2020-11-19 16:27:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E02.2A
  
 1) IS PANEL H1 A MAIN?
  
 2) NOT ALL WIRE SIZES SHOWN ON RISER 215.5
  
 3) FAULT CURRENT CALCULATION NEEDED FOR SERVICE TO SHOW
 CORRECT AIC RATING 110.9, 110.10
  
 4) ARC FLSH MITIGATION REQUIRED PER 240.87 FOR MAINS 1
 THRU 4
  
 PAGESE02.1 B AND C
  
 1) NOT ALL WIRE SIZES SHOWN ON RISER 215.5
  
 PAGE E1.81A
  
 OUTLETS ON ROOF TO BE WITHIN 25' OF AC EQUIPMENT 210.63
  
 PAGES E9.1.1 THROUGH E9.1,14
  
 1) SMOKE ALARMS ARE CLOSE TO KITCHEN RANGE NEED TO
 INSTALLED PER NFPA 72 29.8.3.4 (4)
  
 2) SMOKE ALARMS INSTLLED TO CLOSE TO THE BATHROOM DOOR
 SEE NFPA 72 29.8.3.4 (6)
  
 GENERAL NOTE
  
 FOLLOWING REQUIRE SEPARATE PERMITS FIRE ALARM, BDA
 SYSTEM, POOL, GENERATOR, LOW VOLTAGE SYSTEMS, LIGHTNING
 PROTECTION, SITE LIGHTING