| Plan Review Notes For Permit 20101376 |
| Permit Number |
20101376 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-04 14:46:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE PROPOSED LIFTS WERE NOT INCLUDED IN THE MASTER | | | PERMIT FIRE PROTECTION PLAN; 18090469, NOR FIRE | | | SPRINKLER SHOP DRAWINGS; 20020533. | | | | | | PLEASE PROVIDE AN APPLICABLE EOR REVIEW OF THE PROPOSED | | | AND THE TYPE OF FIRE PROTECTION THAT WILL BE PROVIDED. | | | | | | | | | | | | 2) THE MASTER PERMIT AND/OR THE SHOP DRAWINGS SHALL BE | | | REVISED WITH ALL APPLICABLE HYDRAULIC CALCULATIONS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|