| 2020-12-02 14:18:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET ALS 6.1 - IT IS NOT CLEAR WHERE THE 2ND EXIT |
| | OFF THE RECREATIONAL DECK IS LOCATED. |
| | |
| | PLEASE REVIEW AND CLEARLY INDICATE AND ACCOUNTING FOR |
| | THE REQUIRED SEPARATION DISTANCE AND OCCUPANT LOAD. |
| | |
| | |
| | 2) SHEET ALS 1.1 - THERE IS AN INDICATION OF AN EGRESS |
| | PASSAGEWAY AT STAIR # 3. THERE ARE 3 DOORS WITHIN THIS |
| | EXIT PASSAGEWAY, ONLY 2 ARE ALLOWED. |
| | |
| | PER NFPA 101 CH 7 MEANS OF EGRESS |
| | |
| | 7.2.3.5 DISCHARGE. |
| | 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE |
| | INTO A PUBLIC |
| | WAY, INTO A YARD OR COURT HAVING DIRECT ACCESS TO A |
| | PUBLIC WAY, OR |
| | INTO AN EXIT PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE |
| | WITHOUT |
| | OPENINGS, OTHER THAN THE ENTRANCE TO THE SMOKEPROOF |
| | ENCLOSURE AND |
| | THE DOOR OPENING TO THE OUTSIDE YARD, COURT, OR PUBLIC |
| | WAY. THE EXIT |
| | PASSAGEWAY SHALL BE SEPARATED FROM THE REMAINDER OF THE |
| | BUILDING |
| | BY A 2-HOUR FIRE RESISTANCE RATING. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NAARRATIVE. |
| | |
| | |
| | 3) SHEETS P 1.0.1.A & 1.01.B - THERE ARE INDICATIONS OF |
| | UNDERGROUND FIRE LINES. |
| | |
| | ALL UNDERGROUND FIRE LINES SHALL SUBMITTED UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS AND PER NFPA 24 |
| | REQUIREMENTS |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 4) SHEET # 6.0.3 - THERE IS AN INDICATION OF A BDA |
| | SYSTEM. |
| | |
| | THE BDA SYSTEM SHALL SUBMITTED UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS AND PER NFPA 72 REQUIREMENTS |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGMENT. |
| | |
| | |
| | 5) FIRE ALARM SHEETS - THERE ARE INDICATIONS OF PULL |
| | STATIONS THROUGHOUT THE OCCUPANCY. |
| | |
| | FOR INFORMATIONAL PURPOSES AND TO REDUCE FALSE ALARMS, |
| | PER NFPA 101, CH 30 & 9 , PULL STATIONS MAY BE |
| | ELIMINATED OR REDUCED PER THE AHJ. |
| | |
| | 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 30.3.4.1 GENERAL. |
| | 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT OR |
| | WITH MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE |
| | MEETING THE |
| | REQUIREMENTS OF 30.3.4.1.2, SHALL BE PROVIDED WITH A |
| | FIRE ALARM |
| | SYSTEM IN ACCORDANCE WITH SECTION 9.6, EXCEPT AS |
| | MODIFIED BY |
| | 30.3.4.2 THROUGH 30.3.4.5. |
| | |
| | 30.3.4.2 INITIATION. |
| | 30.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE BY |
| | MANUAL MEANS IN ACCORDANCE WITH 9.6.2, UNLESS THE |
| | BUILDING |
| | COMPLIES WITH 30.3.4.2.2. |
| | |
| | 30.3.4.2.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 30.3.5, |
| | REQUIRED FIRE ALARM SYSTEMS SHALL BE INITIATED UPON |
| | OPERATION OF |
| | THE AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE |
| | DETECTION OR |
| | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM |
| | SYSTEM IN |
| | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN |
| | ONE MANUAL |
| | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY |
| | HAVING |
| | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE |
| | ALARM SIGNAL. |
| | |
| | BELOW IS THE APPENDIX NARRATIVE FOR INFORMATIONAL |
| | PURPOSES. |
| | |
| | A.9.6.2.6 THE MANUAL FIRE ALARM BOX REQUIRED BY 9.6.2.6 |
| | IS INTENDED |
| | TO PROVIDE A MEANS TO MANUALLY ACTIVATE THE FIRE ALARM |
| | SYSTEM WHEN THE AUTOMATIC FIRE DETECTION SYSTEM OR |
| | WATERFLOW DEVICES |
| | ARE OUT OF SERVICE DUE TO MAINTENANCE OR TESTING, OR |
| | WHERE |
| | HUMAN DISCOVERY OF THE FIRE PRECEDES AUTOMATIC |
| | SPRINKLER SYSTEM |
| | OR AUTOMATIC DETECTION SYSTEM ACTIVATION. WHERE THE |
| | FIRE ALARM |
| | SYSTEM IS CONNECTED TO A MONITORING FACILITY, THE |
| | MANUAL FIRE |
| | ALARM BOX REQUIRED BY 9.6.2.6 SHOULD BE CONNECTED TO A |
| | SEPARATE |
| | CIRCUIT THAT IS NOT PLACED ?ON TEST? WHEN THE DETECTION |
| | OR SPRINKLER |
| | SYSTEM IS PLACED ON TEST. THE MANUAL FIRE ALARM BOX |
| | SHOULD BE |
| | LOCATED IN AN AREA THAT IS ACCESSIBLE TO OCCUPANTS OF |
| | THE BUILDING |
| | AND SHOULD NOT BE LOCKED. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE TO |
| | COORDINATE LOCATIONS WITH THE OFFICE OF THE FIRE |
| | MARSHAL. |
| | |
| | SHOULD THE EOR OR OWNER NOT WNAT TO REDUCE LOCATIONS, |
| | PROVIDE THAT APPLICABLE NOTE. |
| | |
| | |
| | 6) FIRE ALARM SHEETS - THERE ARE INDICATIONS OF SMOKE |
| | DETECTION THROUGHOUT THE OCCUPANCY. |
| | |
| | FOR INFORMATIONAL PURPOSES AND TO REDUCE FALSE ALARMS, |
| | PER NFPA 101, CH 30 & 9 , COMPLETE SMOKE DETECTION IS |
| | NOT REQUIRED MAY BE ELIMINATED OR REDUCED. |
| | |
| | 30.3.4.4 DETECTION. (RESERVED) |
| | 30.3.4.5* SMOKE ALARMS. SMOKE ALARMS SHALL BE INSTALLED |
| | IN |
| | ACCORDANCE WITH 9.6.2.10 IN EVERY SLEEPING AREA, |
| | OUTSIDE EVERY |
| | SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE |
| | BEDROOMS, AND ON |
| | ALL LEVELS OF THE DWELLING UNIT, INCLUDING BASEMENTS. |
| | |
| | 9.6.2.9 WHERE A TOTAL (COMPLETE) COVERAGE SMOKE |
| | DETECTION |
| | SYSTEM IS REQUIRED BY ANOTHER SECTION OF THIS CODE, |
| | AUTOMATIC |
| | DETECTION OF SMOKE IN ACCORDANCE WITH NFPA 72, NATIONAL |
| | FIRE |
| | ALARM AND SIGNALING CODE, SHALL BE PROVIDED IN ALL |
| | OCCUPIABLE |
| | AREAS IN ENVIRONMENTS THAT ARE SUITABLE FOR PROPER |
| | SMOKE DETECTOR |
| | OPERATION |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE TO |
| | COORDINATE LOCATIONS WITH THE OFFICE OF THE FIRE |
| | MARSHAL. |
| | |
| | SHOULD THE EOR OR OWNER NOT WNAT TO REDUCE LOCATIONS, |
| | PROVIDE THAT APPLICABLE NOTE. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |