Plan Review Notes
Plan Review Notes For Permit 20101431
Permit Number 20101431
Review Stop B
Sequence Number 1
Notes
Date Text
2020-12-04 13:42:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017) & CITY OF W.P.B.
 CHAPTER 1 AMENDMENTS
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 345 BANYAN BLVD.
 PERMIT #20101431
 170 MPH, EXPOSURE "D"
 FLOOD ZONE "X"
 HIGH-RISE BLDG. PER FBC 403 (15 STORIES, 177'-8" TO TOP
 OF OCCUPIED FLOOR, 188'-0" TO HIGHEST ROOF OF OCCUPIED
 SPACE)
 CONSTRUCTION TYPE: IA (REDUCED TO IB FOR FIRE
 RESISTANCE RATING OF BUILDING MATERIALS PER FBC
 403.2.1.1)
 OCCUPANCY TYPE: (MIXED USE) R-2, S-2, S-1, M, B, A-3
 BLDG. AND GARAGE ARE FULLY SPRINKLERED
 GARAGE IS ENCLOSED
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT IS A THRESHOLD BUILDING PER FL S. S.
 553.71(7) "THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DEFINED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF
 GREATER THAN 500 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL THRESHOLD BUILDING INSPECTION PLAN IS
 TO PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 2) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT
 822-1515 OR E-MAIL: [email protected]
  
 3) SUBMIT A SIGNED AND SEALED GEOTECHNICAL REPORT FROM
 A FLORIDA LICENSED ENGINEER WITH THE RECOMMENDED SOIL
 PREPARATION METHOD AND THE SOIL BEARING CAPACITY. FBC
 1801.2
  
 4) SPECIFY HOW COMPLIANCE WITH FBC CHAPTER 33
 SAFEGUARDS DURING CONSTRUCTION FOR THE FOUNDATION
 PERMIT WILL BE MET. PROVIDE A MOT (MANAGEMENT OF
 TRAFFIC) PLAN. RIGHT OF WAY PERMITS WILL BE REQUIRED TO
 CLOSE SIDEWALKS, STREETS, ETC.
  
 5) IN ORDER TO AVOID ANY CONFUSION, PLEASE IDENTIFY THE
 VERTICAL DATUM FOR THE ELEVATIONS ON THE SITE PLANS. I
 DID SEE A SMALL NOTE ON THE ARCHITECTURAL PLANS THAT
 ALL ELEVATIONS ARE NAVD. FBC 107.2.1
  
 6) THE EXIT PASSAGEWAY AT STAIR 3 IS INCORRECTLY
 LABELED AS AN EGRESS PASSAGEWAY. PLEASE CHANGE LABEL TO
 EXIT PASSAGEWAY AND ADD NOTE THAT OPENINGS AND
 PENETRATIONS INTO IT ARE ONLY ALLOWED FOR EXITING
 PURPOSES AND ITEMS SERVING THE PASSAGEWAY. AN EXIT
 PASSAGEWAY IS AN EXTENSION OF THE ENCLOSED INTERIOR
 EXIT STAIRWAY AND HAS REQUIREMENTS SIMILAR TO THE
 STAIRWAY. SEE FBC 1023.1 AND 1024.
  
 7) THE EXIT DISCHARGE FROM STAIR 3 IS NOT TO A PUBLIC
 WAY. IT APPEARS THAT THE OCCUPANTS WILL NEED TO TRAVEL
 THROUGH THE ADJACENT PROPERTY TO REACH THE PUBLIC WAY.
 [A] PUBLIC WAY. A STREET, ALLEY OR OTHER PARCEL OF LAND
 OPEN TO THE OUTSIDE AIR LEADING TO A STREET, THAT HAS
 BEEN DEEDED, DEDICATED OR OTHERWISE PERMANENTLY
 APPROPRIATED TO THE PUBLIC FOR PUBLIC USE AND WHICH HAS
 A CLEAR WIDTH AND HEIGHT OF NOT LESS THAN 10 FEET (3048
 MM). PLEASE CLARIFY. FBC 1022
  
 8) THE EAST WALL IS NOT LISTED IN THE FIRE SEPARATION
 TABLE 705.8 ON SHEET ALS.0.1. FBC 107.2.1
  
 9) THE SITE PLANS APPEAR TO SHOW A PORTION OF THE EAST
 WALL IS ON THE PROPERTY LINE. THE DOORS TO THE
 TRANSFORMER ROOM SWING OUT OVER THE PROPERTY LINE WHICH
 IS NOT ALLOWED. PLEASE PROVIDE CLARIFICATION. FBC
 107.2.1
  
 10) THERE ARE MULTIPLE OPENINGS IN THE EAST WALL THAT
 ARE NOT ALLOWED BASED THE FIRE SEPARATION DISTANCE AND
 TABLE 705.8. NO OPENINGS ARE ALLOWED FROM 0<3 FEET AND
 15 PERCENT FROM 3<5 FEET. PROVIDE CALCULATIONS FOR THE
 ALLOWABLE AREA OF OPENINGS ON THE EAST AND NORTH WALLS
 OF THE BUILDING. FBC 107.2.1.2
  
 11) PLEASE REVISE GENERAL NOTE 21 ON SHEET ALS.0.1 TO
 REFERENCE THE 2017 FBC ACCESSIBILITY RATHER THAN THE
 2003 IBC FOR ACCESSIBILITY.
  
 12) PLEASE REVISE THE NOTES ON ALS.0.2 THAT REFERENCE
 THE 2012 N.C. BUILDING CODE TO THE 2017 FBC.
  
 13) SHOW COMPLIANCE. FBC 3002.4 REQUIRES ANY BUILDING
 THAT IS MORE THAN THREE STORIES HIGH OR IN WHICH THE
 VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING
 AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET TO BE
 CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR
 THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE
 DEPARTMENT ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL
 BE OF A SIZE AND ARRANGEMENT TO ACCOMMODATE AN
 AMBULANCE STRETCHER 24 INCHES BY 76 INCHES WITH NOT
 LESS THAN 5-INCH RADIUS CORNERS, IN THE HORIZONTAL,
 OPEN POSITION AND SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES
 (STAR OF LIFE).
  
 14) THE ELEVATOR LOBBIES HAVE DIMENSIONS THAT ARE LESS
 THAN THE REQUIRED 8 FEET. 3007.6.4 LOBBY SIZE.
 REGARDLESS OF THE NUMBER OF FIRE SERVICE ACCESS
 ELEVATORS SERVED BY THE SAME ELEVATOR LOBBY, THE
 ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE
 NOT LESS THAN 150 SQUARE FEET (14 M2) IN AN AREA WITH A
 DIMENSION OF NOT LESS THAN 8 FEET (2440 MM). SEE SHEET
 A6.1.2 (PG. 157) AND OTHER SHEETS.
  
 15) SHOW COMPLIANCE. 403.6.1 FIRE SERVICE ACCESS
 ELEVATOR. IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN
 120 FEET (36 576 MM), MEASURED FROM THE ELEVATION OF
 STREET-LEVEL ACCESS TO THE LEVEL OF THE HIGHEST
 OCCUPIABLE FLOOR, NO FEWER THAN TWO FIRE SERVICE ACCESS
 ELEVATORS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 3007. ALL REMAINING ELEVATORS, IF ANY, SHALL BE
 PROVIDED WITH PHASE I AND II EMERGENCY OPERATION. EACH
 FIRE SERVICE ACCESS ELEVATOR SHALL HAVE A CAPACITY OF
 NOT LESS THAN 3,500 POUNDS (1588 KG).
  
 16) ON SHEET ALS.1.1 THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE LOBBY AREA NEEDS TO INCLUDE THE
 MANAGERS OFFICE, WHICH IS PART OF THAT AREA. THE
 LONGEST DIAGONAL SHOULD BE TO THE EXTERIOR WALLS OFNTHE
 AREA FROM THE MANAGER'S OFFICE TO THE SOUTHEAST CORNER
 OF THE LOBBY. FBC 1007.1.1 TWO EXITS OR EXIT ACCESS
 DOORWAYS.
  
 17) ON SHEET ALS.4.1 THE SEPARATION DISTANCE OF THE TWO
 EXITS FROM UNIT 15 IS SHOWN ON THE PLANS, HOWEVER, THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE UNIT IS NOT
 PROVIDED. FBC 107.2.3
  
 18) ON ALL LIFE SAFETY PLANS, SPECIFY THE COMMON PATH
 OF TRAVEL DISTANCE FROM THE MOST REMOTE POINT OF THE
 BALCONIES IN THE LARGER UNITS AND SHOW THE EXIT ACCESS
 TRAVEL DISTANCE FROM THE MOST REMOTE POINT OF THE MOST
 REMOTE UNIT ON THE FLOOR TO THE NEAREST EXIT COMPLIES
 WITH FBC 1017.
  
 19) ON ALL LIFE SAFETY PLANS, SPECIFY THE EXIT ACCESS
 TRAVEL DISTANCES IN THE PARKING GARAGE ON THE PLANS TO
 COMPLY WITH FBC 1017.
  
 20) ON SHEET ALS.6.1, THE EXIT PATH OF TRAVEL IS NOT
 SHOWN FROM THE MOST REMOTE POINT OF THE BALCONY IN UNIT
 8. FBC 1017
  
 21) ON SHEET ALS.7.1, THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE BUILDING AND THE 1/3 DIAGONAL EXIT
 SEPARATION DISTANCE ARE NOT PROVIDED. FBC 107.2.3
  
 22) ON SHEET ALS.8.1, SPECIFY THE TOTAL OCCUPANT LOAD
 IN THE TABLE. IT APPEARS THAT THE TOTAL LOAD IS 94
 OCCUPANTS. THE NUMBERS SPECIFIED AT THE EXIT STAIRS ARE
 FOR ONLY 47 OCCUPANTS. PLEASE CORRECT. FBC 107.2.3
  
 23) THE MEAN ROOF HEIGHT IS NOT SPECIFIED IN THE GN -
 DESIGNER LOADS TABLE ON SHEET S0.1. (PG 272). FBC
 107.2.1
  
 24) ON SHEET S0.1, CONCRETE NOTE #1 NEEDS TO BE UPDATED
 TO THE 2017 FBC. FBC 107
  
 25) ON SHEET S0.0.5, NOTE #5 IN THE WIND DIAGRAM NOTES
 SPECIFIES THE MEAN ROOF HEIGHT AS 118'-2" AND THE PLANS
 LIST 188'-0" AS THE HIGHEST ROOF OF THE OCCUPIED SPACE.
 PLEASE CLARIFY. FBC 107.2.1
  
 26) THE WASTE (TRASH) CHUTE IS REQUIRED TO HAVE A 2
 HOUR FIRE RESISTIVE RATING PER FBC 713.4 AND THE CHUTE
 ACCESS ROOMS ARE REQUIRED TO BE A MINIMUM 1 HOUR FIRE
 BARRIER PER FBC 713.13. SOME OF LIFE SAFETY PLANS
 SHEETS DO NOT CLEARLY SHOW THIS. PLEASE CORRECT. FBC
 107.2.1
  
 27) SHOW COMPLIANCE WITH FBC 2304.12 FOR TERMITE
 PROTECTION.
  
 28) VERIFY THE REQUIRED VERTICAL CLEARANCE OF 98 INCHES
 FOR THE VAN PARKING SPACE, ACCESS AISLE AND VEHICULAR
 ROUTE SERVING IT AS REQUIRED BY FBC ACCESSIBILITY
 SECTION 502.5. THERE HAVE BEEN ISSUES WITH EQUIPMENT OR
 SYSTEMS INSTALLED BELOW THE REQUIRED 98" IN THESE AREAS
 OF PARKING GARAGES. PLEASE PROVIDE NOTES ON THE
 DRAWINGS TO HELP AVOID THIS ISSUE.
  
 29) THE MICROWAVE OVEN IN THE WORK ROOM SHOWN IN
 ELEVATION 6 ON SHEET A9.50.5 DOES NOT APPEAR TO COMPLY
 WITH THE REQUIRED REACH RANGES OF FBC ACCESSIBILITY
 SECTIONS 308, 309.3 AND 804.6.2.
  
 30) SHOW COMPLIANCE FBC ACCESSIBILITY SECTION 242 FOR
 ACCESSIBLE ENTRY INTO THE POOL OR SPECIFY ON THE PLANS
 WHY IT IS NOT REQUIRED. COMMUNITY POOLS THAT ARE
 ASSOCIATED WITH A PRIVATE RESIDENTIAL COMMUNITY THAT DO
 NOT RECEIVE GOVERNMENTAL FINANCIAL ASSISTANCE OR
 SPONSORSHIP AND ARE LIMITED TO THE EXCLUSIVE OF
 RESIDENTS AND THEIR GUESTS ARE NOT COVERED BY THE ADA
 ACCESSIBILITY REQUIREMENTS, INCLUDING PROVISIONS FOR
 POOL LIFTS OR SLOPED ENTRIES. IF A SWIMMING POOL
 LOCATED IN A RESIDENTIAL COMMUNITY IS MADE AVAILABLE TO
 THE PUBLIC FOR RENTAL OR USE IT IS REQUIRED TO COMPLY
 WITH TITLE II OF THE ADA. SPECIFY ON THE PLANS THE
 FORMER OR SHOW COMPLIANCE WITH THE LATTER STATEMENTS.
 SEE DECLARATORY STATEMENT, DS 2013-011. (NOTE: A
 SEPARATE PERMIT WILL BE REQUIRED FOR THE POOL.)
  
 31) THE MAXIMUM DISTANCE FROM THE WATER'S EDGE OF THE
 SWIMMING POOL TO THE RESTROOMS IS NOT SHOWN CORRECTLY
 ON THE PLAN SHEET ALS.6.1. FBC454.1.6.1 THE ENTRY DOORS
 OF ALL RESTROOMS SHALL BE LOCATED WITHIN A 200-FOOT (60
 960 MM) WALKING DISTANCE OF THE NEAREST WATER'S EDGE OF
 EACH POOL SERVED BY THE FACILITIES. PLEASE CORRECT.
  
 32) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED.
  
 33) FBC 107.3.4.1 DEFERRED SUBMITTALS. (I NOTED THAT
 THERE IS A LIST OF DEFERRED SUBMITTALS AND SEPARATE
 PERMITS ON SHEET ALS.0.1) FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 34) SHOW COMPLIANCE WITH FBC SECTION 1207 SOUND
 TRANSMISSION, 1207.2 AIR-BORNE SOUND AND 1207.3
 STRUCTURE-BORNE SOUND. TEST REPORTS WILL NEED TO BE
 SUBMITTED FOR THE SOUND INSULATION THAT WILL BE
 INSTALLED UNDER FINISH FLOORING.
  
 35) IN ORDER TO VERIFY THE BUILDING VALUATION, PLEASE
 PROVIDE AREA TABULATIONS FOR THE ENTIRE BUILDING.
 PLEASE SEPARATE AREA TABULATIONS BY OCCUPANCY TYPE. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 36) SEPARATE PERMITS, REVIEWS AND FEES ARE REQUIRED FOR
 SOME ITEMS THAT MAY HAVE BEEN INCLUDED IN THE VALUE FOR
 THIS PROJECT. ITEMS SUCH AS FIRE ALARM, FIRE SPRINKLER,
 LOW VOLTAGE, LANDSCAPING, IRRIGATION AND ALL ITEMS
 OTHER THAN BUILDING, MECHANICAL, ELECTRIC AND PLUMBING.
 PLEASE PROVIDE A COST BREAKDOWN SO THAT WE CAN DEDUCT
 THESE ITEMS FROM THE PERMIT VALUE SO THAT YOU WILL NOT
 BE CHARGED TWICE FOR THE SAME ITEM.
  
 37) THE P.B.C. PROPERTY APPRAISER SHOWS THIS PROJECT IS
 LOCATED ON A LARGER PARCEL THAN THE SITE PLAN AND
 SURVEY THAT WAS SUBMITTED. IS THIS PARCEL BEING
 SUBDIVIDED OR TO REMAIN AS ONE PARCEL WITH TWO
 BUILDINGS ON IT? PLEASE CLARIFY.
  
 38) THE ADDRESS OF THE PROJECT HAS BEEN CHANGED TO 345
 BANYAN BLVD. PLEASE CHANGE THE ADDRESS IN THE TITLE
 BLOCK OF THE PLANS. THE DESCRIPTION OF THE PROJECT AS
 PARKING LOT REDEVELOPEMENT IN THE TITLE BLOCK IS NOT
 SPECIFIC. A MORE ACCURATE DISCRIPTION WOULD BE A NEW
 RESIDENTIAL HIGH RISE BUILDING AND PARKING GARAGE. FBC
 107.2.1
  
 39) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 ****PROVISOS****
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE
 FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS
 SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR
 PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS,
 STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS
 REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW
 AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION.
  
 COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A PDF
 VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL.
  
 AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR
 TO C.O.
  
 SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED
 TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS
 TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE
 POUR.
  
 A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED
 TO BE PROVIDED PRIOR TO INSTALLATION.
  
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  