| 2021-02-12 16:05:50 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20101378 |
| | 2/12/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: PLEASE PROVIDE THE TOTAL DEVELOPED LENGTH |
| | OF THE SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET- |
| | THE BBQ GRILL- SEE SECTION G2413.4.1 FBC RES. CORRECT |
| | THE 80 FT. LONGEST RUN NOTE. |
| | |
| | 2) GAS RISER: SHOW THE TYPE AND SIZE OF PIPE FROM THE |
| | METER TO THE FIRST RISER TEE, AND FROM THE 1ST RISER |
| | TEE TO THE 2ND RISER TEE- SECTIONS G2413.4.2 FBC RES. |
| | |
| | 3) GAS RISER: PROVIDE THE SIZING TABLE USED FOR THE |
| | LOW-PRESSURE SYSTEM- G2413.3 & G2413.4 FBC RES. |
| | |
| | 4) GAS RISER: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR |
| | THE NEW REGULATORS MARKED OR HIGHLIGHTED TO SHOW WHICH |
| | MODEL IS SELECTED, THE INLET AND OUTLET PIPE SIZES AND |
| | PRESSURES AND ORIFICE SIZES- SECTION G2621 FBC RES. |
| | PLEASE NOTE THAT THE SPECS MAY BE DEFERRED AND BE |
| | ONSITE AT TIME OF INSPECTION. |
| | |
| | 5) GAS RISER: PLEASE LABEL ALL GAS-FIRED EQUIPMENT AND |
| | APPLIANCES SHOWN AS EITHER NEW OR EXISTING. PLEASE NOTE |
| | I COULD NOT LOCATE RECORDS OF PREVIOUS GAS PERMITS FOR |
| | PIPING OR APPLIANCES WHICH MAY RESULT IN COMPLETE |
| | INSPECTION OF THE SYSTEM AND APPLIANCE INSTALLATIONS- |
| | SECTION 105.1 AND 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |