Plan Review Notes
Plan Review Notes For Permit 20101376
Permit Number 20101376
Review Stop B
Sequence Number 2
Notes
Date Text
2021-05-27 12:22:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101376
 ADD: 360 S. ROSEMARY AVE. 8TH FLOOR PARKING 64 GARAGE
 CAR LIFTS.
 CONT: PARK PLUS FL INC.
 TEL: 954-929-7511
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. MAY 27TH/ 2021
 ACTION: DENIED
  
 NOTE, THE RESPONSE SHEET APPEARS TO BE FROM THE
 CONTRACTOR AND NOT THE DESIGN PROFESSIONAL VIRAPHPNH
 SOUKAMNEUTH THE P. E. FOR THIS PROJECT. THE RESPONSE
 COMMENTS 3-5 STATE REFER TO THE ATTACHED ADDENDUM.
 THERE WAS NO ADDENDUM IN THE 2ND SUBMITTAL.
  
 1-2) COMPLIED.
  
 3) 2ND REQUEST. SHEET MP1.0 SHOWS THE 64 CAR LIFTS.
 WHEN VIEWING THE LIFTS APPROXIMATELY 53 & 54 IT APPEARS
 THESE ARE DOUBLE LIFTS JUST LIKE THE REMAINDER OF THE
 LIFTS. WHEN YOU REFER BACK TO THE MASTER PERMIT
 18090469-PAGE AE4.08 THE ENLARGED 8TH FLOOR PLAN
 DIRECTLY ACROSS FROM THE ELEVATOR BANK THE MASTER
 PERMIT SHOWS (2) ACCESSIBLE PARKING SPACES WITH ACCESS
 AISLES. IT WOULD APPEAR THAT THE 2 ACCESSIBLE PARKING
 SPACES AND ACCESS AISLES NEEDS TO BE UPDATED AND SHOWN
 ON THE LIFT PLAN AS WELL. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED, DISCREPANCY IN THE PLANS.
  
 4) 2ND REQUEST. UNDER THE MASTER BUILDING PERMIT FOR
 THIS BUILDING (18090469) THE PARKING SPACES 626-629 ARE
 SET UP FOR ELECTRIC CAR PARKING, DOES THIS MEAN THAT
 FOR THESE SAME PARKING SPACES THERE WILL BE CHARGING
 STATIONS FOR BOTH THE UPPER AND LOWER
 PARKING SPACES THAT WAS PROVIDED BY THE LIFT. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) 2ND REQUEST. SHEET AE4.08 SHOWS THE WEST PALM BEACH
 CITY STANDARD (MARKING WITH DOUBLE LINE) PARKING
 SPACES, WILL THIS FLOOR COMPLY WITH THE CITY STANDARD
 PARKING SPACE AND ACCESSIBLE PARKING SPACES? ACCESSIBLE
 PARKING SPACE / STALL PAINTING.
 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES.
 EACH PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL
 BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN
 ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 6) COMPLIED
  
 7) 2ND REQUEST. PLEASE PROVIDE TO WHAT STANDARD THE CAR
 LIFTS HAVE TO MEET. CAR LIFTS DO NOT NEED TO MEET THE
 DEFINITION OF ELEVATORS AND MEET THE EXCEPTION FOUND
 UNDER SECTION 3001.6 EXCEPTION 19. OF THE 2017 FBC-B.
 THIS INFORMATION NEEDS TO SHOW ON THE PLANS.
  
 8) SEMI- COMPLIED, WITH MSDS SHEETS. SHEET MP0.0 DOES
 HAVE A NEW HYDRAULIC POWER PACK BUT THE RESPONSE LETTER
 DOES NOT ANSWER THE QUESTIONS THAT WERE PRESENTED.
 PLEASE PROVIDE THE MSDS SHEETS FOR THE HYDRAULIC FLUID
 THAT APPEARS TO HAVE A COMMON PUMP. PLEASE ALSO SHOW
 THE TOTAL GALLONS OF HYDRAULIC FLUID THAT IT TAKES FOR
 THE WHOLE SYSTEM AND BEING STORED IN A CLOSED SYSTEM.
 2017 FBC-B TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITIES
 PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A
 PHYSICAL HAZARD. ALSO SEE 307.1.1(3). THIS INFORMATION
 NEEDS TO SHOW ON THE PLANS.
  
 9) 2ND REQUEST. THE PLAN SHEET MP2.0 DETAIL 4 INDICATES
 THE USE OF SILKA ANCHORFIX EPOXY ADHESIVE TO THE
 UNDERSIDE OF THE LEG. SEE NOTES FOR APPLICATION
 INSTRUCTIONS. FURTHER DOWN THE PAGE THERE ARE TO ANCHOR
 NOTES:
 NOTE 1. USE ADHESIVE FOR POST TENSION SLAB (DETAIL 3.
 NOTE 2. USE POST INSTALLED ANCHOR FOR REINFORCED
 CONCRETE SLAB. DETAIL 3A.
 PLEASE NOTE DETAIL 3 ONLY STATES SEE ASD REACTIONS @
 TABLE 2.0 (END LEGS). THERE IS NO ADDITIONAL
 INFORMATION BEEN SUBMITTED ON THE ADHESIVE, WHERE IT IS
 SUPPOSED TO BE APPLIED, WHAT SURFACE AREA IT IS TO BE
 SUPPLIED AND THE HOLDING POWER OF THE ADHESIVE WHEN
 CURED. THERE IS NO INFORMATION ON THE PRODUCT SILKA
 ANCHORFIX EPOXY NOR IS THERE EVIDENCE IT HAS BEEN
 REVIEWED BY THE DESIGNER OF RECORD WITH THEIR APPROVAL
 OF A SHOP DRAWING STAMP OF APPROVAL BEFORE BEING
 SUBMITTED TO THE BUILDING DEPARTMENT.
  
 SHEET MP0.0 UNDER THE HEADING MECHANICAL FASTENERS ARE
 REQUIRED STATES ABOUT (3) HILTI KWIKBOLTS 5/8 INCH DIA.
 AND EMBEDMENT OF 4 INCHES. PLANS ARE TO BE SPECIFIC IN
 NATURE.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2020 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1ST ROUND OF COMMENTS. THE PLANS INDICATE THAT
 4-INCH-DEEP HOLES ARE TO BE DRILLED INTO THE POST
 STRESSED DECK. PLEASE PROVIDE HOW WILL THE LOCATION OF
 THE TENDONS IN THE SLAB BE FOUND? IF A TENDON IS NICKED
 WHAT IS THE REPAIR? 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  