Plan Review Notes
Plan Review Notes For Permit 20101376
Permit Number 20101376
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-12-04 14:46:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED LIFTS WERE NOT INCLUDED IN THE MASTER
 PERMIT FIRE PROTECTION PLAN; 18090469, NOR FIRE
 SPRINKLER SHOP DRAWINGS; 20020533.
  
 PLEASE PROVIDE AN APPLICABLE EOR REVIEW OF THE PROPOSED
 AND THE TYPE OF FIRE PROTECTION THAT WILL BE PROVIDED.
  
  
  
 2) THE MASTER PERMIT AND/OR THE SHOP DRAWINGS SHALL BE
 REVISED WITH ALL APPLICABLE HYDRAULIC CALCULATIONS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  