| 2020-12-03 14:40:14 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20101431 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE HEATING AND COOLING SIZING |
| | CALCULATIONS. FBC EC C403.2.1 |
| | |
| | 2) SHEET M0.3.1- VENTILATION SCHEDULES INDICATES THE |
| | PUBLIC TOILET ROOMS EXHAUST FANS ARE EXHAUSTING 50 CFM. |
| | SHEET M0.2.2 FAN SCHEDULE INDICATES EF-1 EXHAUSTS 75 |
| | CFM AND IS INTERLOCKED WITH WALL LIGHT SWITCH. FBC M |
| | TABLE 403.3.1.1 NOTE E INDICATES THE 50 CFM MUST BE FOR |
| | CONTINUOUS OPERATION. PLEASE USE THE 75 CFM IN THE |
| | VENTILATION CALCULATIONS OR REMOVE CONTROL TYPE 2 AND |
| | MAKE THE EF-1 CONTINUOUSLY OPERATED. |
| | |
| | |
| | 3) SHEET M0.4.2- DETAIL 1: 504.8.5 LENGTH |
| | IDENTIFICATION. |
| | WHERE THE EXHAUST DUCT EQUIVALENT LENGTH EXCEEDS 35 |
| | FEET (10 668 MM), THE EQUIVALENT LENGTH OF THE EXHAUST |
| | DUCT SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG. |
| | THE LABEL OR TAG SHALL BE LOCATED WITHIN 6 FEET (1829 |
| | MM) OF THE EXHAUST DUCT CONNECTION. |
| | |
| | 4) PLEASE PROVIDE A LETTER FROM THE DRYER MANUFACTURER |
| | STATING THAT THE X VENT DRYER EXHAUST TERMINATION IS |
| | ALLOWED WITH EACH SPECIFIC DRYER. THE X VENT IS UNIQUE |
| | IN THE FACT THAT IT USES BOTH THE BACK-DRAFT DAMPER AND |
| | THE LOUVER. THE INSTALLATION MANUAL DOES NOT ADDRESS |
| | THIS KIND OF INSTALLATION. WITH THE X VENT SYSTEM THE |
| | BOX OF THE X VENT IS MOUNTED INTO THE EXTERIOR OF THE |
| | WALL AND THE LOUVER IS FLUSH TO THE EXTERIOR WALL. THE |
| | EXHAUST OF THE DRYER MUST TRAVEL THROUGH THE EXHAUST |
| | DUCT, OPEN THE BACK-DRAFT DAMPER AND TRAVEL THROUGH THE |
| | X VENT COVER (LOUVER) BEFORE IT IS EXHAUSTED TO THE |
| | OUTDOORS. BECAUSE THIS PRODUCT USES BOTH THE BACK-DRAFT |
| | DAMPER AND THE OUTER COVER OF THE BOX (LOUVER) INSTEAD |
| | OF EITHER THE BACK-DRAFT DAMPER OR THE LOUVER AS |
| | TYPICALLY SEEN IN THE MANUFACTURES INSTALLATION MANUAL |
| | THE OUTER LOUVER IS A RESTRICTION THAT MUST BE |
| | ADDRESSED. IN LIEU OF THE MANUFACTURES LETTER STATING |
| | THE MAXIMUM DRYER EXHAUST DUCT TO BE USED WITH THE X |
| | VENT SYSTEM THE ENGINEER OF RECORD MUST DETERMINE THE |
| | AMOUNT OF RESTRICTION THIS CREATES AND THE EFFECT TO |
| | THE DRYER EXHAUST DUCT LENGTH. THE ENGINEER OF RECORD |
| | MUST SUBMIT THE CALCULATIONS AND PROVIDE MAX. EXHAUST |
| | DRYER DUCT LENGTHS FOR EACH DRYER USED IN THIS PROJECT. |
| | FBC M 504.8.4.2 |
| | |
| | 5) SHEET M0.6.1- GARAGE EXHAUST SEQUENCE OF OPERATIONS: |
| | THE SEQUENCE OF OPERATION MUST ALSO INCLUDE NITROGEN |
| | DIOXIDE DETECTORS. FBC M 404.1 |
| | 404.1ENCLOSED PARKING GARAGES. |
| | WHERE MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED |
| | PARKING GARAGES OPERATE INTERMITTENTLY, SUCH OPERATION |
| | SHALL BE AUTOMATIC BY MEANS OF CARBON MONOXIDE |
| | DETECTORS APPLIED IN CONJUNCTION WITH NITROGEN DIOXIDE |
| | DETECTORS. SUCH DETECTORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THEIR MANUFACTURERS? RECOMMENDATIONS. |
| | |
| | 6) SHEET M1.1.1A: PLEASE SHOW THE DAMPERS AT THE RATED |
| | WALL AND FLOOR PENETRATIONS FOR THE DUCT WORK GOING UP |
| | TO AHU-A1 AND AHU-A2. FBC M 607 |
| | |
| | 7) SHEET M1.1.1A: AHU-A2 IS SUPPLYING 1250 CFM?S |
| | AIRFLOW TO THE LEASING AREA. SHEET M0.2.1 SPLIT SYSTEM |
| | DX SCHEDULE INDICATES THE AIRFLOW RATE FOR AHU-A2 IS |
| | 700 CFM?S OF AIRFLOW. PLEASE CORRECT THIS. FBC 107.2.1 |
| | |
| | 8) SHEETS M1.1.1A, M1.11.1B, M1.2.1B: AHU-A1 IS |
| | SUPPLYING 1,800 CFM, SHEET M0.2.1 SPLIT SYSTEM DX |
| | SCHEDULE INDICATES THAT AHU-A1 IS 1400 CFM?S OF AIR |
| | FLOW. PLEASE CORRECT THIS. FBC 107.2.1 |
| | |
| | 9) SHEET M1.1.1B: PLEASE MAKE SURE NOTE 8 INCLUDES ALL |
| | PENETRATIONS IN RATED WALLS. THE WALL SEPARATING THE |
| | PARKING GARAGE AND THE STORAGE ROOM IS BEING PENETRATED |
| | BY THE STAIR PRESSURIZATION DUCT WORK. |
| | |
| | |
| | 10) SHEET M1.1.1B: THE EF-2 EXHAUST FAN DUCT FOR THE |
| | GENERATOR ROOM IS PASSING THROUGH SEVERAL 2 HOUR RATED |
| | WALLS. PLEASE SHOW HOW THE PENETRATIONS IN THESE RATED |
| | WALLS ARE TO BE PROTECTED. FBC M 607 |
| | |
| | 11) SHEET M1.1.1B: THE GENERATOR EXHAUST PIPE IS |
| | PENETRATING RATED WALLS AND TRAVELING THROUGH THE |
| | EGRESS CORRIDOR. PLEASE SHOW HOW THE PENETRATIONS IN |
| | THE RATED WALLS WILL BE PROTECTED. FBC M607 |
| | |
| | 12) SHEET M1.1.1B: THE GENERATOR EXHAUST PIPE CANNOT |
| | PASS THROUGH THE EGRESS CORRIDOR. FBC 1024.6 |
| | |
| | 13) SHEET M1.1.1B: EF-6 AND 8; THE DUCTWORK FOR THESE |
| | EXHAUST FANS ARE PENETRATING SEVERAL RATED WALLS, |
| | PLEASE SHOW THE RATED DAMPERS AT EACH PENETRATION. FBC |
| | M607 |
| | |
| | 14) SHEET M1.1.1B:THE FRESH AIR DUCT FOR AHU-A7 IS |
| | PENETRATING A RATED WALL, PLEASE PROVIDE A RATED DAMPER |
| | AT THE PENETRATION. FBC M 607 |
| | |
| | 15) SHEET M1.2.1A: EF-1 DUCT WORK IS PENETRATING RATED |
| | WALLS, PLEASE SHOW RATED DAMPERS AT EACH PENETRATION. |
| | FBC M 607 |
| | |
| | 16) SHEET M1.2.1A: AHU-3 IS SUPPLYING 2220 CFM?S TO THE |
| | |
| | 17) SHEET M1.2.1B: THERE ARE NO NOTES ON THIS SHEET. |
| | NOTE 6 IN THE PARKING GARAGE APPEARS TO BE FOR A |
| | SENSOR. PLEASE PROVIDE NOTES FOR THIS SHEET. FBC |
| | 107.2.1 |
| | |
| | |
| | 18) SHEET M1.3.1A: PLEASE SHOW THE DAMPER FOR THE |
| | ELECTRIC ROOM EXHAUST AT RATED WALL. FBC M 607 |
| | |
| | 19) SHEET M1.4.1A: PLEASE SHOW THE DAMPER FOR THE |
| | ELECTRIC ROOM EXHAUST AT RATED WALL. FBC M 607 |
| | |
| | 20) SHEET M1.5.1A: PLEASE SHOW THE DAMPER FOR THE |
| | ELECTRIC ROOM EXHAUST AT RATED WALL. FBC M 607 |
| | |
| | 21) SHEET M1.6.1A: AHU-A4 IS SUPPLYING 2640 CFM TO THE |
| | FITNESS CENTER AREA, NO CFM?S LABELED FOR THE WOMEN?S |
| | TOILET ROOM. SHEET M0.2.1 SPLIT SYSTEM DX SCHEDULE |
| | INDICATES AHU-A4 SUPPLIES 1400CFM?S OF AIR FLOW. PLEASE |
| | CORRECT THIS. FBC 107.2.1 |
| | |
| | 22) SHEET M1.6.1A: AHU-A5 IS SUPPLYING 1200 CFM TO THE |
| | EXERCISE ROOM. SHEET M0.2.1 SPLIT SYSTEM DX SCHEDULE |
| | INDICATES AHU-A5 SUPPLIES 700 CFM TO THE EXERCISE ROOM. |
| | PLEASE CORRECT THIS. FBC 107.2.1 |
| | |
| | 23) SHEET M1.6.1A: THE OUTDOOR AIR DUCT FOR AHU-A5 FOR |
| | THE EXERCISE ROOM IS PENETRATING A RATED WALL. PLEASE |
| | PROVIDE A RATED DAMPER AT THIS PENETRATION. FBC M 607 |
| | |
| | 24) SHEET M1.6.1A: THE OUTDOOR AIR DUCT FOR THE |
| | VESTIBULE IS PENETRATING A RATED WALL AND APPEARS TO BE |
| | FLEX DUCT. PLEASE PROVIDE A RATED DAMPER AT THIS |
| | PENETRATION. FBC M 607 |
| | |
| | 25) SHEET M1.6.1A: PLEASE SHOW THE DAMPER FOR THE |
| | ELECTRIC ROOM EXHAUST AT RATED WALL. FBC M 607 |
| | |
| | 26) SHEET M1.6.1A: PLEASE IDENTIFY THE EXHAUST FAN FOR |
| | THE TOILETS IN THE FITNESS CENTER AREA. FBC 107.2.1 |
| | |
| | 27) SHEET M1.6.1A: PLEASE PROVIDE THE CFM?S TO THE |
| | BATHROOM GRILLE?S PROVIDED BY AHU-A4. FBC M 403.3.1.2 |
| | |
| | 28) SHEET M1.7.1A: PLEASE SHOW THE DAMPER FOR THE |
| | ELECTRIC ROOM AND STORAGE ROOM EXHAUST AT RATED WALL. |
| | FBC M 607 |
| | |
| | 29) SHEET M1.8.1A: NOTE 6 DISCUSSES SUPPLY AND EXHAUST |
| | AIR DUCTWORK SERVING THE DOAS. BUT NOTE 7 LIST THE |
| | DUCTWORK AS THE RISER FOR THE TRASH ROOM EXHAUST. IT |
| | APPEARS THAT THIS IS ONE AND THE SAME DUCTWORK. WHY |
| | WOULD THE TRASH ROOM EXHAUST BE GOING BACK TO THE DOAS |
| | UNIT? PLEASE MAKE THIS CLEARER FOR THE MECHANICAL |
| | REVIEWER. FBC 107.2.1 |
| | |
| | 30) SHEET M1.8.1B: NOTE 3 MENTIONS A DUCTLESS AIR |
| | HANDLER, THE KEYNOTE 3 SYMBOL IS IN THE ELEVATOR LOBBY |
| | AREA. PLEASE SHOW THE DUCTLESS AIR HANDLER ON THE |
| | DRAWING AND IDENTIFY IT ON THE SCHEDULES SHEET. FBC |
| | 107.2.1 |
| | |
| | 31) SHEET M1.6.1A: AHU-A4 IS SUPPLYING 2640 CFM TO THE |
| | FITNESS CENTER AREA, NO CFM?S LABELED FOR THE WOMEN?S |
| | TOILET ROOM. SHEET M0.2.1 1 SPLIT SYSTEM DX SCHEDULE |
| | INDICATES AHU_A4 SUPPLIES 1400CFM?S OF AIR FLOW. PLEASE |
| | CORRECT THIS. FBC 107.2.1 |
| | |
| | 32) SHEET M0.3.1 VENTILATION SCHEDULES: AHU-A1 |
| | INDICATES THAT 210 CFM OF OUTDOOR AIR IS REQUIRED FOR |
| | THIS AREA OF THE BUILDING. SHEET M0.2.1 SPLIT SYSTEM DX |
| | SCHEDULE INDICATES AHU-A1 IS SUPPLYING 160 CFM TO THIS |
| | AREA. PLEASE CORRECT THIS. FBC 107.2.1 |
| | |
| | 33) SHEET M0.3.1 VENTILATION SCHEDULES: AHU-A2 |
| | INDICATES THAT 87 CFM OF OUTDOOR AIR IS REQUIRED FOR |
| | THIS AREA. SHEET M0.2.1 SPLIT SYSTEM DX SCHEDULE |
| | INDICATES AHU-A2 IS SUPPLYING 80 CFM TO THIS AREA. |
| | PLEASE CORRECT THIS. FBC 107.2.1 |
| | |
| | 34) SHEET M0.3.1 VENTILATION SCHEDULES: AHU-A3 |
| | INDICATES THAT 240 CFM OF OUTDOOR AIR IS REQUIRED FOR |
| | THIS AREA. SHEET M0.2.1 SPLIT SYSTEM DX SCHEDULE |
| | INDICATES AHU-A3 IS SUPPLYING 125 CFM TO THIS AREA. |
| | PLEASE CORRECT THIS. FBC 107.2.1 |
| | |
| | 35) SHEET M0.3.1 VENTILATION SCHEDULES: AHU-A4 |
| | INDICATES THAT 385 CFM IS REQUIRED FOR THIS AREA. SHEET |
| | M0.2.1 SPLIT SYSTEM DX SCHEDULE INDICATES AHU-A4 IS |
| | SUPPLYING 160 CFM TO THIS AREA. PLEASE CORRECT THIS. |
| | FBC 107.2.1 |
| | |
| | 36) SHEET M0.2.1 AHU-B INDICATES 750-800 SUPPLY AIR |
| | FLOW. SHEET M9.1.2 UNIT TYPE 4 INDICATES AHU-B IS |
| | SUPPLYING 865 CFM FOR THIS UNIT. PLEASE CORRECT THIS. |
| | FBC EC C403.2.1 |
| | |
| | 37) SHEET M9.1.3: UNIT TYPE 5 SUPPLY DUCT FOR KITCHEN |
| | AREA IS MISSING THE SUPPLIED CFM?S. PLEASE SHOW THE |
| | CFM?S FOR THIS AREA. FBC EC C403.2.1 |
| | |
| | 38) SHEET M0.2.1 AHU-B INDICATES 750-800 SUPPLY AIR |
| | FLOW. SHEET M9.1.8 UNIT TYPE 13 INDICATES 890 CFM BEING |
| | SUPPLIED TO THIS UNIT. PLEASE CORRECT THIS. FBC EC |
| | C403.2.1 |
| | |
| | 39) SHEET M0.2.1 AHU-C INDICATES 950-100CFM OF SUPPLY |
| | AIR FLOW. SHEET M9.1.9 UNIT 15 INDICATES AHU-C IS |
| | SUPPLYING 1,050 CFM OF AIR FLOW. PLEASE CORRECT. FBC EC |
| | C403.2.1 |
| | |
| | 40) SHEET M0.2.1 AHU-C INDICATES 950-100 CFM OF SUPPLY |
| | AIR FLOW. SHEET M9.1.12 UNIT TYPE 17 INDICATES AHU-C IS |
| | SUPPLYING 1,070 CFM OF AIR FLOW. PLEASE CORRECT. FBC EC |
| | C403.2.1 |
| | |
| | 41) PLEASE PROVIDE CALCULATIONS FOR THE PARKING GARAGE |
| | VENTILATION. FBC M 404 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |