Plan Review Notes
Plan Review Notes For Permit 20101376
Permit Number 20101376
Review Stop E
Sequence Number 3
Notes
Date Text
2022-04-26 09:17:27ELECTRIC REVIEW FAILED
 1) PREVIOUS COMMENTS NOT ADDRESSED,PLEASE PROVIDE PANEL
 SCHEDULE OR LOAD CALCULATION FOR PANEL PL6 AND UPSTREAM
 PANELS, WIRE SIZES FOR EQUIPMENT DISCONNECTS, WHICH
 CARSTACKERS ARE SERVED BY EACH DISCONNECT AND OTHER
 RELEVANT INFORMATION TO CONVEY THE EXACT SCOPE OF THE
 PROJECT. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved