| 2020-12-13 10:04:58 | 12/13/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SHOW ON ISOMETRIC DRAWING THE LENGTH OF ALL |
| | CUT SECTIONS OF PIPE PER 2017 FBC FG SECS. 402.4.1, |
| | 402.4.2. 11. |
| | |
| | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PLEASE SPECIFY THE TYPE OF GAS (LP OR NATURAL) PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. THE SHUT-OFF VALVES ON ALL ALLIANCES NEED TO BE |
| | SHOWN IMMEDIATELY AHEAD OF EACH REGULATOR. 2017 FBC FG |
| | SEC. 409.4. |
| | |
| | 5. PLEASE LIST THE TOTAL BTU LOAD OF ALL EQUIPMENT ON |
| | THE SYSTEM. REFER TO THE 2017 FBC FG SECS. 401.8 |
| | THROUGH 402.6.1 AND TABLES 402.4 (1) THROUGH 402.4 |
| | (37). |
| | |
| | 6. PLEASE GIVE THE DISTANCE FROM THE POINT OF DELIVERY |
| | (GAS METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN |
| | THE BUILDING AND OR SYSTEM PER THE 2017 FBC FG SEC. |
| | 402.4.1. |
| | |
| | 7. PLEASE SHOW ON ISOMETRIC THE GAS RISER DETAIL 2/P |
| | 0.3.2 NOTES PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FG SEC. 304.1, 614.5 (POOL HEATER). |
| | A. IF USING COMBUSTION AIR FOR A MECHANICAL COMBUSTION |
| | AIR SUPPLY SYSTEM, THE PLANS' INFORMATION NEEDS TO |
| | INDICATE WHERE THIS COMBUSTION AIR IS BEING SUPPLIED |
| | FROM. |
| | B. IF USING LOUVERS LOCATION FOR COMBUSTION AIR, |
| | PLEASE SHOW THE LOUVERS' LOCATION AND SIZE THAT ARE |
| | BEING INSTALLED F. THE LOUVERS CANNOT BE LOCATED ON AN |
| | EXTERIOR WALL THAT IS FIRE RATED AS THE WALL'S FIRE |
| | RATING MUST BE MAINTAINED PER THE WPB AMENDMENTS TO FBC |
| | SEC.107.2.1. 61. |
| | 9. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER THE 2017 FBC FG SEC. 402.2 OR 2017 FBC |
| | RES. SEC. G2413.2. |
| | |
| | 10. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FG SEC.305.1. |
| | |
| | 11. PLEASE SHOW P 0.3.2 ISOMETRIC RISERS WHERE THE GAS |
| | PIPE IS COMING OR CONNECTING PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 12. PLEASE PLACE A NOTE ON BOTH SETS OF PLANS LISTING |
| | THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD |
| | BEING USED IN THIS SYSTEM'S DESIGN PER THE 2017 FBC FG |
| | SEC. 402.3. |
| | |
| | 13. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC |
| | RES. SEC. G2421.1. |
| | |
| | 14. PLEASE PROVIDE DETAIL OF ALL UNIONS IN FRONT OF |
| | REGULATOR 1? OF EITHER SIDE, DRIP LEG PER THE 2017 FBC |
| | RES. SEC G2421.2 OR 2017 FBC FG SEC 410.2. |
| | |
| | 15. THE CITY OF WEST PALM BEACH WILL REQUIRE THE GAS |
| | SYSTEM TO BE PURGE AND ADMINISTERED BY A CITY |
| | INSPECTOR. PLEASE DESCRIBE HOW THE PURGE WILL TAKE |
| | PLACE BEFORE DOING THIS PROCESS AND WHEN SUBMITTED TO |
| | THE PLUMBING DEPARTMENT IN ADVANCE. PLEASE PROVIDE A |
| | NOTE ON PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |