO BE 3" ALSO, IN THE
 SAME RUN DOWNSTREAM SIZE, THE 6" SANITARY IS MISSING;
 DOWNSTREAM FROM THE WYE, THERE IS 1/P 0.3.0 (84) THAT
 IS MISSING A SIZE. ON THE OTHER SIDE OF THAT BRANCH,
 TWO 1/P 0.3.0 (84 DFU) ARE MISSING THEIR SIZES, AND
 UPSTREAM OF THAT, 1/P0.3.1 IS MISSING A SIZE AS WELL.
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 C) IN DETAIL EIGHT, THE LEFT TOP CORNER OF THE LAST
 RISER IS MISSING THE SIZE AND DFU, AND THE 1/P 0.3.0 IS
 NOT POINTING TO IT. PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 59) SHEET P 9.0.15, PLEASE SHOW BYPASS AND SHUTOFF
 VALVES ON BOOSTER PUMPS, PLEASE LABEL ALL SHUT OFF
 VALVED AND ACCESS PANELS, 6? WATER MAIN, PLEASE LABEL
 WHERE IT'S COMING FROM, PLEASE LABEL ALL WATER GOING UP
 TO WHERE IT CONTINUES PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 60) SHEET P 9.0.16, PLEASE LABEL ALL SHUT OFF VALVED
 AND ACCESS PANELS; PLEASE SHOW A SHUTOFF VALVE FOR ALL
 HB-3 ON THE ROOF; AP-5 HAS NO REFERENCE POINT TO WHAT
 IT SERVES. PLEASE LABEL REFERENCES TO WHERE WATER LINES
 COME FROM AND GO PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 61) SHEET P 9.0.18, IN THE FIRST AREA DRAIN NEXT TO THE
 TRENCH DRAIN, AN AD-1 IS NOT LABELED OR SIZED PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 62) SHEET P 9.1.2, IN DETAIL TWO, 3/4" H & C LINES FROM
 WATER HEATER NOT SIZED OR LABELED AND 1/2" H & C TO THE
 TUB'S LINES ARE NOT LABELED, PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) IN DETAIL TWO, THE DISTANCE FROM THE STACK TO THE
 SHOWER SHALL NOT EXCEED 8 FEET PER THE 2017 FBC SEC.
 TABLE P 909.1
 63) SHEET P 9.1.3, IN DETAIL TWO, 3/4" H & C LINES FROM
 WATER HEATER NOT SIZED OR LABELED, 1/2" H & C TO THE
 LINES TO THE TUB, WATER CLOSET, LAVE AND SHOWER NOT
 SIZED AND LABELED THE PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 64) SHEET P 9.1.4, IN DETAIL ONE, H & C WATER LINES
 COMING OUT OF THE HEATER NOT SIZED OR LABELED / ALSO IN
 DETAIL THREE, 1/2" H & C LINES TO THE WASHING MACHINE
 AND THE KITCHEN NOT SIZED OR LABELED PER THE PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 65) SHEET P 9.1.5, IN DETAIL THREE, 1/2" H & C LINES TO
 THE SHOWER, C WATER CLOSET, AND H & C TO THE LAV NOT
 SIZED OR LABELED PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 66) SHEET P 9.1.6, IN DETAIL TWO, 3/4" HOT ON WATER
 HEATER NOT SIZED OR LABELED, IN DETAIL FOUR, 1/2" H & C
 TO THE LINES TO THE KITCHEN AND FRIG NOT SIZED OR
 LABELED PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 67) SHEET P 9.1.7, IN DETAIL ONE, 3/4" H & C LINES FROM
 WATER HEATER NOT SIZED OR LABELED, IN DETAIL TWO 1/2" H
 & C TO THE LAV NOT SIZED OR LABELED PER THE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 68) SHEET P 9.1.8, 1/2" H & C TO THE TUB LINES ON TUB
 AND WATER CLOSET NOT SIZED OR LABELED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) THE LAVATORY ARM SHOWS A HORIZONTAL SANITARY TEE ON
 A DOUBLE LAVATORY WHICH IS NOT PERMITTED PER THE 2017
 FBC TABLE P 706.3.
 69) SHEET P 9.1.9, 1/2" H & C TO THE WASHING MACHINE,
 FRIG, LAV, AND WATER CLOSET ARE NOT SIZED OR LABELED
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 70) SHEET P 9.1.10, 3/4" HOT COMING OUT THE WATER
 HEATER NOT LABELED OR SIZED, 1/2" H & C LINES NOT
 LABELED OR SIZE ON THE WATER TO THE FRIG AND THE TWO
 WATER CLOSET AND TUB PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 71) SHEET P 9.1.11, 1/2" H & C LAV NOT SIZED OR LABELED
 AND H & C TO THE KITCHEN NOT SIZED OR LABELED PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) DETAIL ONE SHOWS WATER CLOSET AND SHOWER NOT VENTED;
 TRAPS REQUIRE A SYSTEM OF VENTING SO THAT A PRESSURE
 DIFFERENTIAL OF NOT MORE THAN 1? FOR EACH PER THE 2017
 FBC SEC. 901.2.
 72) SHEET P 9.1.12, 1/2" H & C NOT LABELED OR SIZED TO
 BOTH LAVS AND WATER CLOSET PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 73) SHEET P 9.1.13, 1/2" H & C NOT LABELED OR SIZED TO
 LAVS, TUB, AND WATER CLOSET AND 1/2" H & C NOT LABELED
 OR SIZED TO LAV AND WATER CLOSET THEN TO SHOWER PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 SWIMMING POOL
 1) SUBMIT A COPY OF THE APPLICATION FOR THE OPERATING
 PERMIT STAMPED BY THE FLORIDA DEPARTMENT OF HEALTH PER
 FL. STATUTES 514.03, 553.79 (11).
 2) SHT. P1.1 -THE PLAN SHOWS THE DISTANCE TO THE
 SANITARY FACILITIES AS 184 FEET THAT TRAVERSES A SET OF
 STAIRS. WHAT IS THE DISTANCE OF THE ACCESSIBLE ROUTE
 FROM THE NEAREST WATER'S EDGE TO THE ENTRY DOORS OF THE
 RESTROOMS? THIS MUST BE TTAKEN INTO CONSIDERATION.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 SHOWER. THE POOL SHOWER SHALL COMPLY WITH THE
 REQUIREMENTS OF ANSI A117.1 FOR COMPLIANCE WITH FAIR
 HOUSING REQUIREMENTS.
 4) SHT. P2.0 - THERE IS A NOTE UNDER THE FRICTION LOSS
 TABLE THAT REFERS TO THE BENDING OF PVC PIPING WITH
 HEAT. APPROVAL OF THIS PROCESS WILL BE BASED ON
 DOCUMENTATION FROM THE MANUFACTURER THAT SPECIFICALLY
 ALLOWS THIS PRROCESS.
 5) FBC-BUILDING SEC.454.1.1.1 STATES THE FILTRATION
 SYSTEM SHALL BE CAPABLE OF PROVIDING A FLOW RATE OF AT
 LEAST .75 GPMM FOR EACH LIVING UNIT AT NONTRANSIENT
 FACILITIES WHICH WOULD BE 174.75 GPM BUT THE DESIGN
 FLOW RATE OR THIS POOL IS 170 GPM. CLARIFY.
 6) FBC-BUILDING SEC. 454.1.6.1.2 - DOORS TO THE
 RESTROOMS SHALL BE WITHIN 50 FEET OF THE BUILDING'S
 EXTERIOR DOOR. INDICATE THIS ON THE SHT. P1.1.
 7) SHOW THE SPACING OF THE WALL INLETS ON SHT. P2.0.
 COMPLY WITH FBC-BULDING SEC. 454.1.6.5.9.1.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAINS. THE MAIN DRAIN COVERS SHALL COMPLY WITH
 ANSI/APSP/ICC 7 - 2013 SEC.4.3.1.1.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATER. THE POOL HEATER SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82% PER 2017 FBC-ENERGY TABLE C404.2.
 10) OUTDOOR HEATED SWIMMING POOLS SHALL BE EQUIPPED
 WITH A VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE
 OR A LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT
 LOSS. SHOW HOW THIS WILL BE ACHIEVEDFBC-ENERGY SEC.
 C404.9.3.
 11) SHOW THE TEMINATION OF THE POOL WASTE LINE ON THE
 PLANS. THE WASTE LLINE SHALL NOT DISCHARGE TO THE STORM
 OR SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF
 ORDINANCES ARTICLE III, SEC. 90-126 (B) (5) (SANITARY
 SEWERS), AND ARTICLE IV, SEC. 90-203 (A). CONTACT MANNY
 GONZALEZ IN THE CITY OF WEST PALM BEACH ENGINEERING
 DEPARTMENT AT 561-494-1040 FOR FURTHER INFORMATION.
 12) SHT. P2.3 SHOWS A FLOOR DRAIN IN THE POOL EQUIPMENT
 ROOM DISCHARGING TO THE STORM SEWER. THIS FLOOR DRAIN
 SHALL DISCHARGE TO THE SANITARY SEWER AND WILL REQUIRE
 A NEUTRALIZATION TANK DUE TO THE CHEMICALS LLOCATED IN
 THIS ROOM PER FBC-PLUMBING SEC. 803.1,,
 13) SHT. P2.3 - THERE IS A NOTE ON THE COLLECTOR TANK
 DETAIL THAT STATES" COLLLECTOR TANK PIT DRAINAGE BY
 G.C." SUBMIT DETAILS ON THIS DRAINAGE AND IT'S
 TERMINATION POINT OR PROVIDE THE PLAN SHEETS OF THIS
 PROJECT WHHERE THIS INORMATION CAN BE FOUND. WPB AMEND.
 TO FBC SEC. 107.2.1.
 14) SHT. P2.4 - POOL EQUIPMENT PLUMBING DIAGRAM - THERE
 IS AN ITEM LOCATED NEXT TO ITEM PH ON THE DIAGRAM THAT
 IS LABELED AS "PI". PI IS FOR THE COLLECTOR TANK.
 CORRECTLY IDENTIFY THIS ITEM. WPB AMENND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  