| Plan Review Notes For Permit 20101431 |
| Permit Number |
20101431 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-19 16:27:57 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E02.2A | | | | | | 1) IS PANEL H1 A MAIN? | | | | | | 2) NOT ALL WIRE SIZES SHOWN ON RISER 215.5 | | | | | | 3) FAULT CURRENT CALCULATION NEEDED FOR SERVICE TO SHOW | | | CORRECT AIC RATING 110.9, 110.10 | | | | | | 4) ARC FLSH MITIGATION REQUIRED PER 240.87 FOR MAINS 1 | | | THRU 4 | | | | | | PAGESE02.1 B AND C | | | | | | 1) NOT ALL WIRE SIZES SHOWN ON RISER 215.5 | | | | | | PAGE E1.81A | | | | | | OUTLETS ON ROOF TO BE WITHIN 25' OF AC EQUIPMENT 210.63 | | | | | | PAGES E9.1.1 THROUGH E9.1,14 | | | | | | 1) SMOKE ALARMS ARE CLOSE TO KITCHEN RANGE NEED TO | | | INSTALLED PER NFPA 72 29.8.3.4 (4) | | | | | | 2) SMOKE ALARMS INSTLLED TO CLOSE TO THE BATHROOM DOOR | | | SEE NFPA 72 29.8.3.4 (6) | | | | | | GENERAL NOTE | | | | | | FOLLOWING REQUIRE SEPARATE PERMITS FIRE ALARM, BDA | | | SYSTEM, POOL, GENERATOR, LOW VOLTAGE SYSTEMS, LIGHTNING | | | PROTECTION, SITE LIGHTING |
|