| 2020-12-01 08:09:10 | SFR REMODEL AND ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE SMOKE AND CARBON MONOXIDE DETECTOR |
| | LOCATIONS THROUGHOUT THE HOUSE PER FBC R314.2.2 |
| | ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. AND FBC R315.1 |
| | CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES. |
| | 2) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION TO |
| | COMPLY WITH FBC R807.1 |
| | 3) PRODUCT APPROVALS PROVIDED FOR THE WINDOWS AND DOORS |
| | = THE PRODUCT APPROVAL NUMBERS DO NOT MATCH THE NUMBERS |
| | SHOWN ON THE DRAWINGS WINDOW AND DOOR SCHEDULES -PLEASE |
| | REVISE THE DRAWINGS OR PROVIDE THE PRODUCT APPROVALS |
| | SHOWN ON THE DRAWINGS. |
| | |