| 2020-12-04 13:42:23 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) & CITY OF W.P.B. |
| | CHAPTER 1 AMENDMENTS |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | 345 BANYAN BLVD. |
| | PERMIT #20101431 |
| | 170 MPH, EXPOSURE "D" |
| | FLOOD ZONE "X" |
| | HIGH-RISE BLDG. PER FBC 403 (15 STORIES, 177'-8" TO TOP |
| | OF OCCUPIED FLOOR, 188'-0" TO HIGHEST ROOF OF OCCUPIED |
| | SPACE) |
| | CONSTRUCTION TYPE: IA (REDUCED TO IB FOR FIRE |
| | RESISTANCE RATING OF BUILDING MATERIALS PER FBC |
| | 403.2.1.1) |
| | OCCUPANCY TYPE: (MIXED USE) R-2, S-2, S-1, M, B, A-3 |
| | BLDG. AND GARAGE ARE FULLY SPRINKLERED |
| | GARAGE IS ENCLOSED |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THIS PROJECT IS A THRESHOLD BUILDING PER FL S. S. |
| | 553.71(7) "THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DEFINED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF |
| | GREATER THAN 500 PERSONS. |
| | |
| | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION |
| | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL THRESHOLD BUILDING INSPECTION PLAN IS |
| | TO PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE. |
| | |
| | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | |
| | J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL |
| | BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER |
| | 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS. |
| | |
| | 2) ART IN PUBLIC PLACES |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT |
| | 822-1515 OR E-MAIL: [email protected] |
| | |
| | 3) SUBMIT A SIGNED AND SEALED GEOTECHNICAL REPORT FROM |
| | A FLORIDA LICENSED ENGINEER WITH THE RECOMMENDED SOIL |
| | PREPARATION METHOD AND THE SOIL BEARING CAPACITY. FBC |
| | 1801.2 |
| | |
| | 4) SPECIFY HOW COMPLIANCE WITH FBC CHAPTER 33 |
| | SAFEGUARDS DURING CONSTRUCTION FOR THE FOUNDATION |
| | PERMIT WILL BE MET. PROVIDE A MOT (MANAGEMENT OF |
| | TRAFFIC) PLAN. RIGHT OF WAY PERMITS WILL BE REQUIRED TO |
| | CLOSE SIDEWALKS, STREETS, ETC. |
| | |
| | 5) IN ORDER TO AVOID ANY CONFUSION, PLEASE IDENTIFY THE |
| | VERTICAL DATUM FOR THE ELEVATIONS ON THE SITE PLANS. I |
| | DID SEE A SMALL NOTE ON THE ARCHITECTURAL PLANS THAT |
| | ALL ELEVATIONS ARE NAVD. FBC 107.2.1 |
| | |
| | 6) THE EXIT PASSAGEWAY AT STAIR 3 IS INCORRECTLY |
| | LABELED AS AN EGRESS PASSAGEWAY. PLEASE CHANGE LABEL TO |
| | EXIT PASSAGEWAY AND ADD NOTE THAT OPENINGS AND |
| | PENETRATIONS INTO IT ARE ONLY ALLOWED FOR EXITING |
| | PURPOSES AND ITEMS SERVING THE PASSAGEWAY. AN EXIT |
| | PASSAGEWAY IS AN EXTENSION OF THE ENCLOSED INTERIOR |
| | EXIT STAIRWAY AND HAS REQUIREMENTS SIMILAR TO THE |
| | STAIRWAY. SEE FBC 1023.1 AND 1024. |
| | |
| | 7) THE EXIT DISCHARGE FROM STAIR 3 IS NOT TO A PUBLIC |
| | WAY. IT APPEARS THAT THE OCCUPANTS WILL NEED TO TRAVEL |
| | THROUGH THE ADJACENT PROPERTY TO REACH THE PUBLIC WAY. |
| | [A] PUBLIC WAY. A STREET, ALLEY OR OTHER PARCEL OF LAND |
| | OPEN TO THE OUTSIDE AIR LEADING TO A STREET, THAT HAS |
| | BEEN DEEDED, DEDICATED OR OTHERWISE PERMANENTLY |
| | APPROPRIATED TO THE PUBLIC FOR PUBLIC USE AND WHICH HAS |
| | A CLEAR WIDTH AND HEIGHT OF NOT LESS THAN 10 FEET (3048 |
| | MM). PLEASE CLARIFY. FBC 1022 |
| | |
| | 8) THE EAST WALL IS NOT LISTED IN THE FIRE SEPARATION |
| | TABLE 705.8 ON SHEET ALS.0.1. FBC 107.2.1 |
| | |
| | 9) THE SITE PLANS APPEAR TO SHOW A PORTION OF THE EAST |
| | WALL IS ON THE PROPERTY LINE. THE DOORS TO THE |
| | TRANSFORMER ROOM SWING OUT OVER THE PROPERTY LINE WHICH |
| | IS NOT ALLOWED. PLEASE PROVIDE CLARIFICATION. FBC |
| | 107.2.1 |
| | |
| | 10) THERE ARE MULTIPLE OPENINGS IN THE EAST WALL THAT |
| | ARE NOT ALLOWED BASED THE FIRE SEPARATION DISTANCE AND |
| | TABLE 705.8. NO OPENINGS ARE ALLOWED FROM 0<3 FEET AND |
| | 15 PERCENT FROM 3<5 FEET. PROVIDE CALCULATIONS FOR THE |
| | ALLOWABLE AREA OF OPENINGS ON THE EAST AND NORTH WALLS |
| | OF THE BUILDING. FBC 107.2.1.2 |
| | |
| | 11) PLEASE REVISE GENERAL NOTE 21 ON SHEET ALS.0.1 TO |
| | REFERENCE THE 2017 FBC ACCESSIBILITY RATHER THAN THE |
| | 2003 IBC FOR ACCESSIBILITY. |
| | |
| | 12) PLEASE REVISE THE NOTES ON ALS.0.2 THAT REFERENCE |
| | THE 2012 N.C. BUILDING CODE TO THE 2017 FBC. |
| | |
| | 13) SHOW COMPLIANCE. FBC 3002.4 REQUIRES ANY BUILDING |
| | THAT IS MORE THAN THREE STORIES HIGH OR IN WHICH THE |
| | VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING |
| | AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET TO BE |
| | CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR |
| | THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE |
| | DEPARTMENT ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL |
| | BE OF A SIZE AND ARRANGEMENT TO ACCOMMODATE AN |
| | AMBULANCE STRETCHER 24 INCHES BY 76 INCHES WITH NOT |
| | LESS THAN 5-INCH RADIUS CORNERS, IN THE HORIZONTAL, |
| | OPEN POSITION AND SHALL BE IDENTIFIED BY THE |
| | INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES |
| | (STAR OF LIFE). |
| | |
| | 14) THE ELEVATOR LOBBIES HAVE DIMENSIONS THAT ARE LESS |
| | THAN THE REQUIRED 8 FEET. 3007.6.4 LOBBY SIZE. |
| | REGARDLESS OF THE NUMBER OF FIRE SERVICE ACCESS |
| | ELEVATORS SERVED BY THE SAME ELEVATOR LOBBY, THE |
| | ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE |
| | NOT LESS THAN 150 SQUARE FEET (14 M2) IN AN AREA WITH A |
| | DIMENSION OF NOT LESS THAN 8 FEET (2440 MM). SEE SHEET |
| | A6.1.2 (PG. 157) AND OTHER SHEETS. |
| | |
| | 15) SHOW COMPLIANCE. 403.6.1 FIRE SERVICE ACCESS |
| | ELEVATOR. IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN |
| | 120 FEET (36 576 MM), MEASURED FROM THE ELEVATION OF |
| | STREET-LEVEL ACCESS TO THE LEVEL OF THE HIGHEST |
| | OCCUPIABLE FLOOR, NO FEWER THAN TWO FIRE SERVICE ACCESS |
| | ELEVATORS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 3007. ALL REMAINING ELEVATORS, IF ANY, SHALL BE |
| | PROVIDED WITH PHASE I AND II EMERGENCY OPERATION. EACH |
| | FIRE SERVICE ACCESS ELEVATOR SHALL HAVE A CAPACITY OF |
| | NOT LESS THAN 3,500 POUNDS (1588 KG). |
| | |
| | 16) ON SHEET ALS.1.1 THE MAXIMUM OVERALL DIAGONAL |
| | DIMENSION OF THE LOBBY AREA NEEDS TO INCLUDE THE |
| | MANAGERS OFFICE, WHICH IS PART OF THAT AREA. THE |
| | LONGEST DIAGONAL SHOULD BE TO THE EXTERIOR WALLS OFNTHE |
| | AREA FROM THE MANAGER'S OFFICE TO THE SOUTHEAST CORNER |
| | OF THE LOBBY. FBC 1007.1.1 TWO EXITS OR EXIT ACCESS |
| | DOORWAYS. |
| | |
| | 17) ON SHEET ALS.4.1 THE SEPARATION DISTANCE OF THE TWO |
| | EXITS FROM UNIT 15 IS SHOWN ON THE PLANS, HOWEVER, THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE UNIT IS NOT |
| | PROVIDED. FBC 107.2.3 |
| | |
| | 18) ON ALL LIFE SAFETY PLANS, SPECIFY THE COMMON PATH |
| | OF TRAVEL DISTANCE FROM THE MOST REMOTE POINT OF THE |
| | BALCONIES IN THE LARGER UNITS AND SHOW THE EXIT ACCESS |
| | TRAVEL DISTANCE FROM THE MOST REMOTE POINT OF THE MOST |
| | REMOTE UNIT ON THE FLOOR TO THE NEAREST EXIT COMPLIES |
| | WITH FBC 1017. |
| | |
| | 19) ON ALL LIFE SAFETY PLANS, SPECIFY THE EXIT ACCESS |
| | TRAVEL DISTANCES IN THE PARKING GARAGE ON THE PLANS TO |
| | COMPLY WITH FBC 1017. |
| | |
| | 20) ON SHEET ALS.6.1, THE EXIT PATH OF TRAVEL IS NOT |
| | SHOWN FROM THE MOST REMOTE POINT OF THE BALCONY IN UNIT |
| | 8. FBC 1017 |
| | |
| | 21) ON SHEET ALS.7.1, THE MAXIMUM OVERALL DIAGONAL |
| | DIMENSION OF THE BUILDING AND THE 1/3 DIAGONAL EXIT |
| | SEPARATION DISTANCE ARE NOT PROVIDED. FBC 107.2.3 |
| | |
| | 22) ON SHEET ALS.8.1, SPECIFY THE TOTAL OCCUPANT LOAD |
| | IN THE TABLE. IT APPEARS THAT THE TOTAL LOAD IS 94 |
| | OCCUPANTS. THE NUMBERS SPECIFIED AT THE EXIT STAIRS ARE |
| | FOR ONLY 47 OCCUPANTS. PLEASE CORRECT. FBC 107.2.3 |
| | |
| | 23) THE MEAN ROOF HEIGHT IS NOT SPECIFIED IN THE GN - |
| | DESIGNER LOADS TABLE ON SHEET S0.1. (PG 272). FBC |
| | 107.2.1 |
| | |
| | 24) ON SHEET S0.1, CONCRETE NOTE #1 NEEDS TO BE UPDATED |
| | TO THE 2017 FBC. FBC 107 |
| | |
| | 25) ON SHEET S0.0.5, NOTE #5 IN THE WIND DIAGRAM NOTES |
| | SPECIFIES THE MEAN ROOF HEIGHT AS 118'-2" AND THE PLANS |
| | LIST 188'-0" AS THE HIGHEST ROOF OF THE OCCUPIED SPACE. |
| | PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 26) THE WASTE (TRASH) CHUTE IS REQUIRED TO HAVE A 2 |
| | HOUR FIRE RESISTIVE RATING PER FBC 713.4 AND THE CHUTE |
| | ACCESS ROOMS ARE REQUIRED TO BE A MINIMUM 1 HOUR FIRE |
| | BARRIER PER FBC 713.13. SOME OF LIFE SAFETY PLANS |
| | SHEETS DO NOT CLEARLY SHOW THIS. PLEASE CORRECT. FBC |
| | 107.2.1 |
| | |
| | 27) SHOW COMPLIANCE WITH FBC 2304.12 FOR TERMITE |
| | PROTECTION. |
| | |
| | 28) VERIFY THE REQUIRED VERTICAL CLEARANCE OF 98 INCHES |
| | FOR THE VAN PARKING SPACE, ACCESS AISLE AND VEHICULAR |
| | ROUTE SERVING IT AS REQUIRED BY FBC ACCESSIBILITY |
| | SECTION 502.5. THERE HAVE BEEN ISSUES WITH EQUIPMENT OR |
| | SYSTEMS INSTALLED BELOW THE REQUIRED 98" IN THESE AREAS |
| | OF PARKING GARAGES. PLEASE PROVIDE NOTES ON THE |
| | DRAWINGS TO HELP AVOID THIS ISSUE. |
| | |
| | 29) THE MICROWAVE OVEN IN THE WORK ROOM SHOWN IN |
| | ELEVATION 6 ON SHEET A9.50.5 DOES NOT APPEAR TO COMPLY |
| | WITH THE REQUIRED REACH RANGES OF FBC ACCESSIBILITY |
| | SECTIONS 308, 309.3 AND 804.6.2. |
| | |
| | 30) SHOW COMPLIANCE FBC ACCESSIBILITY SECTION 242 FOR |
| | ACCESSIBLE ENTRY INTO THE POOL OR SPECIFY ON THE PLANS |
| | WHY IT IS NOT REQUIRED. COMMUNITY POOLS THAT ARE |
| | ASSOCIATED WITH A PRIVATE RESIDENTIAL COMMUNITY THAT DO |
| | NOT RECEIVE GOVERNMENTAL FINANCIAL ASSISTANCE OR |
| | SPONSORSHIP AND ARE LIMITED TO THE EXCLUSIVE OF |
| | RESIDENTS AND THEIR GUESTS ARE NOT COVERED BY THE ADA |
| | ACCESSIBILITY REQUIREMENTS, INCLUDING PROVISIONS FOR |
| | POOL LIFTS OR SLOPED ENTRIES. IF A SWIMMING POOL |
| | LOCATED IN A RESIDENTIAL COMMUNITY IS MADE AVAILABLE TO |
| | THE PUBLIC FOR RENTAL OR USE IT IS REQUIRED TO COMPLY |
| | WITH TITLE II OF THE ADA. SPECIFY ON THE PLANS THE |
| | FORMER OR SHOW COMPLIANCE WITH THE LATTER STATEMENTS. |
| | SEE DECLARATORY STATEMENT, DS 2013-011. (NOTE: A |
| | SEPARATE PERMIT WILL BE REQUIRED FOR THE POOL.) |
| | |
| | 31) THE MAXIMUM DISTANCE FROM THE WATER'S EDGE OF THE |
| | SWIMMING POOL TO THE RESTROOMS IS NOT SHOWN CORRECTLY |
| | ON THE PLAN SHEET ALS.6.1. FBC454.1.6.1 THE ENTRY DOORS |
| | OF ALL RESTROOMS SHALL BE LOCATED WITHIN A 200-FOOT (60 |
| | 960 MM) WALKING DISTANCE OF THE NEAREST WATER'S EDGE OF |
| | EACH POOL SERVED BY THE FACILITIES. PLEASE CORRECT. |
| | |
| | 32) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE |
| | DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE |
| | SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT |
| | BEFORE THEY CAN BE INSTALLED. |
| | |
| | 33) FBC 107.3.4.1 DEFERRED SUBMITTALS. (I NOTED THAT |
| | THERE IS A LIST OF DEFERRED SUBMITTALS AND SEPARATE |
| | PERMITS ON SHEET ALS.0.1) FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 34) SHOW COMPLIANCE WITH FBC SECTION 1207 SOUND |
| | TRANSMISSION, 1207.2 AIR-BORNE SOUND AND 1207.3 |
| | STRUCTURE-BORNE SOUND. TEST REPORTS WILL NEED TO BE |
| | SUBMITTED FOR THE SOUND INSULATION THAT WILL BE |
| | INSTALLED UNDER FINISH FLOORING. |
| | |
| | 35) IN ORDER TO VERIFY THE BUILDING VALUATION, PLEASE |
| | PROVIDE AREA TABULATIONS FOR THE ENTIRE BUILDING. |
| | PLEASE SEPARATE AREA TABULATIONS BY OCCUPANCY TYPE. FBC |
| | 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 36) SEPARATE PERMITS, REVIEWS AND FEES ARE REQUIRED FOR |
| | SOME ITEMS THAT MAY HAVE BEEN INCLUDED IN THE VALUE FOR |
| | THIS PROJECT. ITEMS SUCH AS FIRE ALARM, FIRE SPRINKLER, |
| | LOW VOLTAGE, LANDSCAPING, IRRIGATION AND ALL ITEMS |
| | OTHER THAN BUILDING, MECHANICAL, ELECTRIC AND PLUMBING. |
| | PLEASE PROVIDE A COST BREAKDOWN SO THAT WE CAN DEDUCT |
| | THESE ITEMS FROM THE PERMIT VALUE SO THAT YOU WILL NOT |
| | BE CHARGED TWICE FOR THE SAME ITEM. |
| | |
| | 37) THE P.B.C. PROPERTY APPRAISER SHOWS THIS PROJECT IS |
| | LOCATED ON A LARGER PARCEL THAN THE SITE PLAN AND |
| | SURVEY THAT WAS SUBMITTED. IS THIS PARCEL BEING |
| | SUBDIVIDED OR TO REMAIN AS ONE PARCEL WITH TWO |
| | BUILDINGS ON IT? PLEASE CLARIFY. |
| | |
| | 38) THE ADDRESS OF THE PROJECT HAS BEEN CHANGED TO 345 |
| | BANYAN BLVD. PLEASE CHANGE THE ADDRESS IN THE TITLE |
| | BLOCK OF THE PLANS. THE DESCRIPTION OF THE PROJECT AS |
| | PARKING LOT REDEVELOPEMENT IN THE TITLE BLOCK IS NOT |
| | SPECIFIC. A MORE ACCURATE DISCRIPTION WOULD BE A NEW |
| | RESIDENTIAL HIGH RISE BUILDING AND PARKING GARAGE. FBC |
| | 107.2.1 |
| | |
| | 39) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | ****PROVISOS**** |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO |
| | INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH |
| | PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND |
| | ENGINEERING (IF APPLICABLE). |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | |
| | DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE |
| | FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS |
| | SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR |
| | PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS, |
| | STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS |
| | REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW |
| | AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION. |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH |
| | PRESSURES SHOWN ON SHEET S0.0.5) |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5 |
| | PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, |
| | INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS |
| | COMPLY WITH MINIMUM DESIGN PRESSURES. |
| | |
| | SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | PARKING LOT |
| | SWIMMING POOLS |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A PDF |
| | VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL. |
| | |
| | AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR |
| | TO C.O. |
| | |
| | SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED |
| | TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS |
| | TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE |
| | POUR. |
| | |
| | A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED |
| | TO BE PROVIDED PRIOR TO INSTALLATION. |
| | |
| | CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |